MPPT25 MAXIMUM POWER POINT TRACKING SOLAR

MPPT25 MAXIMUM POWER POINT TRACKING
SOLAR BATTERY CHARGE CONTROLLER
The Intronics Power Inc. MPPT25 Solar Charge Controller continually tracks the maximum
power point of the solar panel array, adjusting the circuit parameters approximately two
times per second to maximize energy transfer from the array to the battery bank.
FEATURES
• Automatic tracking of solar panel maximum
power point
• Two or three stage charging (selectable)
• High energy conversion efficiency (94-97%)
• Tracking of MPPT to within 2%
• Temperature compensated
• LCD display and LED status indicators
• User adjustable set points
• 12V or 24V system capability (selectable)
• 25 amp output rating
• Maximum panel input voltage 80 VDC
• Maximum battery voltage 65 VDC
• 25 amp auxiliary load output
• Reverse connection protection
• Output current automatically limited to 27
amps
• All common grounds
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555
INSTALLATION
1. Connect the BAT+ and BAT- cables from the battery
bank to the marked terminals on the controller. Be sure
BULK CHARGE
polarity is not reversed. If these cables are reversed, the
protective fuse will blow, and will need to be replaced.
The MPPT25 delivers the maximum power available
2. Connect the PANEL+ and PANEL- cables to the
from the solar array to the battery bank.
marked terminals on the controller. Do not short the
cables or connect them with reversed polarity, or the
ABSORPTION (If enabled)
fuse will blow and will need to be replaced.
3. Connect the cables to any auxiliary 12V or 24V loads
When the battery voltage reaches the battery absorption
to the AUX+ and AUX- terminals on the controller. If
voltage set point, the controller maintains the battery
the cables are shorted or load is greater than the fuse
charge at that voltage for two hours. If the system
rating, the fuse will blow and need to be replaced. DO
voltage falls below the absorption voltage set point due
NOT CONNECT ANY INVERTER TO THE
to clouds, system loads, etc, the controller returns to
CONTROLLER. INVERTERS SHOULD BE
bulk mode. When the battery voltage rises again to the
CONNECTED DIRECTLY TO THE BATTERY
absorption set point, the controller maintains that
BANK.
voltage until a total of two hours (per day) has elapsed.
• See the Auxiliary Output Section
CHANGING SEQUENCE
FLOAT
The controller can be mounted on a flat surface or on a
wall. Be sure it is in a dry protected location. If it is not
The controller maintains the battery voltage at the float
close to the battery bank, be sure to use heavy cable to
voltage set point.
reduce voltage loss in the cables. #10 gauge or 4mm
wire or heavier is recommended. Be sure the batteries
EQUALIZATION (If enabled)
are in a protected area with good ventilation. Install the
controller far enough from the batteries that it will not
The controller will raise the battery voltage to 15V (12v
system) or 30V (24V system) for a total of one hour per be exposed to battery acid splashes or fumes.
month to ensure that all batteries and cells in the battery
bank are at an equal state of charge. Not recommended There are three other pages of data available on the
display, generally used only in setting up the system.
for gel or AGM batteries.
See SETUP.
DISPLAY AND STATUS INDICATORS
In normal operation, the display shows:
Input voltage from the solar panel (Vp) VOLTS
Input current from the panel (Ip) AMPERES
Battery voltage (Vb) VOLTS
Output current to the battery (Ib) AMPERES
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555
The leftmost LED shows the battery state of charge:
for 12V or 24V systems
Steady Green: Fully charged, above 13.5/27.0V
Blinking Green: Nearly full above 12.5/25.0V
Steady Yellow; Partial charge above 12.0/24.0V
Blinking Yellow: Partial charge above 11.75/23.5V
Steady Red: Low charge above 11.5/23V
Blinking Red Low charge less than 11.5/23V
Note: these indications are only approximate guides to
the battery state of charge, due to the effects of system
loads, battery condition, etc.
Pushing it again and holding it down while the
display shows Page 2 will change the display to Page
3 which shows:
Absorb disabled/enabled
Equalize enabled/disabled
Absorb charge time so far this day
Equalize time deficit
The middle LED (white) is on if the auxiliary output is
on.
