MA-COM CDEUL

Catalog: 1654986
Issue Date: 06.2011
Corcom Facility EMI Filters Product Guide
CDEUL Series - Extended Range Buffer Networks (Inductive Input)
CDEUL Series
Filter Cabinet
60 Hz Models Only
• Modified NEMA I, constructed of not less than #14
gauge CRS with galvanized bulkhead
• Blue epoxy finish to all non-conductive surfaces
• R.F. Radiation of the shielded (load) compartment
greater than 100 dB from 14 kHz to 10 GHz
• Front cover access, dual cover design
• Filter inserts pre-wired to standoffs and lugs
• Lifting hooks and mounting tabs
• Legs for floor mount available (see page 24)
Individual Filters
• Sealed components with welded and/or soldered
seams
• Constructed of not less than #16 gauge steel with
corrosion resistant plating
• Bleeder resistor to eliminate shock hazard provided
• HEMP Surge arrestors provided upon request‡
Electrical Characteristics
Voltage Drop:
Less than 1% @ unity power factor
Overload:
140% of rated current for 15 minutes
Harmonic Distortion:
Less than 2% @ full rated current
Dielectric Withstanding Voltage:
Per MIL-PRF-15733 and UL1283
D.C. Insulation Resistance:
Per MIL-STD-202, Method 302
Terminal Strength:
Per MIL-STD-202, Method 211, Condition E
Temperature Rise:
Shown with optional legs
Center mounting bracket not installed on all sizes
Per MIL-PRF-15733 and UL1283
R.F. Radiation:
100 dB minimum shielding effectiveness
How to Order:
CDEUL 4 01000 A6 -S -L
Insertion Loss:
Legs
Surge Arrestors (optional)
Voltage/Frequency
100 dB from 14 kHz - 10 GHz per MIL-STD-220A, under
load condition, using extended range buffer networks
over the frequency range of 14 kHZ - 20 MHz
A6 - 120/208V, 60Hz
B6 - 277/480V, 60Hz
A4 - 120/208V, 400Hz
Current Rating 2
Applicable Publications:
# of Filtered Phases
Series
MIL-PRF-15733 — Filters, radio interference
MIL-STD-202 — Test methods for Components
Examples:
CDEUL401000A6-S-L =
MIL-STD-220A — Test method of Insertion Loss
MIL-STD-188-125 — HEMP
MIL-STD-285 — Test method for Shielding Effectiveness
NFPA 70-1987 — National Electric Code
486A - 1983 — Wire Connectors and Lug
UL1283 — UL standard for EMI Filters
1
4, 1000A CDEUL, 120/280V filters in cabinet
with surge arrestors and legs
CDEUL300030B6 =
3, 30A CDEUL, 277/480V filters in cabinet
Note 1:
Surge Arrestor for A6/A4* Models: V251BA60
Surge Arrestor for B6 Models: V481BA60
Note 2:
Current configuration listed as 5 digits with leading zeros
‡ Intended for HEMP applications <150A. For filters rated >225A refer
to the new TECUL Series on page 14.
12
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric
equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
USA Cust. Svc.:
Corcom Prods:
1-800-468-2023
1-847-680-7400
te.com
corcom.com
Catalog: 1654986
Issue Date: 06.2011
Corcom Facility EMI Filters Product Guide
CDEUL Series - ERBN (Inductive Input) (continued)
Mounting Brackets
E
A
C
Removable Cover
RF
Gasket
Removable Individual
Phase Filters
B
D
Corcom Facility EMI Filters — NEMA Cabinet Style
Center mounting
bracket not installed
on all sizes
2
Removable Cover
For optional legs, refer to page 24
Area for Conduit Penetration
Recommended torque for fasteners on removable cover: 25 in. lb. ± 3 in. lb.
