74-PWR-AC2 - Grayhill, Inc.

OpenLine® Control System
POWER SUPPLY
FEATURES
• Rugged Construction
• UL, CSA, CE Certified
• Some Models Provide Built-In
Redundancy
• Wide Input Voltage Ranges
• Compact Package
• Wide Operating Temperature Range
• DIN Rail Mountable
MO
M1
M2
M3
M4
M5
M6
M7
MO
M1
M2
M3
M4
M5
M6
M7
SPECIFICATIONS
General
Terminal Blocks:
J2: 1 row of 6 for internal bus power (Mating
connector not included3)
J3: 1 row of 3 for AC input. (Mating plug included)
J4: 1 row of 4 for auxiliary loads (Mating plug
included)
Terminals Screw Torque: 7-9 in-lbs
Bus Output: +5V output can be run in parallel
with other bus supplies.
POWER SUPPLY UNIT ON OPENLINE® SYSTEM
SPECIFICATIONS
74-PWR-AC1
74-PWR-AC2
74-PWR-AC3
Input Voltage Range:
Input Frequency Range:
Input Current:
Output Voltage Ranges:
85-250 Vac
47-440 Hz
1.5A @ 115 Vac
4.8 to 5.2 Vdc,
11.7 to 12.9 Vdc, &
-11.7 to 12.9 Vdc
7.0A @ 0-40°C derate
2.5% per degree 40-70°C
0A @
NA
85-250 Vac
47-440 Hz
1.0A max. (RMS) @115 Vac
4.8 to 5.2 Vdc,
11.7 to 12.9 Vdc, &
-11.7 to 12.9 Vdc
3.0A @ 0-40°C, derate
2.5% per degree 40-70°C
0.3A @ 5 Vdc
NA
85-250 Vac
47-440 Hz
1.0A max. (RMS) @115 Vac
4.8 to 5.2 Vdc
5.0A @ 0-40°C, derate
2.5% per degree 40-70°C
0A
NA
70% typical
<50 mV
1 green power supply OK LED4
(1) 14 AWG or (2) 16 AWG
3.15A @ 250 Vac fuse,
overload and reverse
polarity protection.
70% typical at full load
<50 mV
1 green power supply OK LED4
(1) 14 AWG or (2) 16 AWG
2.0A @ 250 Vac fuse,
overload and reverse
polarity protection.
70% typical at full load
<50 mV
1 green power supply OK LED4
(1) 14 AWG or (2) 16 AWG
2.0A @ 250 Vac fuse,
overload and reverse
polarity protection.
Maximum Output Current1:
Minimum Load Current:
Secondary Output Current2:
Efficiency:
Ripple:
Indicator:
Conductor Size:
Protection:
OpenLine® Control System
Specification
1
Output current rating assumes horizontal DIN rail or panel mounting, no cover and no auxiliary air flow. For horizontal mounting with cover, current rating
is specified from 0 to 30°C, derate 2.5% per degree 30 to 70°C. For vertical mounting with cover, current rating is derated 15% from 0 to 30°C, derate additional
2.5% per degree from 30 to 60°C.
2
-5V output current is derived from +5V output using a DC-DC converter with 75% efficiency. Therefore, +5V output maximum current is derated by 1.33
x -5V output current.
3
PC mount mating plug connector Phoenix Contact type MSTB 2.5/6-G-5.08.
4
Power LED will pulse on and off if min. load requirement for proper regulation is not met.
