Installation Guide - The Energy Conscious

Installation
Guide
TH3110B
Non-programmable Digital Thermostat
PRO TH3110B Non-programmable Digital Thermostat
Product Application
Table of contents
This thermostat provides electronic control of 24 VAC single-stage heating and cooling systems, or 750 mV heating systems.
Installation
Pre-installation checklist ................2
Wallplate installation ......................3
Wiring..............................................4
Wiring diagrams ..............................5
System Types
Power Type
•
Gas, oil, or electric heat with air
conditioning
•
•
Warm air, hot water, high-efficiency
furnaces, heat pumps, steam, gravity
System Settings
•
Heat only
Fan Settings
•
Heat only with fan
•
•
Cool only
•
750 mV heating systems
•
AA alkaline batteries (2)
Heat, Off, Cool
Appendices
Quick reference to controls..........10
Quick reference to display............10
Compressor protection ................10
In case of difficulty ......................11
Accessories....................................12
Specifications ................................12
Installer Setup
Fan operation settings ....................6
Battery installation ..........................7
Thermostat mounting ....................7
Installer setup..................................8
Installer system test ........................9
Auto, On
Installation tips
Install the thermostat about 5 feet (1.5m) above the floor in an area
with good air circulation at average temperature.
Must be installed by a trained, experienced technician
•
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
•
Check the ratings in this booklet to verify that this product is suitable for your
application (see page 12).
•
Always test for proper operation after installation (see pages 8-9).
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not
place the old control in the trash. Contact your local waste management authority for
instructions regarding recycling and proper disposal.
® U.S. Registered Trademark. Patents pending.
Copyright © 2005 Honeywell International Inc. All rights reserved.
NO
NO
NO
Do not install in locations where the thermostat can be affected by:
• Drafts or dead spots behind doors and in corners
• Hot or cold air from ducts
• Sunlight or radiant heat from appliances
• Concealed pipes or chimneys
• Unheated/uncooled areas such as an outside wall behind the thermostat
1
PRO TH3110B Non-programmable Digital Thermostat
Product Application
Table of contents
This thermostat provides electronic control of 24 VAC single-stage heating and cooling systems, or 750 mV heating systems.
Installation
Pre-installation checklist ................2
Wallplate installation ......................3
Wiring..............................................4
Wiring diagrams ..............................5
System Types
Power Type
•
Gas, oil, or electric heat with air
conditioning
•
•
Warm air, hot water, high-efficiency
furnaces, heat pumps, steam, gravity
System Settings
•
Heat only
Fan Settings
•
Heat only with fan
•
•
Cool only
•
750 mV heating systems
•
AA alkaline batteries (2)
Heat, Off, Cool
Appendices
Quick reference to controls..........10
Quick reference to display............10
Compressor protection ................10
In case of difficulty ......................11
Accessories....................................12
Specifications ................................12
Installer Setup
Fan operation settings ....................6
Battery installation ..........................7
Thermostat mounting ....................7
Installer setup..................................8
Installer system test ........................9
Auto, On
Installation tips
Install the thermostat about 5 feet (1.5m) above the floor in an area
with good air circulation at average temperature.
Must be installed by a trained, experienced technician
•
Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
•
Check the ratings in this booklet to verify that this product is suitable for your
application (see page 12).
•
Always test for proper operation after installation (see pages 8-9).
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not
place the old control in the trash. Contact your local waste management authority for
instructions regarding recycling and proper disposal.
® U.S. Registered Trademark. Patents pending.
Copyright © 2005 Honeywell International Inc. All rights reserved.
NO
NO
NO
Do not install in locations where the thermostat can be affected by:
• Drafts or dead spots behind doors and in corners
• Hot or cold air from ducts
• Sunlight or radiant heat from appliances
• Concealed pipes or chimneys
• Unheated/uncooled areas such as an outside wall behind the thermostat
1
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Pre-installation checklist
Wallplate installation
Package contents
Grasp top and bottom of wallplate
and pull to remove from thermostat.
Remove the wallplate from the thermostat as shown at left, then follow
directions below for mounting.
Check to make sure your package includes the following items:
1 Pull wires through wire hole.
2 Position wallplate on wall, level and
mark hole positions with pencil.
3 Drill holes at marked positions as
shown below, then tap in
supplied wall anchors.
Wall anchors and
mounting screws
(2 each)
4 Place wallplate over anchors, insert
and tighten mounting screws.
Operating manual
PRO TH3110B
digital thermostat
(wallplate attached to back)
AA alkaline
batteries (2)
Drill 3/16” holes for drywall.
