Datasheet

MPPT75 MAXIMUM POWER POINT TRACKING
SOLAR BATTERY CHARGE CONTROLLER
The Intronics Power Inc. MPPT75 Solar Charge Controller continually tracks the maximum
power point of the solar panel array, adjusting the circuit parameters approximately two
times per second to maximize energy transfer from the array to the battery bank.
FEATURES
• Automatic tracking of solar panel
maximum power point
• One, two or three stage charging
(selectable)
• High energy conversion efficiency (9497%)
• Tracking of MPPT to within 2%
• Temperature compensated
• LCD display and LED status indicators
• User adjustable set points
• 12V or 24V system capability (selectable)
• 75 amp output rating
• Maximum panel input voltage 80 VDC
• Maximum battery voltage 65 VDC
• 25 amp auxiliary load rated output
• Output current automatically limited to 78
amps
• Self Consumption <1 Watt
• All common grounds
• MCU controlled ventilation fan
• All stainless steel hardware
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555 www.intronicspower.com
CHARGING SEQUENCE
BULK CHARGE
The MPPT75 delivers the maximum power available
from the solar array to the battery bank.
ABSORPTION (If enabled)
When the battery voltage reaches the battery
absorption voltage set point, the controller maintains
the battery charge at that voltage for two hours. If
the system voltage falls below the absorption voltage
set point due to clouds, system loads, etc, the
controller returns to bulk mode. When the battery
voltage rises again to the absorption set point, the
controller maintains that voltage until a total of two
hours (per day) has elapsed.
FLOAT
The controller maintains the battery voltage at the
float voltage set point. There are two float voltage
set points (selectable)
EQUALIZATION (If enabled)
The controller will raise the battery voltage to 15V
(12v system) or 30V (24V system) for a total of one
hour per month to ensure that all batteries and cells
in the battery bank are at an equal state of charge.
Not recommended for gel or AGM batteries.
SETUP
To set up the controller, you must detach the end
panel from the aluminum housing by removing the
four screws.
You will see a small pushbutton and an 8 position
DIP switch. The pushbutton is RESET. It will erase
any stored Equalize and Absorb data, any stored max
amp and amp hour data, and start a fresh search for
the panel Max Power Point.
The yellow button on the top of the controller is used
to navigate between LCD display pages. Pushing it
once and holding it down will change the display
from the normal display to Page 2, which shows:
Aux Output Mode (Refrigeration or Lights)
System nominal voltage (12V or 24V)
Float Voltage at 25 degrees C (13.5/27V or
13.9/27.8V)
Controller temperature in degrees C
Pushing it again and holding it down while the
display shows Page 2 will change the display to
Page 3 which shows:
Absorb disabled/enabled
Equalize enabled/disabled
Absorb charge time so far this day
Equalize time deficit
Pushing it again and holding it down while the
display shows Page 3 will change the display to
Page 4 which shows diagnostic information for
troubleshooting, including software revision, PWM
duty cycle, and float/absorb/equalize voltage limits.
Pushing the button after Page 4 will display Page 5,
which shows the amp hours so far today, plus the
amp hours for the previous five days.
Pushing the button after Page 5 will display Page 6,
which shows the maximum amps so far today, plus
the maximum amps for the previous five days.
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555 www.intronicspower.com
Releasing the pushbutton will return the display to
Page 1 after a few seconds delay.
INSTALLATION
1. Connect the BAT+ and BAT- cables from the
battery bank to the marked terminals on the
controller. Be sure polarity is not reversed.
2. Connect the PANEL+ and PANEL- cables to the
marked terminals on the controller. Do not short
the cables or connect them with reversed polarity.
3. Connect the cables to any auxiliary 12V or 24V
DC loads to the AUX+ and AUX- terminals on the
controller.
DO NOT CONNECT ANY INVERTER TO THE
CONTROLLER. INVERTERS SHOULD BE
CONNECTED DIRECTLY TO THE BATTERY
BANK.
• See the Auxiliary Output Section
The controller can be mounted on a flat surface or
on a wall. Be sure it is in a dry protected location.
If it is not close to the battery bank, be sure to use
heavy cable to reduce voltage loss in the cables.
