69-0579 - T87F Zone Thermostat and 137421N,P

T87F Zone Thermostat and
137421N,P Wallplates; T87F Zone
Thermostat and Q539A,B Subbases
INSTALLATION INSTRUCTIONS
APPLICATION
Thermostats. The T87F is used with the 137421N or P
Wallplate (provided) or Q539A or B Subbase (ordered
separately), depending on application. See Table 1 for
thermostat/wallplate and subbase applications and
specifications.
The T87F Thermostat provides 24 Vac single-stage
temperature control of Honeywell Zone Control Panels.
The panel operates the heating or cooling systems and
zone dampers in response to the T87F Zone
Table 1. Thermostat/Wallplate and Subbase Applications and Specifications.
Thermostat
/Wallplate
or Subbase
T87F3707/
137421N
T87F3715/
137421P
T87F3715/
Q539A1436
T87F3707/
Q539A1428
T87F3715/
Q539B1039
Switching
Application
System
Fan
Comments
To control zones other than zone
1 using MM-2 or MM-3 Zone
Control Panels. To control zone
damper actuators in independent
heating-only systems.
None
None
Wallplate included with
thermostat. Terminals are
marked: W, R, Y.
To control any zone on TZ-3,
EZ-2, EZ-4, EMM-3 or EMM-3U
or zone one on MM-2 or MM-3
Zone Control Panels.
COOL-OFFHEAT
ON-AUTO
Q539A ordered
separately. Terminals
marked: R,W,Y,G,O,B.
To control zone damper
actuators in independent zones
in heating-cooling systems.
HEAT__COOL
None
Q539B ordered
separately. Terminals
marked: 4,5,6.
T87F3707/
Q539B1021
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of an old control.
INSTALLATION
When Installing This Product...
1.
2.
3.
4.
5.
® U.S. Registered Trademark
Copyright © 2002 Honeywell •
•All Rights Reserved
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
Disconnect the power supply to prevent electrical
shock or equipment damage.
Check the rating given in the instructions and on
the product to make sure the product is suitable for
your application.
Installer must be a trained, experienced service
technician.
After completing installation, use these instructions
to check out the product operation.
69-0579-4
T87F ZONE THERMOSTAT AND 137421N,P WALLPLATES; T87F ZONE THERMOSTAT AND Q539A,B SUBBASES
Selecting Location
5.
• Install the thermostat about 5 ft (1.5 meters) above the
floor in an area with good air circulation at average
temperature.
• Do not install the thermostat where it can be affected
by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside
wall behind the thermostat.
• Handle this thermostat carefully; it is a precision
instrument that was carefully calibrated at the factory.
Loosely fasten the thermostat wallplate or subbase
to the wall with a screw through the left mounting
hole. See Fig. 3.
Adjust the wallplate or subbase so it is approximately level and start the second screw through
the right mounting slot. Do not tighten.
6.
T87F3715/Q539B1039
T87F3707/Q539B1021
TEMPERATUE RISE
ADJUSTABLE
HEAT
ANTICIPATOR
TEMPERATUE FALL
W
Y
HEAT
CAUTION
J
Electrical Shock Hazard
Can cause personal injury or equipment
damage.
Disconnect power supply before installation.
COOL
HEAT
J
R/5
Mounting and Wiring
COOL
W/4
Y/6
R
C
IMPORTANT
To prevent interference with thermostat linkage,
keep wire length to a minimum and run wires as
close as possible to the subbase.
AT140 TRANSFORMER
ARD CONFIGURED
WITH POWER OPEN
M14842
All wiring must comply with local codes and ordinances.
Fig. 1. Wiring single ARD (power open) to thermostat.
T87F Zone Thermostat and wallplate or subbase are
used in zoned conventional single-stage heating or
heating-cooling systems.
T87F3715/Q539B1039
T87F3707/Q539B1021
137421 Wallplate or Q539 Subbase
TEMPERATUE RISE
ADJUSTABLE
HEAT
ANTICIPATOR
REPLACEMENT APPLICATION
1. Remove old equipment. Dispose of properly. See
Mercury Notice.
2. Check the existing wallplate or subbase wires for
cracked or frayed insulation.
