Xtralis ® VLF VLF-500 Features • Out-of-the-Box Installation and Commissioning • 8OWUDVRQLF$LUÀRZ6HQVLQJ • Laser-Based Absolute Smoke Detection • Pre-engineered pipe network designs • Programmable Alarm Thresholds • Clean air barrier optics protection • Instant Recognition Display • Instant Fault Finder™ • AutoLearn™ Smoke • AutoLearn™ Flow • Field Service Access Door The Xtralis VESDA VLF-500 detector is a very early warning smoke detector designed to protect small, business-critical environments of less than 5000 sq. ft. (500 m2). • Multiple Event Logging in separate logs The detector works by continually drawing air into sampling holes in a pipe QHWZRUN7KHDLULV¿OWHUHGDQGSDVVHGLQWRDGHWHFWLRQFKDPEHUZKHUHOLJKW scattering technology detects the presence of very small amounts of smoke. Detector status information is communicated on the detector display and via relays or optional interface cards. • Up to 5000 sq. ft. (500 m2) coverage* Out-of-the-box operation • FM The VLF can be installed and commissioned out-of-the-box without the need for a special interface or software programming tools. • CFE In operation, the unique Smoke Dial display provides the user with an instant understanding of a smoke event, even from a distance. Should a fault occur, WKHXVHUVLPSO\RSHQVWKH¿HOGVHUYLFHGRRUDQGDFWLYDWHVWKHInstant Fault Finder feature to determine the VSHFL¿FIDXOWFRQGLWLRQ7KLVLQIRUPDWLRQ FDQWKHQEHSDVVHGRQWRWKHLU¿UHVHUYLFHFRPSDQ\HQVXULQJWKDWVHUYLFH technicians arrive onsite fully prepared. • VdS • Event log – up to 18000 events • 2IÀLQHRQOLQHFRQ¿JXUDWLRQFDSDELOLW\ Listings/Approvals • UL • ULC • LPCB • VNIIPO • AFNOR • ActivFire • CE - EMC and CPD • EN 54-20 Ultrasonic Flow Sensing The patent-pending Ultrasonic Flow Sensing used in the VLF provides a GLUHFWUHDGLQJRIWKHVDPSOLQJSLSHÀRZUDWH7KHV\VWHPLVLPPXQHWRDLU temperature and pressure changes and is unaffected by contamination. The 9/)LVWKH¿UVWDLUVDPSOLQJVPRNHGHWHFWRUWRXVHXOWUDVRQLFÀRZVHQVLQJ Regional approvals listings and regulatory compliance vary between Xtralis VESDA product models. Refer to www.xtralis.com for the latest product approvals matrix. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com GF11236_11 page 1 of 2 Xtralis VLF ® VLF-500 6SHFL¿FDWLRQV Input Power Voltage: Current @ 24 VDC: 24 V DC Nominal (18-30 V DC) 410 mA nominal, 490 mA in alarm Dimensions (W x H x D) 978 in x 718 in x 312 in (255 mm x 185 mm x 90 mm) Weight Approx. 4.4 lbs (2 kg) IP Rating IP30 Mounting Upright, inverted or horizontal Operating Conditions† Detector Ambient: Sampled Air: Humidity: 32°F to 104°F (0°C to 40°C) 32°F to 104°F (0°C to 40°C) 5% to 95% (non-condensing) Sampling Network Maximum pipe lengths: Sampling Hole Options: 1 x 150 ft (50 m) (Max. 24 holes) 2 x 90 ft (30 m) per branch (Max. 12 holes per branch) Pre-Engineered Option or Maximum Pipe length in accordance with Pipe Modelling Design Tool (ASPIRE2™) Air Inlet Pipe Accepts both metric and American standard pipe sizes. American Pipe: IPS ¾ in, Metric: 25 mm. Area Coverage Up to 5000 sq. ft. (500 m2) depending on local codes and standards Relay Outputs FKDQJHRYHUUHOD\V)LUH$FWLRQ)DXOW&RQWDFWVUDWHG$#9'&PD[121&&RQWDFWV Cable Access 3 x 1116 in. (25 mm) cable entries (1 rear entry, 2 top entry) Cable Termination Screw Terminals 