HFS-D Intelligent Non-Relay Photoelectric Duct Smoke

HFS-D Intelligent
Non-Relay Photoelectric
Duct Smoke Detector
Intelligent Non-Relay
Photoelectric Duct Smoke Detector
Description
The HFS-D intelligent non-relay photoelectric duct smoke
detector features a pivoting housing that fits both square
and rectangular footprints that are capable of mounting to a
round or rectangular duct. The HFS-D is compatible with
the Gamewell-FCI IdentiFlex 100 addressable fire alarm
control panel and it is flexible enough to fit mounting configurations from square to rectangular and everything in
between.
This unit senses smoke in the most challenging conditions,
operating in airflow speeds of 100 to 4000 feet per minute,
temperatures of -4°F to 158°F, and a humidity range of 0 to
95 percent (non-condensing).
An improved cover design isolates the sensor head from
the low-flow feature for simple maintenance. A cover
tamper feature was added to indicate a trouble signal for a
removed or improperly installed sensor cover. The housing
provides a ¾-inch conduit knockout and ample space to
facilitate easy wiring and mounting of the HFS-MR relay
module.
The HFS-D can be customized to meet local codes and
specifications without additional wiring. The new HFS-D is
compatible with various remote test accessories.
WARNING: Duct smoke detectors have specific limitations.
DUCT SMOKE DETECTORS ARE:
NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire detection
system.
Refer to NFPA 72 and 90A for additional duct smoke detector application information.
HFS-D Intelligent Non-Relay Photoelectric Duct Detector
Features
• Photoelectric, integrated low-flow technology
(HFS-DPR detector head included)
• Air velocity rating from 100 ft/min. to 4000ft/min. (0.5m/s
to 20.32m/sec)
• Versatile mounting options: square or rectangular configuration
• Broad ranges for operating temperature (-4°F to 158°F)
and humidity (0% to 95% non-condensing)
• Patented sampling tube installs from front or back of the
detector with no tools required
• Cover tamper signal
• Increased wiring space with a newly added ¾-inch
conduit knockout
• Available space within housing to accommodate
mounting of relay module
• Easily accessible code wheels on sensor head
• Clear cover for convenient visual inspection
• UL® 268A Listed
• Remote testing capability
• Requires com line power only
An ISO 9001-2000 Company
SIGNALING
S1869
3189837NYM-001a
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60607 Rev. A page 1 of 2
©2010 by Honeywell International Inc. All rights reserved.
Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations and different
means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL® Listed.
Figure 1 - RTS151 (UL S2522)
Figure 2 - RA100Z (UL S2522)
Figure 3 - RTS151KEY (UL S2522)
Ordering Information
UL® is a registered trademark of Underwriters Laboratories Inc.
.
Specifications
Part Number
HFS-D
Architectural/Engineering Specifications
The air duct smoke detector shall be an HFS-D Intelligent
Non-Relay Photoelectric Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for
use in air handling systems. The flexible housing of the
duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/
min. to 4000 ft/min. (0.5 m/sec to 20.32 m/sec). The unit
shall be capable of providing a trouble signal in the event
that the sensor cover is removed or improperly installed. It
shall be capable of local testing via magnetic switch or
remote testing using the RTS151KEY remote test station.
Terminal connections shall be of the strip and clamp
method suitable for 12–18 AWG wiring.
Physical Specifications
Size
Rectangular:
5” W x 14.38” L x 2.5” D
(12.7 W x 37 L x 6.6 D cm)
Square:
9” W x 7.75” L x 2.5” D
(22.9 W x 19.7 L x 6.35 D cm)
Weight:
1.6 lb (0.73 kg)
Operating Tempera- –4°F to 158°F (–20°C to 70°C)
ture Range:
Storage Temperature –22°F to 158°F (–30°C to 70° C)
Range:
Operating Humidity 0% to 95% relative humidity
Range:
(non-condensing)
Air Duct Velocity:
100 to 4000 ft/min (0.5 to 20.32 m/s)
Electrical Ratings
Please see detector head installation manual for electrical
specifications.
Accessory Current Loads at 24 VDC
Device
Standby
Alarm
RA100Z
0 mA
12 mA max.
RTS151/RTS151KEY 0 mA
12 mA max.
Accessories
DST1
DST1.5
DST3
DST5
DST10
DH400OE-1
ETX
HFS-DPR
HFS-MR
M02-04-00
P48-21-00
RA100Z
RTS151
RTS151KEY
Description
Intelligent non-relay photoelectric lowflow duct smoke detector
Metal sampling tube duct width up to 1ft
(0.3m)
Metal sampling tube duct widths 1 ft to 2
ft (0.3 to 0.6 m)
Metal sampling tube duct widths 2 ft to 4
ft (0.6 to 1.2 m)
Metal sampling tube duct widths 4 ft to 8
ft (1.2 to 2.4 m)
Metal sampling tube duct widths 8 ft to
12 ft (2.4 to 3.7 m)
Weatherproof enclosure
Metal exhaust tube duct width 1ft (0.3m)
Replacement photoelectric head for
duct detector
Relay Module
Test magnet
End cap for metal sampling tubes
Remote annunciator alarm LED
Remote test station
Remote test station with key
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60607 Rev. A page 2 of 2
www.gamewell-fci.com