3. Replace any wires in poor condition.
4. If the wires are plastered into the wall, make a hole
next to the wires so they can be pushed back into
the wall later.
5. Continue with step 3 for New Installation.
TEMPERATUE FALL
W
Y
HEAT
COOL
HEAT
COOL
2
J
J
R/5
NEW INSTALLATIONS
1. Run low voltage thermostat cable (if necessary) to
the thermostat location.
2. Pull about 3 in. (76 mm) of cable through a hole in
the wall.
3. Connect wires to the terminals inside the wallplate
or subbase. See Fig. 1 and 2 or zone control panel
installation instructions for wiring diagrams of typical zone systems.
4. Push excess wire back through the hole and plug
any opening with insulation to prevent drafts that
can affect thermostat performance.
3
DAMPER
ACTUATOR
1
W/4
4
(COM)
1
5
Y/6
6
Z
3
X
(HOT)
2
L2
L1
(HOT)
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2 NO SYSTEM SWITCHING ON 137421 WALLPLATE.
137421 Wiring Cross Reference
Old Terminal
New Terminal
4
W
5
R
6
Y
69-0579-4
3 FOR CORRECT SYSTEM OPERATION, DO NOT DISCONNECT FACTORYINSTALLED J-J JUMPER ON Q539B.
M19059
Fig. 2. Wiring T87F Thermostat and Q539B Subbase
or 137421 Wallplate in independent zone.
2
T87F ZONE THERMOSTAT AND 137421N,P WALLPLATES; T87F ZONE THERMOSTAT AND Q539A,B SUBBASES
THERMOSTAT
CABLE
ENTRANCE
HOLE
SPIRIT
LEVEL
MOLDED POST
THERMOSTAT
CABLE
ENTRANCE
HOLE
MOUNTING
HOLES
137421
1 WALLPLATE
MOUNTING
SLOTS
T87F
Q539
SUBBASE
1
CAPTIVE
MOUNTING
SCREWS (3)
HORIZONTAL
CENTER
LINE
THERMOSTAT
COVER RING
1
USE 137421 WALLPLATE FOR HEAT ONLY APPLICATIONS.
SEE TABLE 1 APPLICATION INFORMATION.
M19048
OPENING
FOR
THERMOSTAT
WIRING
Fig. 3. Mounting T87F Thermostat and 137421
Wallplate or Q539 Subbase.
Level the thermostat wallplate or subbase exactly
using a spirit level as shown in Fig. 4.
Settings and Adjustments
Temperature Selection
To select the desired temperature for each zone, turn the
transparent dial on the zone thermostat until the desired
point on the setting scale (top scale) is aligned with the
pointer.
Tighten mounting screws.
System and Fan Switching
T87 Thermostat
1.
2.
M1371B
Fig. 4. Leveling wallplate or subbase before
mounting T87F.
IMPORTANT
Do not overtighten thermostat captive mounting
screws because damage to subbase threads
can result.
8.
MOUNTING
SLOTS
9
[14]
16
VERTICAL GUIDE
IMPORTANT
An incorrectly leveled thermostat causes the
temperature control to deviate from setpoint.
7.
1 [13]
2
Before mounting the thermostat, see Heat Anticipator Adjustment in Settings and Adjustments section.
Align the thermostat over the wallplate or subbase
and tighten the three mounting screws.
Q539A
The Q539A provides System and Fan switches to control
heating-cooling equipment and zone one fan in multizone applications:
• The System switch controls the system operation:
— Heat: Only the heating system operates.
— Off: Both heating and cooling control systems are
disconnected.
— Cool: Only the cooling system operates.
• The Fan switch controls the fan operation:
— Auto: The fan operates in response to the plenum
fan control in heating; the fan operates in
response to the thermostat in cooling.
— On: The fan runs continuously.
• To change positions, use thumb and index fingers to
move the switch lever to the desired position. Place
the switch lever directly over the selected function
indicator mark.
3
69-0579-4
T87F ZONE THERMOSTAT AND 137421N,P WALLPLATES; T87F ZONE THERMOSTAT AND Q539A,B SUBBASES
Q539B
The Q539B provides System switching to control damper
actuators in independent zones of heating-cooling
systems.
IMPORTANT
To assure accurate temperature control, do not
touch or breathe on the thermostat bimetal or
thermometer.
