Velociti® Series
AMM-2RIF
Description
Addressable Input/Output Module
The Gamewell-FCI Velociti Series multi-function
module (AMM-2RIF) combines two relay outputs and
two monitor inputs into one device. The module is
capable of Class B supervised wiring that is used for
the monitored devices. It also contains Form C relay
contacts which allow the panel to switch the contacts
on command. There is a dedicated LED on the module for each input and output. The control panel can
use these bi-color LEDS to indicate normal, alarm
and trouble conditions.
This module is ideally suited for areas where inputs
and outputs are needed in the same location. It could
be used to function with any of the following devices:
• smoke/fire dampers • security doors
• HVAC fan
• dedicated smoke control
• non-dedicated smoke fan
By combining two (2) relay outputs and two (2) monitor inputs into one device, you can save the cost of
installing four (4) devices. This feature can be beneficial when you need to install these devices in high
rise buildings or large shopping complexes.
The two input/two output module is the same size
module as the standard single modules. It can mount
directly to a 4-inch (10.16 cm) square electrical box,
the surface mounted SMB500, or into a DNR(W)
duct housing.
Relay Contact Ratings
Current
Maximum
Load
Rating
Voltage Description Application
2A
25 VAC
PF = 0.35 Non-coded
3A
30 VDC
Resistive
Non-coded
2A
30 VDC
Resistive
Coded
0.46 A
30 VDC
Inductive
(L/R - 20ms) Non-coded
0.7 A
70.7 VAC
PF = 0.35 Non-coded
0.9 A
125 VDC
Resistive
Non-coded
0.5 A
125 VDC
PF = 0.75 Non-coded
0.3 A
125 VDC
PF = 0.35 Non-coded
AMM-2RIF
Features
•
•
•
•
•
•
Velociti® and E3 Series® are registered trademarks of Honeywell
International Inc.
Provides two (2) relay outputs and two (2)
monitor inputs in one space-saving module
Offers visual rotary, decimal switch addressing
(01-159)
Contains the following:
- Two (2) sets of Class B initiating device circuits
- Two (2) sets of Form C relay contacts
Uses bicolor LEDs for each input and output
flash, when addressed, and lights steady when
in alarm
Includes a Dip switch to manually disable one (1)
input and one (1) output
Ideal for fan, smoke control, and door entry
installations
SIGNALING
S1949
7300-1703-0174
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60709 Rev. B page 1 of 2
©2013 Honeywell International Inc. All rights reserved.
Description (Continued)
Specifications
Use rotary switches to set the address setting. You
can set the base via the rotary switch and assign the
address to Relay Output #1 from Address 00 to
Address 156. The module automatically assigns the
next three addresses as appropriate to Monitored
Input #1, Relay Output #2, and Monitored Input #2. If
the Relay Output #2 or the Monitored Input #2 are
not used, use the DIP switch to manually disable
those addresses. You can use Relay Output #2 and
the Monitored Input #2 addresses for other devices
on the loop.
Supervisory Current:
Alarm Current:
Operating
Temperature:
Relative Humidity:
Figure 1 illustrates the Address Disable Switch.
0.00130 A
0.024 A
32°F to 120°F (0°C to 49°C)
10% to 93%
(Non-condensing)
Temperature Rating: 32°F to 120°F (0°C to 49°C)
Dimensions:
4 1/2” H x 4” W x 1 1/4” D
(11 H x 10.2 W c 3.2 D cm)
End-of-Line Resistor: 47k Ohms
Ordering Information
Part Number Description
AMM-2RIF
Addressable 2 Input/2 Output Module