MS-7 Series Manual Station

MS-7 Series
Non-Coded, Manual
Fire Alarm Stations
Description
The Gamewell-FCI, MS-7 Series manual fire alarm stations are available in a wide variety of configurations. The
Stations comply with the Americans with Disabilities Act
(ADA) 5-lb. maximum pull force requirement. Operating
instructions and Braille text are engraved in the handle. All
stations have a key lock/reset which is keyed alike with
Gamewell-FCI fire alarm control panels and other manual
fire alarm stations.
MS-7AF Velociti Addressable Station
The MS-7AF Velociti® Series addressable station is a double action station designed for installation in the signaling
line circuit of Gamewell-FCI analog addressable control
panels. Activation of the station causes its assigned
address to register at the control panel. The door contains
an LED which flashes green in normal condition and lights
steady red when the station has been activated.* The station features screw terminals.
MS-7ASF Velociti Addressable Station
The MS-7ASF Velociti® Series addressable station is a
single action station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the station causes its assigned
address to register at the control panel. The door contains
an LED which flashes green in normal condition and lights
steady red when the station has been activated.* The station features screw terminals.
The Velociti® Series stations use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI
analog addressable fire alarm controls. These devices
operate in a grouped fashion. If one of the devices in the
group has a status change, the panel’s microprocessor
stops the group poll and focuses on the single device. The
net effect is response speed up to five times greater than
earlier designs.
MS-7 Double Action Station
The MS-7 double action station is used with conventional
fire alarm control panels. It features a set of single pole
contacts and screw terminals for connection to an initiating
circuit.
Velociti® is a registered trademark of Honeywell International Inc.
MS-7
Features
• Addressable stations compatible with all Gamewell-FCI
analog addressable fire alarm controls
• Conventional stations suitable for use with any UL®
Listed control panel
• Both single and double action stations available
• Tumbler lock for test and reset keyed alike with
Gamewell-FCI controls
• Surface or semi-flush mounting
• Shock and vibration resistant
• Stations (MS-7LOB) Listed for outdoor applications
• Complies with ADA pull force requirements
*Only the red LED is operative in panels that do not operate in Velociti mode.
SIGNALING
FM
UL® is a registered trademark of Underwriter’s Laboratories Inc.
MEA
Approved
S2465 3023594 67-02-E Vol.VIII 7150-1703:0119
7150-1703:0170
7150-1703:0109
APPROVED
LEXAN® is a registered trademark of GE Plastics, a subsidiary of General
Electric Company.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0616 Rev. E page 1 of 2
©2013 by Honeywell International Inc. All rights reserved.
Specifications
MS-7S Single Action Station
The MS-7S single action station is used with conventional
fire alarm control panels. It features a set of single pole
contacts and wire leads for connection to an initiating circuit.
Material:
Contact Ratings:
Lexan®
0.25 amps. @ 30 VAC/VDC
(resistive)
5 5/8” H x 4 1/4” W x 1 1/4” D
(14 x 10.1 x 3.2 cm)
MS-7SP Double Action Station
The MS-7SP is a double action station similar to the MS-7
station, with the additional feature of both English and
Spanish instructions molded into the unit.
MS-7LR Dual-action Agent Release Station
The MS-7LR is designed for use with the Gamewell-FCI
fire alarm control panels with releasing capabilities and
Flex Series releasing systems. It features a set of single
pole contacts and screw terminals for connection to an initiating circuit.
MS-7LRA Agent Release Station with Abort
The MS-7LRA is designed for use with the Gamewell-FCI
fire alarm control panels with releasing capabilities and
Flex Series releasing systems where system abort capabilities are required. It consists of an MS-7LR mounted on a
plate with an abort switch and LED indicators for system
normal, and system activated status.
MS-7LOB Double Action Station
(Listed for Outdoor Applications)
Dimensions:
Operating Temperature
(MS-7AF, MS-7ASF):
(MS-7LOB):
Relative Humidity
(MS-7AF, MS-7ASF):
(MS-7LOB):
Alarm Current:
Supervisory Current
(MS-7AF, MS-7ASF):
32° to 120° F (0° to 49° C)
-30° to 150° F (-35° to 66° C)
10 to 93% (non-condensing)
85% ± 5% @ 86° ± 3.6°
(30° ± 2° C)
.0030 amp. 0.007 for LED
.00030 amps.
Ordering Information
Part Number
Description
MS-7
MS-7AF**
The MS-7LOB station must be mounted on a Model SB-I/O
backbox. In retrofit applications, the station is UL Listed for
use with the WP-10 backbox. It is intended for use with
conventional control panels and has a set of single pole
contacts and screw terminals.
Mounting
The MS-7 interior stations may be surface mounted or
semi-flush mounted on a standard double-gang, or 4-inch
(10.2 cm) square electrical box. An optional trim ring
(BG12TR) may also be used for semi-flush mounting.
NYC-Plate
The NYC-Plate provides the backplate for the manual pull
station. (See Figure 1).
Double action station
Velociti addressable double action
station
MS-7ASF**
Velociti addressable single action station
MS-7S
Single action station, wire leads
MS-7SP
Double action station, English and
Spanish instructions
MS-7LR
Agent release station, dual-action
MS-7LRA
Agent release station with abort switch,
LED indicators, dual- action
MS-7LOB
Double action station, outdoor use
(Includes SB-I/O - Indoor/outdoor use
backbox)
SB-I/O
Indoor/outdoor use backbackbox
SB-10
Surface backbox
BG12TR
Trim ring for semi-flush mount, plastic
NY-PLATE
NYC backplate for manual pull station
**For use with the Gamewell-FCI analog addressable
control panels only.
Figure 1 NYC-Plate
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0616 Rev. E page 2 of 2
www.gamewell-fci.com