Pushing it again and holding it down while the
display shows Page 3 will change the display to Page
4 which shows diagnostic information for
troubleshooting, including software revision, PWM
duty cycle, and float/absorb/equalize voltage limits.
The rightmost LED (blue) indicates that the panel is
connected and is charging the battery bank.
Releasing the pushbutton will return the display to
Page 1 after a few seconds delay.
SETUP
For version 1.1 and higher
Pushing the button again after Page 4 will display
Page 5, which shows the total amp-hours delivered
so far today, plus the accumulated amp hours for
each of the previous five days.
To set up the controller, you must detach the end panel
from the aluminum housing by removing the four
screws.
You will see two small pushbuttons and two DIP
switches. The leftmost pushbutton is RESET. It will
erase any stored Equalize and Absorb data and start a
fresh search for the panel MPPT.
The second (long) pushbutton is used to navigate
between the four display screens. Pushing it once and
holding it down will change the display from the
normal display to Page 2, which shows:
Aux Output Mode (Refrigeration or Lights)
System nominal voltage (12V or 24V)
Float Voltage at 25 degrees C (13.5/27V or
13.9/27.8V)
Controller temperature in degrees C
Pushing the button after Page 5 will display Page 6,
which shows the maximum amps so far today, plus
the maximum amps for the previous five days.
DIP SWITCHES
There are two dipswitches. The small one has two
switches, and the large has four switches.
Large Dipswitch
The leftmost switch is Auxiliary Output Mode. If
the DC loads are for lights or other devices that need
to be available at night, set the switch UP.
If the DC loads are things like refrigeration or pumps
that can be used during the day, and are not
necessary at night, set the switch DOWN.
See the Auxiliary Output section for more
explanation.
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555
The second leftmost switch is System Voltage Select.
Setting the switch UP selects a 24 volt system. Setting
it DOWN selects a 12 volt system.
The second rightmost switch is Float Voltage Select.
Setting the switch UP enables High Float (13.9/ 27.8
volts), setting it DOWN enables Low Float (13.5/27.0
volts)
High Float is recommended for flooded batteries. Low
Float is recommended for sealed, gel and AGM
batteries. You may need to experiment to find the
appropriate setting for your batteries. The nominal
float voltage for 25 degrees C can be seen on Page 2
of the LCD display. The actual float voltage will be
different from the displayed value if the temperature is
not 25 degrees C.
The temperature can be seen on Page 2 of the display.
If Absorption is not enabled, the controller will supply
the maximum current available to the batteries (Bulk
charge) until they reach the Float voltage, and will
then maintain them at the float voltage if possible.
On page 3 of the LCD display you can see the total
minutes of absorption so far in the day.
EQUALIZATION
If Equalization is enabled, the controller will raise the
battery voltage to the Equalization voltage (Float
voltage plus 1.25/2.5 volts) for a total of 1.5 hours per
month. It will do this in increments when the panels
are able to supply sufficient current to do so, while
keeping track of the equalization time. You can see
the total running deficit of equalization time on Page 3
of the LCD. If the deficit is zero, the battery is fully
equalized.
The right most switch is not used.
Auxiliary Output
Small Dipswitch
The left switch is Equalize Enable. Setting the switch
UP enables equalization.
The right switch is Absorb Enable. Setting the switch
UP enables absorption (three stage charging).
The Equalize and Absorb settings can be seen on
Page 3 of the display.
ABSORPTION
There are two setup options for the charging
algorithm. If Absorb is enabled, the controller will
charge the batteries with the maximum current
available from the solar panels. This is called Bulk
charging. Once the battery voltage reaches the
Absorption voltage (Float voltage plus .75/1.5v), it
will maintain the batteries at the absorption voltage
until it has been at that voltage for a total of one hour
per day. Then the controller will reduce the battery to
the Float voltage, and maintain it at that voltage for
the remainder of the day. If the panels cannot supply
enough current to hold the batteries at the Absorption
or Float voltage, the controller will supply the
maximum current available to the batteries.
The Auxiliary output is used for DC loads, such as DC
lights, radios, water pumps and refrigerators. It should
NOT be connected to any inverters.
