72-MOD-4000 - Grayhill, Inc.

OpenDAC® I/O System
NETWORK INTERFACES
OpenDAC® for Modbus
FEATURES
• Each Unit Controls/Monitors up to
32 Analog and/or Digital I/O using
OpenLine® Modules
• Network up to 247 OpenDACs® per
Host PC, Each Separated by as
much as 4,000 Feet
• Communicate Over RS-422/485 at
Speeds from 9600 Baud to 56.7 KB
• 100% Modbus ASCII or Modbus
RTU Compatible
• CE Certified
• DIN Rail or Panel Mount
MODBUS UNIT ON OPENDAC® SYSTEM
APPLICATIONS
GENERAL DESCRIPTION
Stand Alone Control
Local Control & I/O
Remote I/O
Distributed I/O
SCADA
OpenDAC® I/O System
RTU
OpenDAC® for Modbus is an inexpensive,
flexible interface to 32 analog or digital
OpenLine® I/O. As one of 247 slave devices on
a Modbus network, OpenDAC® for Modbus
constantly scans and stores the current status
of each I/O. Upon command from the host
device, the controller will change the status of
an output or return the value of an input. The
slave address is switch selectable. Diagnostic
LEDs provide troubleshooting assistance.
ANALOG & DIGITAL I/O
OpenDAC® for Modbus connects directly to two
16 channel racks. Any combination of analog
and digital I/O modules may be used. On power
up, the OpenDAC® scans and stores the I/O
configuration and makes the information
available to the master for query.
In addition to simple On/Off instructions, Modbus
commands allow you to:
• Read linearized thermocouple and RTD
temperature values
• Count pulses at frequencies up to 1000Hz
• Detect rising or falling edges
• Latch momentary input events
• Set the level of analog outputs
COMMUNICATIONS
format to code the command and the response
messages. Application programs running on
the host computer issue commands and then
await responses from the OpenDAC®. The
communications speed is switch selectable
between 9600 and 56700 baud. The entire
network can span 4000 feet.
FAULT TOLERANCE
Each OpenDAC® for Modbus has an internal
communications watchdog timer to minimize
the impact of a broken Modbus link between the
controller and the master device. If activated,
the timer must be reset by an incoming message
within the prescribed period of time. If not, the
controller will force it’s outputs into a default
state.
SOFTWARE
Software drivers are available which simplify
the task of interfacing host programs written in
Visual Basic or C to the Modbus network. Sample
programs, set-up and debug utilities are included
on the disk with the drivers. Interface drivers for
most third party software packages are available
through their distributors. Our DLL will assist
you in building custom Man-Machine Interfaces
using Visual Basic, Visual C/C++, or Borland
compilers running on Windows 95, 98 or NT.
The host computer and OpenDAC® for Modbus
communicate serially over one or two pair of
twisted wires per RS-422/485 in a multi-drop
configuration. They use Modbus ASCII or RTU
OpenDAC
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
4
OpenDAC® I/O System
DIMENSIONS
In inches (and millimeters)
4.1(104.26)
1.1
(28.22)
3.9 (99.56)
DIN RAIL LATCH
1.0
(25.86)
3.0
(75.69)
2.6
(65.48)
2.3 (57.17)
TO CENTERLINE OF
DIN RAIL CHANNEL
PIN 1
SPECIFICATIONS
ORDERING INFORMATION
Part Number
Description
OpenDAC® Network Interface
72-MOD-4000
Analog/Digital OpenDAC® for Modbus
OpenDAC® User’s Manual and Software
72-UM-OMOD
72-UME-DLL32
72-UOL
OpenDAC® for Modbus user’s manual
Ethernet/Modbus DLL for Windows 95/98/NT
OpenLine® configuration and product data
Compatible Components
®
OpenDAC I/O Racks
Digital OpenLine® I/O Modules
Analog OpenLine® I/O Modules
Power Supply
Available from your local authorized Grayhill
Distributor. For prices and discounts, contact
your local sales office, an authorized Distributor,
or Grayhill.
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
OpenDAC
5
OpenDAC® I/O System
Power Supply: 4.75 to 5.25 Vdc
Supply Current (less modules): 1 amp @ 5
Vdc max.
Operating Temperature: 0 to 60°C
Humidity: 95% non-condensing
Microprocessor: V25 @ 10 MHz
Housing Material: ABS/Polycarbonate blend
Connections:
RS-422/485: 5 position depluggable connector
Passive Rack: 48-pin Euro DIN (male)
Serial Data:
Format: 10 Bit ASCII: 1 Start, 1 Stop, 8 Data
Integrity: Message Checksum
Range of Network: Compliant with EIA/TIA
RS485-A (1 standard load per controller).
Operates in multi-drop mode. 247 DIP switch
selectable addresses. May require RS485
repeaters for lengths over 4000 feet or more
than 32 controllers. Consult factory for special
configurations.