GAMEWELL-FCI AOM-2RF

Velociti® Series
AOM-2RF
Description
Addressable Output Relay
Control Module
The Gamewell-FCI Velociti® Series, addressable output
relay control module (AOM-2RF) allows an Gamewell-FCI
analog addressable fire alarm control to switch discrete
relay contacts by code command. The relay provides two
(2), isolated sets of Form-C contacts which transfer simultaneously. Circuit connections to the relay contacts are not
supervised by the module.
The Velociti® Series use a communication protocol that
substantially increases the speed of communication
between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate in a
grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and concentrates on the single device. The net effect is
response speed up to five times greater than earlier
designs.
The AOM-2RF Module is designed for installation in the
signaling line circuit of any Gamewell-FCI analog addressable fire control panel. The module contains a panel controlled LED. The AOM-2RF is designed to mount in a 4”
square junction box 2 1/8” deep.
AOM-2RF
Features
• Two (2) sets of Form “C” contacts
• Visual rotary, decimal switch addressing (01-159)
• Bicolor LEDs flash green whenever the sensor is
addressed, and light steady red on alarm*
• Compact size allows easy installation
Note: Only the red LED is operative in panels that do not operate
in Velociti® mode.
Specifications
Relay Contact Ratings
Current Maximum
Load
Rating
Voltage Description
3A
2A
0.9A
0.5A
0.5A
30 VDC
30 VDC
110 VDC
125 VAC
30 VDC
1A
30 VDC
0.5A
125 VAC
0.7A
75 VAC
Resistive
Resistive
Resistive
Resistive
Inductive
(L/R=5ms)
Inductive
(L/R=2ms)
Inductive
(PF=.35)
Inductive
Application
Non-Coded
Coded
Non-Coded
Non-Coded
Coded
Coded
Supervisory current:
Alarm current:
Operating temperature:
Relative humidity:
Dimensions:
.000375 amps.
.0065 amps.
32° to 120° F (0° to 49° C)
10 to 93% relative humidity
(non-condensing)
4 1/2” H x 4” W x 1 1/4”
(11.4 x 10.2 x 3.2 cm)
Ordering Information
Model
Description
AOM-2RF
Addressable output relay control module
Non-Coded
A n IS O 900 1- 20 00 C o m p a n y
Non-Coded
SIGNA LIN G
Velociti® Series is a registered trademark of Honeywell International Inc.
FM
S1949
MEA
Approv ed
3023594 227-03-E Vol.IV 07300-0694:178
A PPRO VED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0625 Rev. D1 page 1 of 1