NOTE: The Q539B System switch must be set to the
dame position as the System switch on the thermostat controlling the heating-cooling equipment.
Multizone System
HEATING
1. Set each thermostat System switch to Heat and
Fan switch to Auto on the TZ-3, EMM-3, EMM-3U,
EZ-2, and EZ-4.
2. On the MM-2 and MM-3, set zone one thermostat
subbase System switch to heat and Fan switch to
Auto.
3. Turn Zone one thermostat dial 10°F (6°C) above
room temperature to call for heat.
4. Turn dials on all other zone thermostats 20°F (6°C)
below room temperature.
5. Be aware that zone one damper remains open and
all other zone dampers close. (Dampers can take
up to 30 seconds to open or close fully.)
6. Observe that furnace starts immediately and fan
starts after a short delay.
7. To check zones other than zone one, turn the dial
on one of the zone thermostats 10°F (6°C) above
room temperature to call for heat.
8. Be aware that the associated zone damper opens.
9. Turn that zone thermostat dial 10°F (6°C) below
room temperature; damper then closes.
10. Repeat steps 7-9 for each zone other than zone
one.
11. Turn zone one thermostat dial 10°F (6°C) below
room temperature to end call for heat.
12. Unless another thermostat is calling for heat, the
furnace shuts off and the fan shuts off after a short
time. All dampers then open unless set to closed
on the MM-2 or MM-3 panel.
• Set the System switch to:
— Heat: When the thermostat is calling for heat, the
damper opens; when the thermostat is satisfied,
the damper closes.
— ____: The thermostat is not set to heat or cool;
the damper remains in the position (Open or
Closed) that it was in when the switch position
changed.
— Cool: When the thermostat is calling for cooling,
the damper opens; when the thermostat is satisfied, the damper closes.
• To change positions, use thumb and index fingers to
move the switch lever to the desired position. Place
the switch lever directly over the selected function
indicator mark.
Heat Anticipator Adjustment
The T87F Thermostat has an adjustable heat anticipator.
When the T87F is connected to a zone panel, the heat
anticipator must be set at 0.1A for correct system
operation. When the T87F is connected to a damper in
an independent zone application, the heat anticipator
must be set to 0.4A for proper system operation. See Fig.
5.
1.0
.8
.6
.5
.4
.3
SCALE
COOLING
1. Set each thermostat System switch to Cool and
Fan switch to Auto on the TZ-3, EMM-3, EMM-3U,
EZ-2 and EZ-4.
2. On the MM-2 and MM-3, set zone one thermostat
subbase System switch to Cool and Fan switch to
Auto.
3. Turn zone one thermostat dial 10°F (6°C) below
room temperature to call for cooling.
4. Turn dials on all other zone thermostats 10°F (6°C)
above room temperature.
5. Be aware that zone one damper remains open; all
other zone dampers close. Dampers can take up to
30 seconds to open or close fully.
6. Observe that cooling and fan come on.
.2
.15
HOLE SUITABLE FOR
PENCIL POINT
TO MOVE INDICATOR
.12
HEAT
ANTICIPATOR
INDICATOR
M1368A
Fig. 5. Adjusting heat anticipator.
IMPORTANT
To prevent compressor short cycling, a minimum off-time may be included to provide a fiveminute time delay before activating the compressor after the thermostat last turned off the
compressor, or after the system first received
power. This delay protects the compressor.
Checkout
When installation is complete, turn on the power supply
and check thermostat operation using the following
procedure. For complete checkout of entire zone system,
refer to the zone control panel installation instructions.
CAUTION
7.
Equipment Damage Hazard.
Shorting across thermostat terminals of zone
control panels can damage heat anticipator.
Check operation using these instructions.
8.
9.
10.
69-0579-4
4
To check zones other than zone one, turn the dial
on one of the zone thermostats 10°F (6°C) below
room temperature to call for cooling.
Be aware that the associated zone damper opens.
Turn that zone thermostat dial 10°F (6°C) above
room temperature; damper then closes.
Repeat steps 7-9 for each zone other than zone
one.
T87F ZONE THERMOSTAT AND 137421N,P WALLPLATES; T87F ZONE THERMOSTAT AND Q539A,B SUBBASES
11.
