GAMEWELL-FCI MS-95

MS-95, MS-95T
Description
Addressable Manual
Pull Station Alarm
CS-2053ph1.wmf
The Gamewell-FCI MS-95 is an easily recognized manual
pull station with the distinctive bulls-eye design compatible
with the Gamewell-FCI addressable 600 Series Fire Alarm
Control Panels (FACPs). The MS-95 is approved to UL
Standard 38 for manual stations, meets architectural
requirements in all building interiors, and is readily noticed
in a fire emergency. The addressable MS-95 manual pull
station with a rugged toggle switch design offers exceptional resistance to accidental alarms caused by vibration
and sudden shock. The MS-95 can be used for surface and
semi-flush installations.
Operations
MS-95
The manual pull station is activated by pulling forward on
the readily identified bulls-eye alarm lever labeled “PULL”
in distinctive white letters. Once pulled, this lever locks in
the alarm position and remains there until manually reset.
To reset the alarm lever, the front cover of the pull station is
released by turning the screw on the top of the cover or
turning the key (on certain models). This unlocks the front
cover which is then lowered. Once the front cover is lowered, the toggle switch is reset.
An optional breakglass rod may be used with all stations.
The self-clearing design prevents jamming of the station
and there is no danger to the operator from broken particles of glass. Space is provided within the station housing
for storage of an additional replacement glass rod.
Features
•
•
•
•
•
•
•
•
•
•
•
The MS-95 connects directly to the analog addressable
circuit via two wires. The electronic circuitry has been
designed to transmit data that can be interpreted as three
(3) output operations:
•
normal standby operation
•
alarm operation
•
trouble operation
In its standby mode of operation, the pull station’s circuit
monitor the switch for alarm conditions. A trouble condition
Compatible with the Gamewell-FCI 600 Series analog
addressable control panels.
Field programmable.
Durable construction.
Compact design, blends with surroundings.
Recessed pull lever prevents accidental operation.
Surface or semi-flush installation.
Double action option.
Key reset option.
Meets ADA requirements.
Visible status LED.
Terminal block model available (MS-95T).
An ISO 9000-2000 Company
SIGNALING
S281
7150-1288:148
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2053 Rev. A page 1 of 2
Operations (Continued)
Ordering Information
occurs when the pull station is addressed by the control
panel and either reports back a trouble response or does
not respond at all. With the standard priority interrupt
feature, the MS-95 will report its condition virtually instantaneously to the Gamewell-FCI FACP.
Model
Description
MS-95
MS-95T
Analog addressable manual pull station.
Analog addressable manual pull station with
terminals.
Double action option.
Key reset option.
Key reset/double action option.
Breakglass rod.
Surface backbox.
Weather proof gasket for MS-95 station.
NYC backplate manual station backplate with
1" (2.54 cm) white stripe.
Backbox, surface for key reset options.
Programming
Programming of the MS-95 manual station address is
accomplished by setting a single DIP switch easily
accessible on the device’s printed circuit board. All other
programming is accomplished at the FACP.
30653
30653-01
30653-02
27060
28762
50397G
72198
71961
Engineer’s Specifictions
The analog addressable manual pull station shall contain
the electronic interface circuitry required for individual
device identification, alarm reporting andtrouble supervision. It shall communicate to the main control panel via the
analog addressable circuit. The single-action station shall
consist of a die-cast aluminum housing fitted with a pull out
lever which, when operated, locks in position after activating an alarm initiating contact.
Specifications
Standby Current:
Alarm Current:
Operating
Temperature:
Relative Humidity:
Material:
Finish:
0.0005 A
0.0015 A
0° C to 49° C (32° F to 120° F)
85%, non-condensing
Die-cast aluminum
Fire alarm red, smooth gloss
enamel. Raised cast letters are
highlighted. Target background for
pull lever is white glossed enamel.
Dimensions MS-95: 4 .625" high x 3.25" wide x 2.0"
deep (11.75 H x 8.26 W x 5.08 D cm)(
from the backplate).
MS-95T:
4.625" high x 3.25" wide x 1.625"
deep (11.75 H x 8.26 W x 4.13 cm)
(from the backplate).
MS-95 with key reset
option:
6.25" high x 3.25" wide x 2.0" deep
(15.88 H x 8.26 W x 5.08 D cm) (from
backplate) with Cat 60 Key.
Surface Backbox
P/N 28762:
4.625" high x 3.25" wide x 2.375"
deep (11.75 H x 8.26 W x 6.03 D cm)
tapped for 3/4" conduit.
Surface Backbox
71961:
6.25" high x 3.0" wide x 3.25"
(15.88 H x 7.6 W x 8.26 D cm) deep.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com