Drill 7/32” holes for plaster.
Wire hole
Required tools & supplies
•
No. 2 Phillips screwdriver
•
Small pocket screwdriver
•
Drill
•
Drill bit (3/16” for drywall, 7/32” for plaster)
•
Hammer
•
Pencil
•
Electrical tape
•
Level (optional)
Wall anchors
2
3
Mounting screws
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Pre-installation checklist
Wallplate installation
Package contents
Grasp top and bottom of wallplate
and pull to remove from thermostat.
Remove the wallplate from the thermostat as shown at left, then follow
directions below for mounting.
Check to make sure your package includes the following items:
1 Pull wires through wire hole.
2 Position wallplate on wall, level and
mark hole positions with pencil.
3 Drill holes at marked positions as
shown below, then tap in
supplied wall anchors.
Wall anchors and
mounting screws
(2 each)
4 Place wallplate over anchors, insert
and tighten mounting screws.
Operating manual
PRO TH3110B
digital thermostat
(wallplate attached to back)
AA alkaline
batteries (2)
Drill 3/16” holes for drywall.
Drill 7/32” holes for plaster.
Wire hole
Required tools & supplies
•
No. 2 Phillips screwdriver
•
Small pocket screwdriver
•
Drill
•
Drill bit (3/16” for drywall, 7/32” for plaster)
•
Hammer
•
Pencil
•
Electrical tape
•
Level (optional)
Wall anchors
2
3
Mounting screws
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Wiring
Wiring diagrams
CAUTION: ELECTRICAL HAZARD. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only.
Use either O or B terminals for changeover valve.
Wiring
Keep wires in this
shaded area
1 Loosen screw terminals, insert
wires into terminal block, then retighten screws.
2 Push excess wire back into the
wall opening. Keep wires in shaded
area as shown at left.
Use a small piece of wire (not supplied) to connect W and Y terminals.
Set fan operation switch to Heat Pump (see page 6) and configure for heat pump (see pg. 8).
Typical 1H/1C system: 1 transformer
Typical 1H/1C system: 2 transformers
3 Plug the wall opening with nonflammable insulation to prevent
drafts from affecting thermostat
operation.
Remove jumper
Terminal
block
Terminal Designations
W Heat relay.
Typical 1H/1C heat pump system
Typical heat-only system
Typical heat-only system with fan
Typical cool-only system
Y Compressor contactor.
NOTES
G Fan relay.
R & Rc terminals
In single-transformer system, leave metal
jumper in place between R & Rc. Remove
metal jumper if two-transformer system.
O Heat pump changeover valve energized in cooling.
Rc Cooling power. Connect to
secondary side of cooling
system transformer.
Heat pump systems
If wiring to a heat pump, use a small piece of
wire (not supplied) to connect terminals W
and Y.
R Heating power. Connect to
secondary side of heating
system transformer.
Wire specifications
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
B Heat pump changeover valve energized in heating.
4
5
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Wiring
Wiring diagrams
CAUTION: ELECTRICAL HAZARD. Can cause electrical shock or equipment damage.
Disconnect power before wiring.
Power supply. Provide disconnect means and overload protection as required.
Factory-installed jumper. Remove for 2-transformer systems only.
Use either O or B terminals for changeover valve.
Wiring
Keep wires in this
shaded area
1 Loosen screw terminals, insert
wires into terminal block, then retighten screws.
2 Push excess wire back into the
wall opening. Keep wires in shaded
area as shown at left.
Use a small piece of wire (not supplied) to connect W and Y terminals.
Set fan operation switch to Heat Pump (see page 6) and configure for heat pump (see pg. 8).
Typical 1H/1C system: 1 transformer
Typical 1H/1C system: 2 transformers
3 Plug the wall opening with nonflammable insulation to prevent
drafts from affecting thermostat
operation.
Remove jumper
Terminal
block
Terminal Designations
W Heat relay.
Typical 1H/1C heat pump system
Typical heat-only system
Typical heat-only system with fan
Typical cool-only system
Y Compressor contactor.
NOTES
G Fan relay.
R & Rc terminals
In single-transformer system, leave metal
jumper in place between R & Rc. Remove
metal jumper if two-transformer system.
O Heat pump changeover valve energized in cooling.
Rc Cooling power. Connect to
secondary side of cooling
system transformer.
Heat pump systems
If wiring to a heat pump, use a small piece of
wire (not supplied) to connect terminals W
and Y.
R Heating power. Connect to
secondary side of heating
system transformer.
Wire specifications
Use 18- to 22-gauge thermostat wire.