#10 gauge or 4mm wire or heavier is
recommended. Be sure the batteries are in a
protected area with good ventilation. Install the
controller far enough from the batteries that it will
not be exposed to battery acid splashes or fumes
DISPLAY AND STATUS INDICATORS
In normal operation, the display shows:
Input voltage from the solar panel (Vp) VOLTS
Input current from the panel (Ip) AMPERES
Battery voltage (Vb) VOLTS
Output current to the battery (Ib) AMPERES
There are 5 other pages of data available on the
display, generally used in setting up the system and
checking system performance.
See SETUP.
The leftmost LED shows the battery state of
charge: for 12V or 24V systems
Steady Green: Fully charged, above 13.5/27.0V
Blinking Green: Nearly full above 12.5/25.0V
Steady Yellow; Partial charge above 12.0/24.0V
Blinking Yellow: Partial charge above
11.75/23.5V
Steady Red: Low charge above 11.5/23V
Blinking Red Low charge less than 11.5/23V
DIP SWITCHES
NOTE: DIP switches are set from the factory in
the UP position.
Float Voltage
The leftmost switch on the dipswitch (#8) is Float
Voltage Select. Setting the switch UP enables
High Float (13.9/ 27.8 volts), setting it DOWN
enables Low Float (13.5/27.0 volts)
High Float is recommended for flooded batteries.
Low Float is recommended for sealed, gel and
AGM batteries. You may need to experiment to
find the appropriate setting for your batteries. The
nominal float voltage for 25 degrees C can be seen
on Page 2 of the LCD display. The actual float
voltage will be different from the displayed value
if the temperature is not 25 degrees C.
The temperature can be seen on Page 2 of the
display.
Note: these indications are only approximate
guides to the battery state of charge, due to the
effects of system loads, temperature, battery
condition, etc.
The middle LED (white) is on if the auxiliary
output is on.
The rightmost LED (blue) indicates that the panel
is connected and is charging the battery bank.
System Voltage
The second leftmost switch (#7) is System
Voltage Select. Setting the switch UP selects a 24
volt nominal system. Setting it DOWN selects a
12 nominal volt system.
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555 www.intronicspower.com
Auxiliary Output Mode
The third leftmost switch (#6) is Auxiliary Output
Mode.
The Auxiliary output is used for DC loads, such as
DC lights, radios, water pumps and refrigerators. It
should NOT be connected to any inverters.
There are two setup options for the auxiliary
output, Lights and Refrigeration. Loads such as
lights must have power available at all times if
possible. Therefore, if the Auxiliary Output is set
up in Lights mode, the output will be on unless the
battery voltage falls below the Low Voltage
Disconnect voltage of 11.25V/22.5V for more than
one minute. When the battery voltage rises above
the Reconnect voltage of 12V/24V, the output is
again turned on. This ensures power is always
available, assuming the batteries are not
excessively discharged. However, loads such as
water pumps and refrigeration can be run when
more power is available during the day, and not at
night when power may be more necessary for loads
such as lights.
If the controller is set up in Refrigeration mode, the
output will go on when the battery voltage is above
13/26 volts, and will stay on for a minimum of 15
minutes. If the voltage then falls below 13/26 volts,
the output will go off. The 15 minute delay ensures
that the refrigerator or pump does not cycle
excessively, which can damage the motor, and
consume more energy. Also the higher connect and
disconnect voltages help ensure that the load will
tend to run during the day when there is more
energy available, while conserving battery charge
for the priority loads (generally supplied by an
inverter) at night.
Whether in Lights or Refrigeration mode, if the DC
loads can draw more than 15 amperes, you should
use the Auxiliary Output to control a relay which in
turn runs the loads. This will protect the controller
from possible over current problems, and also
conserve energy. Setting the switch UP selects
Light mode.
Setting it DOWN selects Refrigeration mode.
ABSORPTION
The fourth leftmost switch (#5) is Absorption.
