Installation Guide

Installation
Guide
TH8320ZW
Touch-screen Thermostat
This manual covers the TH8320ZW.
System Types
• Gas, oil, or electric heat with air
conditioning
• Warm air, hot water, high
efficiency furnaces, heat
pumps, steam, gravity
• Heat only — including power to open
and close zone valves (Series 20), and
normally open zone valves
• Heat only with fan
• Cool only
• 750 mV heating systems
This thermostat contains a Lithium battery which may contain Perchlorate material.
Perchlorate Material—special handling may apply.
See www.dtsc.ca.gov/hazardouswaste/perchlorate
Need Help?
For assistance with this product please visit http://customer.honeywell.com
or call Honeywell Customer Care toll-free at 1-800-468-1502
® U.S. Registered Trademark.
US Patent No. 6,574,581, 6,975,958, 7,114,554,
7,346,467, 7,636,604, 7,693,582, 7,788,936,
7,845,576, and other patents pending.
Copyright © 2013 Honeywell International Inc.
All rights reserved.
69-2486-09
Installation Guide
Wallplate installation
1. Separate wallplate from thermostat.
2. Mount wallplate as shown below.
Grasp top and bottom of wallplate
and pull to remove from thermostat.
+
+
+
Drill 3/16” holes for drywall.
Drill 7/32” holes for plaster.
M29480
Wire hole
Mounting screws
Wall anchors
M29481
Must be installed by a trained, experienced technician
• Read these instructions carefully. Failure to follow these instructions
can damage the product or cause a hazardous condition.
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning
installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not
place the old control in the trash. Contact your local waste management authority for
instructions regarding recycling and proper disposal.
69-2486—09
2
TH8320ZW
Power Requirements
HEAT PUMP
CONVENTIONAL
K
Remove tab.
K
M32429
Connect the common side of the
transformer to “C” terminal. This
connection is mandatory.
M32428A
The thermostat is shipped from the factory
with the coin cell installed. To keep the battery from discharging during shipment and
storage, the thermostat is shipped with a
plastic tab inserted in the battery holder.
This tab must be removed during installation. Simply pull the plastic tab out of the
battery tray. Make sure that the battery tray
is fully inserted into the thermostat.
Wiring
Remove factory-installed jumper only
for two-transformer systems.
Push excess wire back into the wall opening. Plug
wall opening with non-flammable insulation.
HEAT PUMP
CONVENTIONAL
K
K
M32431
M32430B
3
69-2486—09
Installation Guide
Wiring
Terminal Designations
Conventional Terminal Letters:
R
Rc
C
W
W2
Y
Y2
G
K
Heat Pump Terminal Letters:
R
Heating power. Connect to secondary
side of heating system transformer.
Cooling power. Connect to secondary
side of cooling system transformer.
Common wire from secondary side of
cooling transformer (if 2 transformers).
1st stage heat relay.
2nd stage heat relay
1st stage compressor contactor.
2nd stage compressor contactor.
Fan relay.
Optional THP9045 Wiring Module
Terminal [9]
Rc
C
Y
Y2
Aux
G
E
L
O/B
K
Heating power. Connect to secondary
side of heating system transformer.
Cooling power. Connect to secondary
side of cooling system transformer.
Common wire from secondary side of
cooling system transformer.
1st stage compressor contactor.
2nd stage compressor contactor.
Auxiliary heat relay.
Fan relay.
Emergency heat relay.
Heat pump reset (powered continuously when System is set to Em Heat;
system monitor when set to Heat,
Cool or Off).
Changeover valve for heat pumps.
Optional THP9045 Wiring Module
Terminal [9]
Wiring guide—conventional systems
1H/1C System (1 transformer)
Rc
R
W
Y
G
C
K
Heat Only System (Series 20)
Rc
R
W
Y
C
Power [1]
[R+Rc joined by jumper]
Heat relay
Compressor contactor
Fan relay
24VAC common [3]
Optional THP9045 Wiring Module
Terminal [9]
2H/2C System (1 transformer)
Y2
W2
Rc
R
W
Y
G
C
K
Heat Only System
Rc
R
W
C
[R+Rc joined by jumper]
Series 20 valve terminal “R” [1]
Series 20 valve terminal “B”
Series 20 valve terminal “W”
24VAC common [3]
Power [1]
[R+Rc joined by jumper]
Heat relay
24VAC common [3]
Cool relay 2
Heat relay 2
Power [1]
[R+Rc joined by jumper]
Heat relay 1
Cool relay 1
Fan relay
24VAC common [3]
Optional THP9045 Wiring Module
Terminal [9]
See [notes] below
[1] Power supply. Provide disconnect means and overload protection as required.
[3] Connection to 24VAC common at the transformer is required.
[9] See "Optional THP9045 Wiring Module" on page 14 for more details.
