Features
■ 100 kA max. discharge current rating
■ Compact design ideal for limited spaces
■ Multi-pole uni-block design
■ Standards compliance:
■ DIN Rail mountable
■ RoHS compliant*
■ UL 60691 compliant integrated thermal
disconnect
■ Visual fault indicator
■ Remote signalling capability
1210 Series Heavy Duty AC Surge Protective Device
Electrical Diagram
L/N
The Bourns® Model 1210 Series is a heavy duty Surge Protective Device (SPD)
designed to protect high risk electrical service entrance and branch panels. This SPD is
intended to be installed at the front end of the installation, in the main switchboard, close
to sensitive terminals or in installations without LPS (lightning rods).
1. 4
1. 1
1. 2
General Information
C
Ft
Ft
Mi
The Model 1210 Series is a single-pole module that can be configured for both common
mode and differential mode protection in single and three phase applications up to 600 V.
V
V
V : High energy varistor
Ft : Thermal fuse
C : Remote signaling contact
t° : Thermal disconnection system
Mi : Disconnection indicator
Electrical Characteristics
Model No.
Characteristic
1210-xS-120
120/240 V,
120/208 V
AC Network
Connection Mode
AC System
Max. Operating Voltage (MCOV)
TOV Withstand
Leakage Current at Uc
Follow Current
UL Nominal Discharge Current (In)
15 Impulses 8/20 µs
Max. Discharge Current (Imax)
1 Impulse 8/20 µs
UL Voltage Protection Rating (VPR)
Protection Level (Up)
UL Short-Circuit Current Rating (SCCR)
150 V
230 V
1210-xS-230
1210-xS-400
220/380 V,
220/380 V,
277/480 V,
240/415 V
347/600 V
1-Pole, L-N or L-G
IT, TT, TN, Single, Split Phase, Delta, Wye
275 V
420 V
440 V
770 V
< 1 mA
None
1210-xS-600
480 V,
600 V
840 V
1117 V
20 kA
100 kA
600 V
0.9 kV
900 V
1.25 kV
1200 V
1.8 kV
3000 V
4.0 kV
1210-xS-400
1210-xS-600
100kAIC
General Characteristics
Model No.
Characteristic
1210-xS-120
Thermal Disconnector
Overcurrent Protection
Connection
Dimensions
Mounting
Remote Signal Indicator
Enclosure Material
1210-xS-230
UL 60691
Time Delay - 125 A Max.
By Screw Terminals, #6 AWG Max.
90 x 18 x 67 mm / (3.543 x 0.709 x 2.638 In.)
DIN Rail, 35 mm Symmetrical
250 V Max., 2 A
Thermoplastic UL 94V0
Environmental Characteristics
Characteristic
Operating Temperature
Operating Altitude
Relative Humidity
Environmental Rating
Model No.
1210-xS-120
1210-xS-230
1210-xS-400
1210-xS-600
-50 °C to +85 °C
13,000 ft. (4,000 m)
5 to 95 % Non-condensing, up to 100 % External
IP 20
*RoHS Directive 2002/95/EC Jan. 27, 2003 including annex and RoHS Recast 2011/65/EU June 8, 2011.
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.
Applications
■ Electrical service entrance
■ Branch panels
1210 Series Heavy Duty AC Surge Protective Device
Product Dimensions and Schematics
1210-1S-xxx
1210-2S-xxx
10.6
(.417)
67.0
(2.638)
18.0
(.709)
36.0
(1.417)
L/N
L/N
L/N
L
L/N
t°
AC Surge
Protector
90.0
(3.543)
N
Ft
Mi
Ft
SPD1210-xxx
V
Uc
In
Imax
Up
AC Surge
Protector
AC Surge
Protector
SPD1210-xxx
SPD1210-xxx
Uc
In
Imax
Up
Uc
In
Imax
Up
Mi
t°
Ft
Mi
t°
V
V
C
C
1210-3S-xxx
54.0
(2.126)
L
AC Surge
Protector
L
N
AC Surge
Protector
L/N
L/N
SPD1210-xxx
SPD1210-xxx
Uc
In
Imax
Up
Uc
In
Imax
Up
Mi
Ft
t°
AC Surge
Protector
SPD1210-xxx
Uc
In
Imax
Up
Mi
Ft
L/N
Mi
Ft
t°
t°
V
V
V
L/N
L/N
L/N
DIMENSIONS:
MM
(INCHES)
C
1210-4S-xxx
72.0
(2.835)
L
L
L
N
AC Surge
Protector
AC Surge
Protector
AC Surge
Protector
AC Surge
Protector
SPD1210-xxx
SPD1210-xxx
SPD1210-xxx
SPD1210-xxx
Uc
In
Imax
Up
Uc
In
Imax
Up
Uc
In
Imax
Up
Uc
In
Imax
Up
Ft
Mi
t°
Ft
Mi
t°
V
Ft
L/N
Mi
t°
V
Ft
Mi
t°
V
V
C
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.
1210 Series Heavy Duty AC Surge Protective Device
Standards Compliance
How To Order
IEC61643-1 - International ................................ Class I, Class II
EN 61643-11 - Europe ....................................... Class I, Class II
NF EN 61643-11 - France ................................. Class I, Class II
UL1449 3rd Edition - USA .................... Type 4, Type 2 Location
UL1449 3rd Edition - Canada ............... Type 4, Type 2 Location
CSA C22.2 No. 8-M1986 ............ Class 9091 32, Class 9091 92
RoHS ..............................................RoHS Directive 2002/95/EC
Jan. 27, 2003 including annex and
RoHS Recast 2011/65/EU June 8, 2011
1210 - x S - xxx
Series
Configuration
1 = One Protected Pole
2 = Two Protected Poles
3 = Three Protected Poles
4 = Four Protected Poles
Remote Signalling Code
S = Remote Signalling
Operating Voltage
120 = 120/240 V, 120/208 V
230 = 220/380 V, 240/415 V
400 = 220/380 V, 277/480 V, 347/600 V
600 = 480 V, 600 V
Asia-Pacific: Tel: +886-2 2562-4117 • Fax: +886-2 2562-4116
EMEA: Tel: +36 88 520 390 • Fax: +36 88 520 211
The Americas: Tel: +1-951 781-5500 • Fax: +1-951 781-5700
www.bourns.com
REV. 03/15
Specifications are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specific applications.