Shielded cable is not required.
B Heat pump changeover valve energized in heating.
4
5
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Fan operation settings
Battery installation
•
•
Gas or Oil: For gas or oil heating
systems, leave the fan operation
switch in this factory-set position
(This setting is for systems that
control the fan in a call for heat.)
Electric or Heat Pump: Change the
switch to this setting for heat
pump or electric heat systems.
(This setting is for systems that
allow the thermostat to control the
fan in a call for heat, if a fan wire is
connected to the G
terminal.)
Install two AA alkaline batteries in the
back of the thermostat, as shown at
left.
Fresh batteries should be installed
immediately when the REPLACE BATT warning begins flashing (see page 10.) The
warning flashes about two months
before batteries are depleted.
Even if the warning does not appear,
Batteries should be replaced once a year,
or before the home is left vacant for
more than a month.
Install batteries in back of thermostat
Thermostat mounting
Set fan operation switch
6
Align the 4 tabs on the wallplate with
corresponding slots on the back of the
thermostat, then push gently until the
thermostat snaps
in place.
7
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Fan operation settings
Battery installation
•
•
Gas or Oil: For gas or oil heating
systems, leave the fan operation
switch in this factory-set position
(This setting is for systems that
control the fan in a call for heat.)
Electric or Heat Pump: Change the
switch to this setting for heat
pump or electric heat systems.
(This setting is for systems that
allow the thermostat to control the
fan in a call for heat, if a fan wire is
connected to the G
terminal.)
Install two AA alkaline batteries in the
back of the thermostat, as shown at
left.
Fresh batteries should be installed
immediately when the REPLACE BATT warning begins flashing (see page 10.) The
warning flashes about two months
before batteries are depleted.
Even if the warning does not appear,
Batteries should be replaced once a year,
or before the home is left vacant for
more than a month.
Install batteries in back of thermostat
Thermostat mounting
Set fan operation switch
6
Align the 4 tabs on the wallplate with
corresponding slots on the back of the
thermostat, then push gently until the
thermostat snaps
in place.
7
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Installer setup
Installer system test
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
Follow the procedure below to test the heating and cooling system.
System test
number
Press and hold both buttons
Function
number
System status
Setting
10
Setup
1
0
0
Test
System switch
and
To begin, press and hold the
buttons until the display changes
Press
to change settings
1 Set SYSTEM switch to Cool.
Press
to advance to next function
2 Press
to turn on cooling system, then check system status (see table, below).
3 Press
to turn off cooling system.
Press and hold
to exit and save settings
4 Set SYSTEM switch to Heat.
Setup Function
Settings & Options
1 System type
0 Gas, oil or electric heat with air conditioning
1 Heat pump (5 minute compressor off time in heating and cooling)
5 Heating cycle rate
(CPH: cycles/hour)
5
1
3
9
9 Compressor
cycle rate (CPH)
For gas or oil furnaces of less than 90% efficiency
For steam or gravity systems
For hot water systems & furnaces of over 90% efficiency
For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
14 Temperature
display
0 Fahrenheit
1 Celsius
15 Compressor
protection
5 Five-minute compressor off time **See page 10
[Other options: 0, 1, 2, 3 or 4-minute off time]
Installer system test
After completing the installer setup above, press the
system test (see next page).
8
button again to begin a
5 Press
to turn on heating system, then check system status (see table, below).
6 Press
to turn off heating system.
7 [Optional] Set SYSTEM switch to Off to display thermostat information (see table, below).
Press
to display 71-76.
8 Press and hold
to terminate system test at any time.
System Test
System Status
10 Heating system
0 Heat and fan turn off.
1 Heat turns on. Fan also turns on immediately if Fan Operation
Switch is set to Electric Heat/Heat Pump (see page 6).
30 Cooling system
0 Compressor and fan turn off.
1 Compressor and fan turn on.
70 Thermostat
information
(for reference only)
71
72
73
74
75
76
Software revision number (major revisions)
Software revision number (minor revisions)
Configuration identification code (major)
Configuration identification code (minor)
Production configuration date code (week)
Production configuration date code (year)
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
9
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Installer setup
Installer system test
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
Follow the procedure below to test the heating and cooling system.
System test
number
Press and hold both buttons
Function
number
System status
Setting
10
Setup
1
0
0
Test
System switch
and
To begin, press and hold the
buttons until the display changes
Press
to change settings
1 Set SYSTEM switch to Cool.
Press
to advance to next function
2 Press
to turn on cooling system, then check system status (see table, below).
3 Press
to turn off cooling system.
