ETC MTL5114P

Hazardous area
MTL5113P AND 5114P
FAILSAFE
SWITCH/PROXIMITY
DETECTOR INTERFACE
LFD option
1kW
With the MTL5113P/5114P, a fail-safe switch/proximity detector
located in the hazardous area can control an isolated fail-safe
electronic output. The MTL5113P units provide line-fault detection
alarm contacts. The MTL5113P and MTL5114P are for use with P + F
TÜV approved fail-safe sensors.
Safe area
6
5
4
3
+ 2
– 1
10kW
7
8
9
10
11
12
13
14
or switch inputs,
sistors must be fitted
–
+
Fail-safe
output
LFD*
Vs–
Vs+
20 to 35V dc
*MTL5113P only
SPECIFICATION
(For both MTL5113P and MTL5114P unless otherwise indicated.)
See also common specification
Terminal
1
2
7
8
11
12
13
14
Number of channels
One
Location of switches
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Location of proximity detector
Zone 0, IIC, T4–6, hazardous location
Div 1, Group A, hazardous location
Voltage applied to sensor
8.6V dc max from 1kΩ
Input/output characteristics
Input value in sensor circuit
Fail-safe
output
Operation
LFD contacts
(MTL5113x
only)
MTL5113P, MTL5114P
2.9mA<Is<3.9mA
ON
Normal
CLOSED
MTL5113P, MTL5114P
Is<1.9mA & Is>5.1mA
OFF
Normal
CLOSED
MTL5113P
Is<50µA
OFF
Broken line
OPEN
MTL5113P
Is>6.6mA
OFF
Shorted line
OPEN
Function
Input –ve
Input +ve
Output –ve
Output +ve
LFD (MTL5113P only)
LFD (MTL5113P only)
Supply –ve
Supply +ve
Power dissipation within unit
MTL5113P
MTL5114P
1.4W
1.2W
at 20V dc
1.5W
1.3W
at 24V dc
2.0W
1.4W
at 35V dc
Safety description
9.7V, 30mA, 70mW, Ci=33nF, Li=0mH
Weight
160g approx.
Note: switch-type sensors must be fitted with resistors as shown
Note: Is = sensor current
Fail-safe electronic output
Output on: > 22.8V
Output off: 0V dc, max <5V dc
Load: 2.4kΩ to 10kΩ
Maximum on-state current: 11mA
Short-circuit current: 25mA
Line fault detection (LFD), MTL5113P only
Relay output for line fault (contacts open when line fault detected)
Switch characteristics: 0.3A 110V ac/dc, 1A 30V dc, 30W/33VA
LED indicators
Amber: one provided for output status, ON when fail-safe output
is energised
Green: one provided for power indication
Red: one provided for LFD, ON when line fault is detected
(MTL5113P only)
Power requirements, Vs
MTL5113P
MTL5114P
80mA
70mA
at 20V dc
70mA
60mA
at 24V dc
65mA
45mA