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
L-52
OpenLine® Control System
DIMENSIONS
In inches (and millimeters)
4.384
3.931
5.895
CONTROLLER
POWER (J2)
INPUT SUPPLY VOLTAGE (J3)
POWER SUPPLY COVER
P/N 74Z1006
AUXILIARY POWER (J4)
2.893
1 2 3
85-250VAC
50/60 HZ
1
2
2.360
TO OF
DIN RAIL
CHANNEL
1 2 3 4 5
60W OUTPUT PWR
+5 +12 -12
1 2 3 4 5
-
3
DIN LOCKING PLATE
MOUNTING PLATE
POWER SWITCH
SPECIFICATIONS
Part Number: Non-Redundant Operations
OpenLine® Control Systems
Specification
74-PWR-AC4
74-PWR-AC5
74-PWR-DC24
Input Voltage Range:
Input Frequency Range:
Input Current:
Efficiency:
Output Voltage Ranges:
85-250 Vac
47-440 Hz
1.5A max. (RMS) @ 115 Vac
70% typical at full load
23.5 to 24.5 Vdc
85-250 Vac
47-440 Hz
1.0A max. (RMS) @ 115 Vac
70% typical at full load
4.8 to 5.2 Vdc, 11.7 to 12.9 Vdc,
& -11.7 to 12.9 Vdc
18-36 Vdc
Maximum Output
Current1:
Minimum Output Current2:
Secondary Output Current:
Ripple:
Terminal Blocks:
2.5A @ 0-40°C, derates 2.5%
per degree 40-70°C
0A
NA
<50 mV
J2: NA
3.0A @ 0-40°C, derates 2.5%
per degree 40-70°C
0.3A @ 5 Vdc
+12V: 0.1A-0.7A, -12V: 0.0A-0.5A
<50 mV
J2: 1 row of 6 for internal bus power
(Mating connector not included3)
J3: 1 row of 3 for AC input.
(Mating plug included)
J4: 1 row of 4 for auxiliary loads
(Mating plug included)
1 green power supply OK LED4
(1) 14 AWG or (2) 16 AWG
7-9 inch-pounds
2.0A @ 250 Vac fuse,
overload and reverse
polarity protection.
Output cannot be parallel
6.5A @ 0-35°C derates 1.2%
per degree 35-105°C
0.7A @ 5 Vdc
+12, -12, -5 Vdc: 0.70A
@ 25°C
J2: 1 row of 6 for internal bus power
(Mating connector not included3)
J3: 1 row of 3 for AC input.
(Mating plug included)
J4: 1 row of 4 for auxiliary loads
(Mating plug included)
1 green power supply OK LED4
(1) 14 AWG or (2) 16 AWG
7-9 inch-pounds
2.0A @ 250 Vac fuse,
overload and reverse
polarity protection.
Output cannot be parallel
Indicator:
Conductor Size:
Terminal Screw Torque:
Protection:
Bus Output:
1,2,3,4
J3: 1 row of 3 for AC input.
(Mating plug included)
J4: 1 row of 4 for auxiliary loads
(Mating plug included)
1 green power supply OK LED
(1) 14 AWG or (2) 16 AWG
7-9 inch-pounds
3.15A @ 250 Vac fuse,
overload and reverse
polarity protection.
Output cannot be parallel
See previous page.
DC
2.15A @ full. load
4.8 to 5.3 Vdc, -4.8 to -5.2 Vdc,
11.4 to 12.9 Vdc, & -11.4 to -12.9 Vdc
ACCESSORIES
See p. L-54
ORDERING INFORMATION
Part Number
Description
Part Number
Description
74-PWR-AC1
74-PWR-AC2
74-PWR-AC3
85-250 Vac in, 7A @ 5 Vdc, +12 Vdc, -12 Vdc out
85-250 Vac in, 3A @ 5 Vdc, +12 Vdc, -12 Vdc out
85-250 Vac in, 5A @ 5 Vdc,
74-PWR-AC4
74-PWR-AC5
74-PWR-DC24
85-250 Vac in, 2.5A @ 25 Vdc out
85-250 Vac in, 3A @ 24 Vdc out, auxilliary outputs
18-36 Vdc in, 6.5A @ 5 Vdc out, auxilliary outputs
Available from your local Grayhill Distributor. For prices and discounts, contact a local Sales Office, an authorized Distributor or Grayhill.
L-53
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com