Press and hold
to exit and save settings
4 Set SYSTEM switch to Heat.
Setup Function
Settings & Options
1 System type
0 Gas, oil or electric heat with air conditioning
1 Heat pump (5 minute compressor off time in heating and cooling)
5 Heating cycle rate
(CPH: cycles/hour)
5
1
3
9
9 Compressor
cycle rate (CPH)
For gas or oil furnaces of less than 90% efficiency
For steam or gravity systems
For hot water systems & furnaces of over 90% efficiency
For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
14 Temperature
display
0 Fahrenheit
1 Celsius
15 Compressor
protection
5 Five-minute compressor off time **See page 10
[Other options: 0, 1, 2, 3 or 4-minute off time]
Installer system test
After completing the installer setup above, press the
system test (see next page).
8
button again to begin a
5 Press
to turn on heating system, then check system status (see table, below).
6 Press
to turn off heating system.
7 [Optional] Set SYSTEM switch to Off to display thermostat information (see table, below).
Press
to display 71-76.
8 Press and hold
to terminate system test at any time.
System Test
System Status
10 Heating system
0 Heat and fan turn off.
1 Heat turns on. Fan also turns on immediately if Fan Operation
Switch is set to Electric Heat/Heat Pump (see page 6).
30 Cooling system
0 Compressor and fan turn off.
1 Compressor and fan turn on.
70 Thermostat
information
(for reference only)
71
72
73
74
75
76
Software revision number (major revisions)
Software revision number (minor revisions)
Configuration identification code (major)
Configuration identification code (minor)
Production configuration date code (week)
Production configuration date code (year)
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
9
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Quick reference to controls
In case of difficulty
Digital display screen
Temperature buttons
Press to adjust temperature
settings
System switch
Fan switch
On: Fan runs continuously.
Auto: Fan runs only when heating
or cooling system is on.
•
Cool: Thermostat controls only
the cooling system.
•
Heat: Thermostat controls only
the heating system.
•
Off: Heating and cooling
systems are off.
If you have difficulty with your thermostat, please try the suggestions below. Most
problems can be corrected quickly and easily.
Display is blank
•
Temperature
settings do not
change
Make sure heating and cooling temperatures are set to acceptable ranges:
Set To
75
75
°
Replace Batt
°
Heat On
Cool On
System status
On when “calling” for
heating or cooling;
flashes when waiting for
compressor restart
Built-in compressor protection (Setup Function 15)
Inside
75
Set To
°
75
°
Cool On
Message flashes until safe
restart time has elapsed
Heat: 40° to 90°F (4.5° to 32°C).
•
Cool: 50° to 99°F (10° to 37°C).
Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
heating equipment to find the cause of the problem.
•
Check for loose or broken wires between the thermostat and the heating
equipment.
Cooling system •
does not respond
(“Cool On”
appears on
•
screen)
Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
cooling equipment to find the cause of the problem
•
Check for loose or broken wires between the thermostat and the cooling
equipment.
Fan does not
turn on in a
call for heat
•
Make sure the Fan Operation switch is set to the proper system (see page 6).
“Cool On” or
“Heat On”
is flashing
•
Compressor protection timeout is engaged. Wait 5 minutes for the
system to restart safely, without damage to the compressor.
“Heat On” is
not displayed
•
Set the System switch to Heat, and set the temperature level above the
current room temperature (see page 10).
“Cool On” is
not displayed
•
Set the System switch to Cool, and set the temperature level below the
current room temperature (see page 10).
Check for 24 Vac between the heat terminal (W) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
heating equipment to find the cause of the problem.
Temperature setting
Inside
Low battery warning
•
Heating system •
does not respond
(“Heat On”
appears on
•
screen)
Quick reference to display screen
Current inside temperature
Make sure fresh AA alkaline batteries are correctly installed (see page 7).
This feature helps prevent damage to the
compressor in the air conditioning or heat
pump system.
Damage can occur if the compressor is restarted too soon after shutdown.This feature
forces the compressor to wait for a few minutes before restarting.
During the wait time, the message Cool On
(or Heat On if you have a heat pump) will
flash on the display.When the safe wait time
has elapsed, the message stops flashing and
the compressor turns on.
10
Check for 24 Vac between the cooling terminal (Y) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
11
Installation Guide
PRO TH3110B Non-programmable Digital Thermostat
Quick reference to controls
In case of difficulty
Digital display screen
Temperature buttons
Press to adjust temperature
settings
System switch
Fan switch
On: Fan runs continuously.
Auto: Fan runs only when heating
or cooling system is on.
