Data Sheet

MS Series
Description
Non-Coded, Manual
Fire Alarm Stations
Model MS-2, MS-2H
The MS-2 manual fire alarm stations are dual action
devices. These stations require that the outer door be lifted
to expose the actuation door which is then pulled forward
to operate the alarm toggle switch. The actuation door is
now locked in the readily observable “alarm” position.
To reset the station, a key (common to Gamewell-FCI control panels) must be inserted and turned ¼ turn clockwise,
opening the station. Closing the station resets the switch
automatically
An optional breakglass rod is available for positive indication of station operation.
Model MS-2L (Institutional)
Operation of the Model MS-2L institutional station requires
that a special key be used to release the actuation door
before it can be operated.
Model MS-2-D (Multiple Contact)
The MS-2-D features a DPST switch for multiple signaling
via wire lead connections.
Model MS-6 (Single Action)
The MS-6 station is a single action device, requiring only
the pulling of the action door to release the compressed
button switch. It is available either with terminals (MS-6T)
or wire leads (MS-6).
The station resets in the same manner as the MS-2. The
reset key is common to FCI control panels.
Specifications
Material (MS-2, MS-6)
Doors (MS-2, MS-6)
Switch Type
MS-2
MS-6
Contact Material
Contact Ratings
MS-2
MS-6
Dimensions (overall)
MS-2, MS-6
Extruded 6063/T5 aluminum
Clear anodize
Figure 1 MS-2
Figure 2 MS-2H
Figure 3 MS-6
Features
• Single and Dual Action Versions
• Tumbler Lock for Test and Reset Keyed Alike with FCI
Control Panels
• Rugged Metal Construction
• Positive Indication of Operation over 180° Viewing
Angle
• Surface or Semi-flush Mounting
• Shock and Vibration Resistant
• Institutional Version (MS-2L)
• Optional “FIRE SUPPRESSION SYSTEM RELEASE”
Markings (MS-2H)
• Optional DPST Switch (MS-2-D)
Enclosed toggle
Enclosed push button
Silver plated bronze or copper
6 amp. max. @ 30 VDC (resistive)
0.5 amp. max. @ 30 VDC
(resistive)
5” H x 3.4” W x 2.8” D
(12.7 cm x 8.64 cm x 7.11 cm)
SIGNALING
FM
MEA
Approved
S2465 OJ3A9.AY/12880 (MS-2) 960-81-SA (MS-2) 7150-1703:0100
AD4A7.AY (MS-6, MS-6T) 103-93-E (MS-6)
APPROVED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0358 Rev. J page 1 of 2
©2013 by Honeywell International Inc. All rights reserved.
Ordering Information
Part Number Description
1100-0615
MS-2, Dual Action fire alarm station
1100-0634
MS-2H Dual Action station with “FIRE
SUPPRESSION SYSTEM RELEASE”
markings
1100-0621
MS-2L, Institutional fire alarm station
1100-0617
MS-2-D, Dual action station with DPST
switch
1100-0632
MS-6, Single action station, wire leads
1100-0633
MS-6T, Single action station, terminals
2520-0023
BB-2, Surface backbox for MS-2, MS-6 stations
1120-0206
Package of two replacement breakglass
rods for MS-2 station
Figure 4 MS Series Installation
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0358 Rev. J page 2 of 2
www.gamewell-fci.com