Velociti® Series AOM-2RF Description Addressable Output Relay Control Module The Gamewell-FCI Velociti® Series, addressable output relay control module (AOM-2RF) allows an Gamewell-FCI analog addressable fire alarm control to switch discrete relay contacts by code command. The relay provides two (2), isolated sets of Form-C contacts which transfer simultaneously. Circuit connections to the relay contacts are not supervised by the module. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier designs. The AOM-2RF Module is designed for installation in the signaling line circuit of any Gamewell-FCI analog addressable fire control panel. The module contains a panel controlled LED. The AOM-2RF is designed to mount in a 4” square junction box 2 1/8” deep. AOM-2RF Features • Two (2) sets of Form “C” contacts • Visual rotary, decimal switch addressing (01-159) • Bicolor LEDs flash green whenever the sensor is addressed, and light steady red on alarm* • Compact size allows easy installation Note: Only the red LED is operative in panels that do not operate in Velociti® mode. Specifications Relay Contact Ratings Current Maximum Load Rating Voltage Description 3A 2A 0.9A 0.5A 0.5A 30 VDC 30 VDC 110 VDC 125 VAC 30 VDC 1A 30 VDC 0.5A 125 VAC 0.7A 75 VAC Resistive Resistive Resistive Resistive Inductive (L/R=5ms) Inductive (L/R=2ms) Inductive (PF=.35) Inductive Application Non-Coded Coded Non-Coded Non-Coded Coded Coded Supervisory current: Alarm current: Operating temperature: Relative humidity: Dimensions: .000375 amps. .0065 amps. 32° to 120° F (0° to 49° C) 10 to 93% relative humidity (non-condensing) 4 1/2” H x 4” W x 1 1/4” (11.4 x 10.2 x 3.2 cm) Ordering Information Model Description AOM-2RF Addressable output relay control module Non-Coded A n IS O 900 1- 20 00 C o m p a n y Non-Coded SIGNA LIN G Velociti® Series is a registered trademark of Honeywell International Inc. FM S1949 MEA Approv ed 3023594 227-03-E Vol.IV 07300-0694:178 A PPRO VED GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0625 Rev. D1 page 1 of 1 ©2008 Honeywell International Inc. All rights reserved.