BOURNS 1420-PV-1000

*R
oH
S
CO
M
PL
IA
N
T
Features
■ Hybrid MOV/GDT design
■ Thermal disconnect
■ No leakage over life
■ Standards compliance:
■ DIN Rail mountable
■ RoHS compliant*
■ 40 kA maximum impulse current rating
■ Minimal footprint within DC power system
■ Uni-block design with replaceable modules
■ Visual fault indicator
1420 Series DC Power SPD for Photovoltaic Applications
General Information
Electrical Diagram
The Bourns® Model 1420 Series is a DC power Surge Protective
Device (SPD) designed to protect power systems operating up
to 1200 Vdc. The unique hybrid MOV/GDT design provides an
enhanced level of protection against the effects of direct or
indirect lightning.
-
+
MI
Ft
t
V:
G:
Ft :
C:
t° :
G
o
V
V
V
High energy MOV
Heavy duty gas discharge tube
Thermal fuse
Remote signaling contact
Thermal disconnection system
C
Electrical Characteristics
Model No.
Characteristic
1420-PV-1000
Network Voltage (Un) dc
Protection Mode
Max. Operating Voltage (Uc) dc
IEC/UL Nominal Discharge Current (In)
15 x 8/20 µs impulses
Max. Discharge Current (Iimp)
10/350 µs max.
Max. Lightning Current by Pole (Imax)
Protection Level @ In (Up)
Residual Voltage at 5 kA
Operating Current (Ic)
Leakage Current at Uc
Follow Current (If)
1000 Vdc
MC/MD1
1200 Vdc
20 kA
-40 kA
< 3.6 V
< 2.6 kV
None
None
Note 1: MC = Common Mode (+/PE or -/PE) and MC/MD = Common Mode and Differential Mode (±).
General Characteristics
Model No.
Characteristic
1420-PV-1000
Thermal Disconnector
Dimensions
Connection
Disconnection Indicator
Mounting
Remote Signaling
Enclosure Material
Internal
See Product Dimensions
By Screw Terminal: #4 AWG max.
1 Mechanical Indicator
DIN Rail, 35 mm Symmetrical
250 V / 0.5 A (AC)
125 V / 3 A (DC)
Thermoplastic UL 94V0
Environmental Characteristics
Model No.
Characteristic
1420-PV-1000
Operating Temperature
Environmental Rating
-50 °C to +85 °C
IP 20
*RoHS Directive 2002/95/EC Jan. 27, 2003 including annex and RoHS Recast 2011/65/EU June 8, 2011.
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.
Applications
■ DC power applications up to 1200 Vdc
1420 Series DC Power SPD for Photovoltaic Applications
Product Dimensions
Standards Compliance
67.0
(2.638)
IEC61643-1 - International ..........Low Voltage SPD - Test Class II
NF EN 61643-11 - France ...........Low Voltage SPD - Test Class II
UL1449 3rd Edition - USA ....................... Type 4, Type 2 Location
CSA C22.2 No. 8-M1986 ............... Class 9091 32, Class 9091 92
DIN EN61643-11 - Germany ...................... Surge Arrestor Type 2
54.0
(2.126)
+
DC Surge
Protector
90.0
(3.543)
DIMENSIONS:
–
How To Order
SPD1420-xxx
Uc
In
Imax
Up
1420 - PV - 1000
Series
Application Code
PV = Photovoltaic
Network Voltage
1000 = 1000 Vdc
MM
(INCHES)
Asia-Pacific: Tel: +886-2 2562-4117 • Fax: +886-2 2562-4116
Europe: Tel: +41-41 768 5555 • Fax: +41-41 768 5510
The Americas: Tel: +1-951 781-5500 • Fax: +1-951 781-5700
www.bourns.com
REV. 05/13
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.