# Filtered phases
@ rated current
2 @ 10A
3 @ 10A
4 @ 10A
2 @ 30A
3 @ 30A
4 @ 30A
2 @ 60 or 100A
3 @ 60 or 100A
4 @ 60 or 100A
2 @ 150A
3 @ 150A
4 @ 150A
A
14.0
355.6
20.0
508.0
26.0
660.4
16.0
406.4
23.0
584.2
30.0
762.0
16.0
406.4
23.0
584.2
30.0
762.0
16.0
406.4
23.0
584.2
30.0
762.0
Dimensions
B
C
D
30.0
6.0
22.0
762.0 152.4 558.8
30.0
6.0
22.0
762.0 152.4 558.8
30.0
6.0
22.0
762.0 152.4 558.8
38.0
8.0
26.0
965.2 203.2 660.4
38.0
8.0
26.0
965.2 203.2 660.4
38.0
8.0
26.0
965.2 203.2 660.4
44.0
10.0
32.0
1117.6 254.0 812.8
44.0
10.0
32.0
1117.6 254.0 812.8
44.0
10.0
32.0
1117.6 254.0 812.8
54.0
14.0
42.0
1371.6 355.6 1066.8
54.0
14.0
42.0
1371.6 355.6 1066.8
54.0
14.0
42.0
1371.6 355.6 1066.8
Max. Operating Voltage
A6:
120/208V, 60 Hz
B6:
277/480V, 60 Hz
A4*:
120/208V, 400 Hz
Weight
E
(Pounds/KG)
16.0
95
406.4
43.1
22.0
100
558.8
45.4
28.0
120
711.2
54.4
18.0
170
457.2
77.1
25.0
240
635.0
108.9
32.0
300
812.8
136.1
18.0
240
457.2
108.9
25.0
310
635.0
140.6
32.0
400
812.8
181.4
18.0
320
457.2
145.1
25.0
430
635.0
195.0
32.0
650
812.8
294.8
# Filtered phases
@ rated current
A
16.0
2 @ 225A
406.4
23.0
3 @ 225A
584.2
30.0
4 @ 225A
762.0
22.0
2 @ 400A
558.8
30.0
3 @ 400A
762.0
38.0
4 @ 400A
965.2
38.0
2 @ 800A
965.2
56.0
3 @ 800A
1422.4
72.0
4 @ 800A
1828.8
56.0
2 @ 1000 or 1200A
1422.4
82.0
3 @ 1000 or 1200A
2082.8
106.0
4 @ 1000 or 1200A
2692.4
Dimensions
B
C
D
54.0
14.0
42.0
1371.6 355.6 1066.8
54.0
14.0
42.0
1371.6 355.6 1066.8
54.0
14.0
42.0
1371.6 355.5 1066.8
64.0
26.0
61.5
1625.6 660.4 1562.1
64.0
26.0
61.5
1625.6 660.4 1562.1
64.0
26.0
61.5
1625.6 660.4 1562.1
70.0
26.0
67.5
1778.0 660.4 1714.5
70.0
26.0
67.5
1778.0 660.4 1714.5
70.0
26.0
67.5
1778.0 660.4 1714.5
70.0
26.0
67.5
1778.0 660.4 1714.5
70.0
26.0
67.5
1778.0 660.4 1714.5
70.0
26.0
67.5
1778.0 660.4 1714.5
Weight
E
(Pounds/KG)
18.0
380
457.2
172.4
25.0
520
635.0
235.9
32.0
700
812.8
317.5
24.0
800
609.6
362.9
32.0
1100
812.8
498.9
40.0
1400
1016.0
635.0
40.0
1400
1016.0
635.0
58.0
2100
1473.2
952.5
74.0
2600
1879.6
1179.3
58.0
2000
1473.2
907.2
84.0
3000
2133.6
1360.8
108.0
3800
2743.2
1723.6
*400Hz filters available upon request. Will require external power factor correction coil.
Please contact TE Connectivity Application Engineering 847-573-6517.
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric
equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
USA Cust. Svc.:
Corcom Prods:
1-800-468-2023
1-847-680-7400
13
te.com
corcom.com