12.
Recalibration
Turn zone one thermostat dial 10°F (6°C) above
room temperature to end call for cooling.
Unless another thermostat is calling for cooling,
cooling and the fan shut off. All dampers then open
unless set to closed on the MM-2 or MM-3 panel.
The T87F is accurately calibrated at the factory under
controlled conditions and recalibration is not necessary. If
it appear that the thermostat is out of calibration:
1. Make sure the thermostat is level and not subjected to radiant heat from the sun, radiators, or
appliances.
1. Remove the thermostat cover ring to observe the
mercury switch action.
2. After a five- or ten-minute off period (with thermostat setting below room temperature), slowly raise
the setting until the switch just makes contact. If
the thermometer pointer and setting indicator have
the same reading the instant the switch makes, no
recalibration is necessary.
3. If recalibration is necessary: turn the setting dial a
few degrees above room temperature and remove
the cover.
4. Slip the 104994 Calibration Wrench (ordered separately) onto the hex under the bimetal coil and,
holding the dial firmly, turn the hex clockwise until
the mercury breaks contact. See Fig. 6.
5. Turn the dial to a low setting so the thermostat
loses the heat it gained from hands and its own
operation. Wait at least five minutes.
6. Slowly turn the dial until the pointers have the
same reading.
7. Firmly holding the dial from turning, carefully turn
the hex counterclockwise until the mercury switch
slips to the heating contact end of the tube.
8. Recheck the calibration, select the desired temperature, and replace the cover.
FAN
1. Set the Fan switch on the zone one thermostat
subbase to On and the System switch to Off.
2. Observe that the fan runs continuously.
3. Move the Fan switch to Auto to control the fan
operation with the plenum fan control in heating
with the thermostat in cooling.
Independent Zone
• Use the T87F with the 137421N or P Wallplate for
heat-only independent zone applications.
• Use the subbase only to control heating and cooling of
independent zones.
• In this application, the T87F controls only the damper
actuator; the thermostat is not connected to the
heating or cooling equipment. A separate thermostat/
subbase is required to control the heating and cooling
equipment. See the thermostat instructions for
heating-cooling equipment checkout.
T87F THERMOSTAT/Q539B SUBBASE
1. With the heating equipment on and Q539B subbase System switch set to Heat, turn the thermostat dial 10°F (6°C) above room temperature to call
for heat. The damper opens.
NOTE: The damper can take up to 30 seconds to fully
open or close.
2.
3.
4.
NOTE: When the T87F provides cooling control, calibration for heating automatically calibrates for
cooling.
Turn the thermostat dial 10°F(6°C) below room
temperature; damper closes.
With the cooling equipment on and the Q539B
Subbase System switch set to Cool, turn the thermostat dial 10°F (6°C) below room temperature to
call for cooling; damper opens.
Turn the thermostat dial 10°F (6°C) above room
temperature; damper closes.
SETTING SCALE
ADJUSTABLE RANGE
STOPS ON SOME MODELS
T87F THERMOSTAT/137421 WALLPLATE
1. With the heating equipment on, turn the thermostat
dial 10°F (6°C) above the room temperature to call
for heat; damper opens.
NOTE: Damper can take up to 30 seconds to fully open
or close.
2.
CALIBRATION NUT
ROOM TEMPERATURE SCALE
CAPTIVE
MOUNTING
SCREW (3)
Turn the thermostat dial 10°F (6°C) below room
temperature; damper closes.
HEAT ANTICIPATOR INDICATOR
M19049
Fig. 6. Recalibrating T87F Thermostat.
5
69-0579-4
T87F ZONE THERMOSTAT AND 137421N,P WALLPLATES; T87F ZONE THERMOSTAT AND Q539A,B SUBBASES
69-0579-4
6
T87F ZONE THERMOSTAT AND 137421N,P WALLPLATES; T87F ZONE THERMOSTAT AND Q539A,B SUBBASES
7
69-0579-4
T87F ZONE THERMOSTAT AND 137421N,P WALLPLATES; T87F ZONE THERMOSTAT AND Q539A,B SUBBASES
Automation and Control Solutions
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422
69-0579-4 G.H. Rev. 08-02
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
www.honeywell.com/yourhome