ETC MTL5511

EPS5511-2
Hazardous area
MTL5511 SWITCH/
PROXIMITY DETECTOR
INTERFACE
Safe area
To earth
leakage
detector
Switch-type sensors
require resistors
if LFD is selected
single channel, with line fault detection
6
5
4
680W
22kW
The MTL5511 enables a safe-area load to be controlled by a switch
or proximity detector located in a hazardous-area. When selected,
open or short circuit conditions in the field wiring are detected by
the line-fault-detect (LFD) facility and also indicated on the top of the
module. Phase reversal for the channel is selected by a switch on
the side of the module and output is provided by changeover relay
contacts.
10
11
12
Output
13
14
Vs–
Vs+
20 to 35V dc
Terminal
SPECIFICATION
1
2
3
10
11
12
13
14
See also common specification
Number of channels
One
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200μA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. A line fault is
indicated by an LED. The channel output relay is de-energised if
an input line fault is detected.
Open-circuit alarm on if Iin < 50μA
Open-circuit alarm off if Iin > 250μA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
3
2
– 1
+
7
8
9
Function
Input –ve
Input +ve
To earth leakage detector*
Output normally-closed contact
Common
Output normally-open contact
Supply –ve
Supply +ve
* Signal plug HAZ1-3 is required for access to this function
LED indicators
Green: power indication
Yellow: channel status, on when output is energised
Red:
LFD indication, on when line fault is detected
Maximum current consumption
25mA at 24V
Power dissipation within unit
0.6W at 24V
Safety description (each channel)
Vo =10.5V I o =14mA Po =37mW Um = 253V rms or dc
Note: Resistors must be fitted when using the LFD facility with a contact
input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Safe-area output
Single pole relay with changeover contacts
Note: reactive loads must be adequately suppressed
Relay characteristics
Response time:
10ms maximum
Contact rating:
250V ac, 2A, cosØ >0.7
40V dc, 2A, resistive load
The given data is only intended as a product description and should not be regarded as a legal warranty of properties or guarantee. In the interest of further
technical developments, we reserve the right to make design changes.
EUROPE (EMEA)
Tel: +44 (0)1582 723633
Fax: +44 (0)1582 422283
AMERICAS
Tel: +1 281 571 8065
Fax: +1 281 571 8069
ASIA PACIFIC
Tel: +65 6 487 7887
Fax: +65 6 487 7997
E-mail: [email protected]
Web site: www.mtl-inst.com
Jan 2009
EPS5500SYS-2
MTL5500 SERIES
COMMON
SPECIFICATION
DIMENSIONS (mm)
Optional TH5000 tag holder for individual
isolator identification.
Accepts tag label 25 x 12.5 ±0.5mm, 0.2mm thick
FLT
OPD
OPC
OPB
OPA
PWR
109.8
Please go to our website at www.mtl-inst.com for the latest information
regarding safety approvals, certificates and entity parameters.
15.8 +/– 0.2
104.8
118.8
Connectors
Each MTL5500 unit is supplied with signal connectors, as
applicable.
When using crimp ferrules for the hazardous and nonhazardous (safe) signal connectors the metal tube length should
be 12mm and the wire trim length 14mm.
Isolation
250V rms, tested at 2200V rms minimum, between safe-area,
hazardous-area and power supply terminals
50V ac or dc between safe-area circuits where applicable.
Supply voltage
20 – 35V dc
Location of units
Safe area
Terminals
Accepts conductors of up to 2.5mm2 stranded or single-core
Mounting
MTL5500 series backplanes
Ambient temperature limits
–20 to +60°C (–6 to +140°F) operating
–40 to +80°C (–40 to +176°F) storage
Humidity
5 to 95% relative humidity
Weight
110g approximately (except where indicated)
SAFE
123.6
HAZ
Top of DIN rail
HART® is a registered trademark of HART Communication Foundation
The given data is only intended as a product description and should not be regarded as a legal warranty of properties or guarantee. In the interest of further
technical developments, we reserve the right to make design changes.
EUROPE (EMEA)
Tel: +44 (0)1582 723633
Fax: +44 (0)1582 422283
AMERICAS
Tel: +1 281 571 8065
Fax: +1 281 571 8069
ASIA PACIFIC
Tel: +65 6 487 7887
Fax: +65 6 487 7997
E-mail: [email protected]
Web site: www.mtl-inst.com
Jan 2009