There are two setup options for the auxiliary output,
Lights and Refrigeration. Loads such as lights must
have power available at all times if possible.
Therefore, if the Auxiliary Output is set up in Lights
mode, the output will be on unless the battery voltage
falls below the Low Voltage Disconnect voltage of
11.25V for more than one minute. When the battery
voltage rises above the Reconnect voltage of 12/24V,
the output is again turned on. This ensures power is
always available, assuming the batteries are not
excessively discharged.
However, loads such as water pumps and refrigeration
can be run when more power is available during the
day, and not at night when power may be more
necessary for loads such as lights.
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555
If the controller is set up in Refrigeration mode, the
output will go on when the battery voltage is above
13/26 volts, and will stay on for a minimum of 15
minutes. If the voltage then falls below 13/26 volts,
the output will go off. The 15 minute delay ensures
that the refrigerator or pump does not cycle
excessively, which can damage the motor, and
consume more energy. Also the higher connect and
disconnect voltages help ensure that the load will tend
to run during the day when there is more energy
available, while conserving battery charge for the
priority loads (generally supplied by an inverter) at
night.
Whether in Lights or Refrigeration mode, if the DC
loads can draw more than 15 amperes, you should use
the Auxiliary Output to control a relay which in turn
runs the loads. This will protect the controller from
possible over current problems, and also conserve
energy.
TEMPERATURE COMPENSATION
The Float, Absorb and Equalize voltage set points are
temperature compensated at -5 mV per degree
Centigrade per cell.
NORMAL OPERATING CONDITIONS
Nominal Battery Voltage 12VDC/24VDC (selectable)
Nominal Solar Array Voltage 12VDC-65VDC
Solar Array Input Current
0-25 Amperes
Battery Output Current
0-25 Amperes
Controller output power
0-325 watts (12V system)
0-650 watts (24V system)
Controller Self Consumption
<1 Watt
Dimensions
6” x 6” x 3” high
RECOMMENDATIONS
Panels
The controller will work with panels with maximum
open circuit voltages up to 65 volts. Check the specs
of your panels to find their ratings. Higher voltage
panels need smaller cable sizes and lose less energy in
the cabling. Lower voltage panels can be connected in
series for higher output voltages. Industrial style
panels often have ratings of 200-300 watts and max
power voltages of 40-55 volts. The Intronics MPPT 25
will work well with such panels.
SYSTEM VOLTAGE
SPECIFICATIONS
ABSOLUTE MAXIMUM RATINGS
Maximum Panel Voltage
Maximum Battery Voltage
Maximum Output Current to the Battery
Maximum Current on the Auxiliary output
80V
65V
30A
30A
For small systems, 12V has the advantages of readily
available DC lights and radios, etc. For larger systems,
24 volts is recommended, as the controller can supply
twice the power, and the cable sizes can be smaller.
Inverters for both 12V and 24V are readily available.
BATTERY
There are as many opinions on battery choices and the
proper settings for battery charging as there are
experts. Consult the battery manufacturer's
recommendations for more information, and
suggestions as to appropriate settings.
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555
We recommend flooded batteries for consumer
stationary applications because they tend to be more
robust, less costly, and the electrolyte levels can be
checked and topped up.
If you use flooded batteries, (preferably deep cycle, or
golf cart types), we suggest you try using the Low
Float setting with Absorb and Equalize enabled. If the
battery will be used only occasionally, we suggest
disabling Absorb and enabling Equalize. If it seems
like the battery is not being fully charged, try using the
High Float setting. If the liquid level in the battery
does not need topped up more than twice a year, High
Float will keep the battery somewhat more fully
charged. If excessive gassing and loss of electrolyte
occurs, move back to Low Float, and/or disable
Absorb and/or Equalize.
If you use AGM, sealed, or gel batteries, we suggest
Low Float, Absorb disabled, and Equalize disabled.
For batteries other than lead acid, consult the battery
manufacturer's recommendations.
1400 PROVIDENCE HIGHWAY • BUILDING 2 NORWOOD, MASSACHUSETTS 02062-5015
PHONE: 781-551-5500 FAX: 781-551-5555