HFS Series Intelligent Plug-in Detectors

HFS Series Intelligent
Plug-in Detectors
Description
The HFS Series intelligent plug-in smoke/heat detectors
with integral communication provide point location for
alarm communication and selective maintenance. This
product line is compatible with the Gamewell-FCI IdentiFlex 100 addressable fire alarm control panel which is ideal
for use in small commercial spaces.
Detector sensitivity can be programmed in the control
panel software. Sensitivity is continuously monitored and
reported to the panel. Point ID capability allows each
detector address to be set with decade address switches to
provide exact detector locations for selective maintenance
when the chamber contamination reaches an unacceptable
level.
The HFS-P photoelectric detector’s unique optical sensing
chamber is engineered to sense smoke produced by a
wide range of combustion sources. Dual electronic thermistors add 135°F fixed temperature thermal sensing on
the HFS-PT model.
The HFS-T detectors use an innovative thermistor sensing
circuit to produce 135°F fixed thermal detection in a low
profile package. These thermal detectors provide costeffective, intelligent property protection in a variety of applications.
Specifications
Physical/Operating Specifications:
Height:
2.0 in (51 mm)
Diameter:
6.1 in (155 mm) installed
Shipping Weight:
Heat:
7.68 oz (217.7 g);
Photo/Photo with Heat:
7.95 oz (225.4 g)
Operating Temperature Range:
Photo:
32°F to 120°F (0°C to 49°C)
Photo with Thermal:
32°F to 100°F (0°C to 38°C)
Thermal:
–4°F to 100°F (–20°C to 38°C)
UL® Listed Velocity Range:
Photo/Photo with Thermal: 0 – 4000 fpm (0 – 20 m/sec)
Operating Humidity
Range:
10% to 93% non-condensing
Thermal Ratings:
Fixed Temperature Setpoint: 135°F (57°C)
Electrical Specifications:
Voltage Range:
15 to 32 volts DC peak
Standby Current
300 µA @ 24VDC
(max. avg.):
(one communication every 5
seconds with LED enabled)
Photo/Photo with Thermal: 300 µA @ 24 VDC
(one communication every 5
seconds with LED enabled)
LED Current (max.):
6.5 mA @ 24 VDC (on)
UL
Intelligent Plug-in
Smoke/Heat Detectors
HFS-P Intelligent Plug-in Photoelectric Detector
Features
•
•
•
•
•
•
•
Streamlined design
Analog communications
Low standby current
Rotary address switches
Superior EMI protection
Dual LEDs for 360° visibility
Shipped with mounting base
Ordering Information
Part Number
HFS-P
HFS-PT
HFS-T
® is a registered trademark of Underwriters Laboratories Inc.
Description
Photoelectric smoke detector
Photoelectric smoke detector with
thermal, 135° F
Fixed temperature thermal detector,
135° F
An ISO 9001-2000 Company
SIGNALING
S1869
3189837NYM-001a
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60605 Rev. A page 1 of 1
©2010 by Honeywell International Inc. All rights reserved.