7200 Micro

7200 Micro
COMPACT ANALOG
FIRE ALARM CONTROL PANEL
DESCRIPTION
The FCI 7200 Micro fire alarm control panel effectively
combines multiprocessor analog system advantages with a
compact design. Designed for commercial, industrial and
institutional use, the 7200 Micro compact control panel is
ideal for life safety applications.
This analog fire alarm control panel provides two (2)
signaling line circuits, each capable of addressing 99 analog
sensors and 98 monitor and/or control points for a total of
197 points per circuit, with a system maximum of 394 points.
Auto-configuration and/or computer programming allow
the 7200 Micro to rapidly adapt to continuously changing
environments. The integral COMPARE Program confirms
any programmed system with proposed software modifications prior to downloading, affording software validation and
minimized system retesting.
The 7200 Micro features sophisticated circuitry and powerful analog software enabling it to read specific (default/user) sensitivity levels of each sensor and compensate
for any changes due to age or environmental conditions.
The 7200 Micro incorporates the FCI Listed Integrated
Sensitivity Testing (LIST) which meets the NFPA 72 sensitivity testing and maintenance requirements. The LIST testing saves substantial time and money in both maintenance
and service while virtually eliminating unwanted alarms.
The switching technology power limited power supply
operates on either 120 or 240VAC, 50/60 Hz and is capable
of maintaining batteries from 7 to 55 ampere/hours in capacity.
The 7200 Micro will accommodate up to four (4) remote
Keyboard Display Units and up to fifteen (15) Remote Annunciator Units for a total of 480 points.
FEATURES
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Switching Technology Power Limited
Power Supply (6 amps)
Dual Rate Battery Charger (7 to 55 AH)
Front Panel Auto-Configuration and/or
Computer Programming
FCI COMPARE Program
80-character Alphanumeric Display
First Alarm Indication
Manual/Automatic Sensor Settings
Individual Sensor Drift Compensation
Listed Integral Sensitivity Testing (LIST)
“Dirty” and “Very Dirty” Sensor Indications
Multilevel Sensor Sensitivity Adjustments
Day/Night Sensor Sensitivity Adjustments
Alarm Verification per Individual Sensor
Two Style 6/7 or Style 4 (Class A or B)
Signaling Line Circuits
Duplicate Address Indication
Two Style Z or Y (Class A or B) Notification
Appliance Circuits.
March Time/Temporal Pattern/Calif. Code
Suitable for Releasing Device Service
Dual-Mode Walk Test
500-Event History Log
Remote Annunciation (Alphanumeric
and/or LED)
Optically Isolated RS232 Serial Port
Programmable Trouble Reminder
301 2nd Ave Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 370-4132
9020-0359/Ver. 1.3
FIRE CONTROL INSTRUMENTS, Inc.
SPECIFICATIONS
Primary input power
Output power
Non-resettable power
Resettable power
Two (2) Notification Appliance Circuits
Operating temperature
Relative humidity
Battery charger capacity
Charge rate
Alarm & trouble relay contacts
Dimensions
Weight
120/240 VAC, 50/60 Hz, 3.0 amps.
6 amp. @ 24 VC (total)
1.7 amp.
1.7 amp.
1.75 amp. each
32o - 120o F (0 - 49o C)
85% (non-condensing)
7 to 55 AH
1 or 2 amp. @ 27.1 VDC
2 amp. @ 24 VDC (resistive)
19.5" H x 15.5" W x 5.25" D (49.53 x 39.37 x 13.34 cm)
24 lbs. (10.9 kg)
ORDERING INFORMATION
Part No.
1100-1126
1100-1125
Model
Micro/R
Micro/B
Description
7200 Micro System, Red
7200 Micro System, Beige
Supv. Current
0.191 A
0.191 A
Alarm Current
0.432 A
0.432 A
1100-0886
1100-0887
TR-1R
TR-1B
Semi-flush Trim Ring, Red
Semi-flush Trim Ring, Beige
Description
7200 Series Keyboard Display Unit
Remote Display Enclosure for KDU,
Red, Surface Mount
Remote Display Enclosure for KDU,
Beige, Surface Mount
Remote Display Enclosure for KDU,
Red, Flush Mount
Remote Display Enclosure for KDU,
Beige, Flush Mount
Supv. Current
.060 A
Alarm Current
.065 A
0.018 A
0.018 A
0.007 A**
0.075 A†
0.018 A
0.040 A‡
ACCESSORIES
Part No.
1120-0512*
1100-0296
Model
KDU
RHRS
1100-0295
RHBS
1100-0298
RHRF
1100-0297
RHBF
1120-0479
RAU
7200 Series Remote Annunciator Unit
1100-1123
1120-0582
RAU-CA
RAU-FV
RAU with enclosure
7200 Series interface for FireVac®III
1100-0220
1100-0908
PTR
VT-1
80-Column printer with Cable
Video Terminal
* Less enclosure
**Per activated LED
†
Per incandescent lamp
‡
Add 0.002 A per activated circuit
Specifications are provided for information only and are believed to be accurate. However, no responsibility is assumed by Fire Control Instruments, Inc. for their use.
Specifications subject to change without notice.
© 1997 All Rights Reserved
301 2nd Ave Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 370-4132
2 of 2
9020-0359