30-12 AWG (0.2-2.5 mm2) Interfaces Shown in Terminal Block Connections diagram, to right, plus an RS232 Programming Port. General Purpose Input (GPI) interface offers: Reset, Disable, Standby, Alarm set 1, Alarm set 2 and External Input functions. Alarm Threshold Setting Range Alert, Action, Fire 1, Fire 2 Individual Alarm Delays Two Alarm Threshold Settings REVIWREVP REVIWREVP 0 – 60 seconds Either time or GPI based Display • 4 Alarm State Indicators • Fault and Disabled Indicators • Smoke Level Indicator • Instant Fault Finder • Reset, Disable and Test Controls • Smoke and Flow AutoLearn Controls Event Log Up to 18000 events, time and date stamped in separate, non-volatile, logs for: Smoke Level, Flow Level, Detector Status and Faults AutoLearn Smoke & Flow $XWRPDWLFDOO\VHWDFFHSWDEOHDODUPWKUHVKROGVIRUERWKVPRNHDQGÀRZOHYHOV • Minimum 15 minutes, maximum 15 days (default 14 days) • During AutoLearn, thresholds are NOT changed from pre-set values Warranty Period 2 years Display: The display provided to the user includes a Smoke Dial and alarm and status indicators. :KHQWKH¿HOGVHUYLFHDFFHVVGRRULVRSHQ the user has access to the RESET , DISABLE , Fire Test , AutoLearn and Instant Fault Finder functions. When the Instant Fault Finder function is activated, the Smoke Dial converts to a fault indicator, with the dial segment numbers corresponding to the faults listed below. Legend of fault indicators: 1 2 3 4 5 Filter Aspirator +LJKÀRZ /RZÀRZ QD 6 7 8 9 10 ([WHUQDO'HYLFH368 Interface card Field wiring AutoLearn Fail Detector failure 1 GPI 2 GPI 3 Display TX 4 Display RX 5 Display Common Ground 6 Display Power 7 Display Power + 8 Power Return 0 VDC 9 Power In 24 VDC 10 Power Return 0 VDC 11 Power Out 24 VDC From power supply unit To next detector (if more than 1 detector per Power Supply Unit) 12 NC 13 Common Fault relay 14 NO Ordering Information: • VLF-500-00: Xtralis VESDA VLF-500 • VIC-010: VESDAnet Interface Card • VIC-020: Multifunction Control Card (MCC) 9,&0XOWLIXQFWLRQ&RQWURO&DUG0&&FZ0RQLWRUHG3RZHU2XWSXW032 • VSP-005: Filter Cartridge • VSP-715: Aspirator for VLF-500 15 NC 16 Common 18 NC 19 Common 20 NO www.xtralis.com The Americas +1 781 740 2223 Asia +852 2297 2438 Australia and New Zealand +61 3 9936 7000 Continental Europe +41 55 285 99 99 UK and the Middle East +44 1442 242 330 The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the FRPSOHWHQHVVDFFXUDF\RUUHOLDELOLW\RIWKHFRQWHQWVRIWKLVGRFXPHQW7KHPDQXIDFWXUHUUHVHUYHVWKHULJKWWRFKDQJHGHVLJQVRUVSHFL¿FDWLRQV without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any LPSOLHGZDUUDQWLHVRIPHUFKDQWDELOLW\DQG¿WQHVVIRUDSDUWLFXODUSXUSRVHDUHH[SUHVVO\H[FOXGHG This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their respective owners. <RXUXVHRIWKLVGRFXPHQWGRHVQRWFRQVWLWXWHRUFUHDWHDOLFHQFHRUDQ\RWKHUULJKWWRXVHWKHQDPHDQGRUWUDGHPDUNDQGRUODEHO This document is subject to copyright owned by Xtralis AG (“Xtralis”). You agree not to copy, communicate to the public, adapt, distribute, transfer, sell, modify or publish any contents of this document without the express prior written consent of Xtralis. Doc. no. 11236_11 Part: 30112 GAMEWELL-FCI Action relay 17 NO 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 GF11236_11 page 2 of 2 www.gamewell-fci.com Fire 1 relay