•
Cool: Thermostat controls only
the cooling system.
•
Heat: Thermostat controls only
the heating system.
•
Off: Heating and cooling
systems are off.
If you have difficulty with your thermostat, please try the suggestions below. Most
problems can be corrected quickly and easily.
Display is blank
•
Temperature
settings do not
change
Make sure heating and cooling temperatures are set to acceptable ranges:
Set To
75
75
°
Replace Batt
°
Heat On
Cool On
System status
On when “calling” for
heating or cooling;
flashes when waiting for
compressor restart
Built-in compressor protection (Setup Function 15)
Inside
75
Set To
°
75
°
Cool On
Message flashes until safe
restart time has elapsed
Heat: 40° to 90°F (4.5° to 32°C).
•
Cool: 50° to 99°F (10° to 37°C).
Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
heating equipment to find the cause of the problem.
•
Check for loose or broken wires between the thermostat and the heating
equipment.
Cooling system •
does not respond
(“Cool On”
appears on
•
screen)
Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the
cooling equipment to find the cause of the problem
•
Check for loose or broken wires between the thermostat and the cooling
equipment.
Fan does not
turn on in a
call for heat
•
Make sure the Fan Operation switch is set to the proper system (see page 6).
“Cool On” or
“Heat On”
is flashing
•
Compressor protection timeout is engaged. Wait 5 minutes for the
system to restart safely, without damage to the compressor.
“Heat On” is
not displayed
•
Set the System switch to Heat, and set the temperature level above the
current room temperature (see page 10).
“Cool On” is
not displayed
•
Set the System switch to Cool, and set the temperature level below the
current room temperature (see page 10).
Check for 24 Vac between the heat terminal (W) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
heating equipment to find the cause of the problem.
Temperature setting
Inside
Low battery warning
•
Heating system •
does not respond
(“Heat On”
appears on
•
screen)
Quick reference to display screen
Current inside temperature
Make sure fresh AA alkaline batteries are correctly installed (see page 7).
This feature helps prevent damage to the
compressor in the air conditioning or heat
pump system.
Damage can occur if the compressor is restarted too soon after shutdown.This feature
forces the compressor to wait for a few minutes before restarting.
During the wait time, the message Cool On
(or Heat On if you have a heat pump) will
flash on the display.When the safe wait time
has elapsed, the message stops flashing and
the compressor turns on.
10
Check for 24 Vac between the cooling terminal (Y) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
11
Installation Guide
Accessories
Please contact your distributor to order accessories.
Cover plate assembly ............................................Part Number 50002883-001
(Used to cover marks left by old thermostats.)
Specifications
Temperature Ranges
• Heat: 40° to 90°F (4.5° to 32°C)
• Cool: 50° to 99°F (10° to 37°C)
Electrical Ratings
Operating Ambient Temperature
• 32° to 120°F (0° to 48.9°C)
Heating
20-30 Vac
0.02-1.0 A
(Powerpile)
750 mV DC
100 mA DC
Cooling
20-30 Vac
0.02-1.0 A
Shipping Temperature
• -20° to 120°F (-28.9° to 48.9°C)
System
Operating Relative Humidity
• 5% to 90% (non-condensing)
Physical Dimensions
• 3-13/16” H x 5-3/8” W x 1-1/4” D
• 97 mm H x 137 mm W x 32 mm D
12
Voltage (50/60Hz)
Running Current
Installation Guide
Accessories
Please contact your distributor to order accessories.
Cover plate assembly ............................................Part Number 50002883-001
(Used to cover marks left by old thermostats.)
Specifications
Temperature Ranges
• Heat: 40° to 90°F (4.5° to 32°C)
• Cool: 50° to 99°F (10° to 37°C)
Electrical Ratings
Operating Ambient Temperature
• 32° to 120°F (0° to 48.9°C)
Heating
20-30 Vac
0.02-1.0 A
(Powerpile)
750 mV DC
100 mA DC
Cooling
20-30 Vac
0.02-1.0 A
Shipping Temperature
• -20° to 120°F (-28.9° to 48.9°C)
System
Operating Relative Humidity
• 5% to 90% (non-condensing)
Physical Dimensions
• 3-13/16” H x 5-3/8” W x 1-1/4” D
• 97 mm H x 137 mm W x 32 mm D
12
Voltage (50/60Hz)
Running Current
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
® U.S. Registered Trademark. Patents pending.
Copyright © 2005 Honeywell International Inc. All rights reserved.
Printed in U.S.A. Document number 69-1793. Date 01-2005.
www.honeywell.com/yourhome