There are two setup options for the charging
algorithm. If Absorb is enabled, the controller will
charge the batteries with the maximum current
available from the solar panels. This is called Bulk
charging. Once the battery voltage reaches the
Absorption voltage (Float voltage plus .75/1.5v), it
will maintain the batteries at the absorption voltage
until it has been at that voltage for a total of one
hour per day. Then the controller will reduce the
battery to the Float voltage, and maintain it at that
voltage for the remainder of the day. If the panels
cannot supply enough current to hold the batteries
at the Absorption or Float voltage, the controller
will supply the maximum current available to the
batteries.
If Absorption is not enabled, the controller will
supply the maximum current available to the
batteries (Bulk charge) until they reach the Float
voltage, and will then maintain them at the float
voltage if possible.
On page 3 of the LCD display you can see the total
minutes of absorption so far in the day.
Setting the switch UP enables absorption
Setting the switch DOWN disables absorption
EQUALIZATION
The fifth leftmost switch (#4) is Equalization
If Equalization is enabled, the controller will raise
the battery voltage to the Equalization voltage
(Float voltage plus 1.25/2.5 volts) for a total of 1.5
hours per month. It will do this in increments when the
panels are able to supply sufficient current to do so,
while keeping track of the equalization time. You
can see the total running deficit of equalization
time on Page 3 of the LCD. If the deficit is zero,
the battery is fully equalized.
Setting the switch UP enables equalization.
Setting the switch DOWN disables equalization.
The three rightmost switches (#3, #2, #1) are not
used.
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555 www.intronicspower.com
TEMPERATURE COMPENSATION
The Float, Absorb and Equalize voltage set points
are temperature compensated at -5 mV per degree
Centigrade per cell.
SPECIFICATIONS
ABSOLUTE MAXIMUM RATINGS
Maximum Panel Voltage
Maximum Battery Voltage
Maximum Output Current to the Battery
Maximum Current on the Auxiliary output
80V
65V
78A
45A
NORMAL OPERATING CONDITIONS
Nominal Battery Voltage 12VDC/24VDC
(selectable)
Nominal Solar Array Voltage 12VDC-65VDC
Solar Array Input Current 0-75 Amperes
Battery Output Current 0-75 Amperes
Controller output power
0-975 watts (12V system)
0-1950 watts (24V system)
Controller Self Consumption <1 Watt
Display accuracy (Page 1) +-5%
Dimensions 7.25” x 6” x 3” high
Weight 3.50 lb
RECOMMENDATIONS
Panels
The controller will work with panels with
maximum open circuit voltages up to 65 volts.
Check the specs of your panels to find their ratings.
Higher voltage panels need smaller cable sizes and
lose less energy in the cabling. Lower voltage
panels can be connected in series for higher output
voltages. Industrial style panels often have ratings
of 200-300 watts and max power voltages of 30-60
volts. The Intronics MPPT75 will work well with
such panels.
SYSTEM VOLTAGE
For small systems, 12V has the advantages of
readily available DC lights and radios, etc. For
larger systems, 24 volts is recommended, as the
controller can supply twice the power, and the
cable sizes can be smaller. Inverters for both 12V
and 24V are readily available.
BATTERY
There are as many opinions on battery choices and
the proper settings for battery charging as there are
experts. Consult the battery manufacturer's
recommendations for more information, and
suggestions as to appropriate settings.
We recommend flooded batteries for consumer
stationary applications because they tend to be
more robust, less costly, and the electrolyte levels
can be checked and topped up.
If you use flooded batteries, (preferably deep cycle,
or golf cart types), we suggest you try using the
Low Float setting with Absorb and Equalize
enabled. If the battery will be used only
occasionally, we suggest disabling Absorb and
enabling Equalize. If it seems like the battery is not
being fully charged, try using the High Float
setting. If the liquid level in the battery does not
need topped up more than twice a year, High Float
will keep the battery somewhat more fully charged.
If excessive gassing and loss of electrolyte occurs,
move back to Low Float, and/or disable Absorb
and/or Equalize.
If you use AGM, sealed, or gel batteries, we
suggest Low Float, Absorb disabled, and Equalize
disabled.
For batteries other than lead acid, consult the
battery manufacturer's recommendations.
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555 www.intronicspower.com
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555 www.intronicspower.com