MA-COM 901X

Phase Sequence Relays
WILMAR™ Protective Relays – 900 Series
Function: 47
Phase sequence relays are designed to monitor
the correct phase rotation of a three phase
system. Several models are avilable from 50 Hz,
60 Hz, and 400 Hz with voltages up to 575 volts.
High shock relay output and reverse contacts are
also available.
Operation:
The relay remains de-energized when voltage in
the proper phase sequence (A, B, C) is applied,
the relay is energized when voltage with incorrect
sequence (A, C, B) is applied.
3 5/32
2 3/4
1
3 /4
6
5 /1
2
2
1/8
6
11/1
2
PART NUMBER SELECTION
6 - 32 x 3/8 studs
4 places
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PRODUCT SPECIFICATIONS
Part Number
900 Series
Input Voltage .................................... See Part Number Selection
Output Contacts
SPDT
Contact Ratings ................................ 5 amp resitive at 120 Vac or 28 Vdc
PART NUMBER SELECTION
Sample Part No.
901X
Type:
900-3X = 120 VAC, 60 Hz, 3 phase,L-L
910X = 190-520 VAC, 60 Hz, 3 Phase, L-L
900-2X = 208-230, 50/60 Hz, 3 Phase
900X = 230 VAC, 60 Hz, 3 phase, L-L
901X = 460 VAC, 60 Hz, 3 phase,L-L
Mounting:
X = Flange
Blank - Stud
Consult factory for additional models and options
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)