69-2486—09
4
TH8320ZW
Wiring
Wiring guide—heat pump systems
1H/1C Heat Pump (no auxiliary heat)
Rc
R
O/B
Y
G
C
K
1H/1C System (2 transformers)
Rc
R
W
Y
G
C
K
Power [1]
[R+Rc joined by jumper]
Changeover valve [5]
Compressor relay
Fan relay
24VAC common [3]
Optional THP9045 Wiring Module
Terminal [9]
2H/1C Heat Pump (with auxiliary heat)
L
E
Aux
Rc
R
O/B
Y
G
C
K
Heat Only System With Fan
Rc
R
W
G
C
Equipment monitor [6, 7]
Emergency heat relay [8]
Auxiliary heat relay (Heat 2) [8]
Power [1]
[R+Rc joined by jumper]
Changeover valve [5]
Compressor relay
Fan relay
24VAC common [3]
Optional THP9045 Wiring Module
Terminal [9]
Power [1]
[R+Rc joined by jumper]
Heat relay
Fan relay
24VAC common [3]
Cool Only System
Rc
R
Y
G
C
K
2H/2C Heat Pump (no auxiliary heat)
Y2
Rc
R
O/B
Y
G
C
K
Power (cooling transformer) [1, 2]
Power (heating transformer) [1, 2]
Heat relay
Compressor contactor
Fan relay
24VAC common [3, 4]
Optional THP9045 Wiring Module
Terminal [9]
Compressor 2 relay
Power [1]
[R+Rc joined by jumper]
Changeover valve [5]
Compressor 1 relay
Fan relay
24VAC common [3]
Optional THP9045 Wiring Module
Terminal [9]
Power [1]
[R+Rc joined by jumper]
Compressor contactor
Fan relay
24VAC common [3]
Optional THP9045 Wiring Module
Terminal [9]
2H/2C System (2 transformers)
Y2
W2
Rc
R
W
Y
G
C
K
Cool relay 2
Heat relay 2
Power (cooling transformer) [1, 2]
Power (heating transformer) [1, 2]
Heat relay 1
Cool relay 1
Fan relay
24VAC common [3, 4]
Optional THP9045 Wiring Module
Terminal [9]
See [notes] below
[1] Power supply. Provide disconnect means and overload protection as required.
[2] Remove jumper for 2 transformer systems.
[3] Connection to 24VAC common at the transformer is required.
[4] Common connection must come from cooling transformer.
[5]O/B set to control as either O or B in installer setup.
[6]If L terminal is used, 24VAC common (terminal C) must be connected.
[7] Heat pump reset (powered continuously when thermostat is set to Em. Heat; system monitor
when set to Heat, Cool, or Off).
[8] Install field jumper between Aux and E terminals if there is no emergency heat relay.
[9] See "Optional THP9045 Wiring Module" on page 14 for more details.
5
69-2486—09
Installation Guide
Mount thermostat
Align pins on back of thermostat
with slots in wallplate, then push
gently until thermostat snaps into
place.
M32435
Set date and time
Press st
to set date
Press st
to set time
TUE
TUE
15
Press st
to set month
Press st
to set year
6
2006
1:00 PM
DONE
DONE
M29485
Press DONE to save changes.
Press DONE to save and exit.
Installer setup
Press SYSTEM.
1.
2.
Press and hold
these two buttons
until the display
changes.
SYSTEM
HEAT
6:00aM
TUE
FAN
AUTO
Inside
70
3.
SYSTEM
HEAT
DONE
6:00aM
SCHED
Change settings
as required (see
pages 7-9).
CANCEL
0120
20
DONE
HOLD
M32417
69-2486—09
6
TH8320ZW
Installer setup
Function
Setting
20
0120
20
0120
DONE
DONE
M32427
Press st to
select function
Press DONE to exit & save settings.
Press st to
change setting
Setup functions
Settings & Options (factory default in bold)
0120
Year
(first two digits)
20(2000-2078)
21(2101-2178)
0130
Year
(second two digits)
10(2010)
[Other options: 00-99]
0140
Month
6
[Other options: 1-12]
0150
Date
15
[Other options: 1-31]
0160
Schedule format
0Nonprogrammable
4Programmable
0165
Restore Energy
Saving Schedule
0No
1Yes
0170
System type
1
2
3
4
5
6
7
8
9
10
11
12
1 heat/1 cool conventional
1 heat/1 cool heat pump (no aux. heat)
Heat only (2-wire systems)
Heat only with fan
Hot water Series 20 system (power to open & close zone
valves/normally open zone valves)
Cool only
2 heat/1 cool heat pump (with aux. heat)
2 heat/2 cool multistage conventional
2 heat/1 cool multistage conventional
1 heat/2 cool multistage conventional
2 heat/2 cool heat pump (no aux. heat)
3 heat/2 cool heat pump (with aux. heat)
0180
Fan control
(heating)
0
1
Gas/Oil heat (equipment controls heating fan)
Electric furnace (thermostat controls heating fan)
0190
Changeover valve
(O/B terminal)
0
1
O terminal controls valve in cooling
B terminal controls valve in heating
0220
1st stage compressor
cycle rate
3
Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
0230
2nd stage compressor
cycle rate
3
Recommended for most compressors
[Other options: 1, 2, 4, 5 or 6 CPH]
0240
1st stage heat cycle
rate (CPH = cycles
per hour)
5
1
3
9
Gas or oil furnaces of less than 90% efficiency
Steam or gravity systems
Hot water systems & furnaces of 90%+ efficiency
Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
Continued on next page
7
69-2486—09
Installation Guide
Installer setup
Setup functions
Settings & Options (factory default in bold)
0250
2nd stage heat
cycle rate (CPH)
9
1
3
5
Electric furnaces
Steam or gravity systems
Hot water systems & furnaces of 90%+ efficiency
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0260
3rd stage heat cycle
rate (CPH)
9
1
3
5
Electric furnaces
Steam or gravity systems
Hot water systems & furnaces of 90%+ efficiency
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0270
Emergency heat
cycle rate (CPH)
9
1
3
5
Electric emergency heat
Steam or gravity systems
Hot water systems & furnaces of 90%+ efficiency
Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
0280
Continuous
Backlight
0
1
Backlight on for approx. 45 seconds after keypress
Backlight always on low intensity, full bright after keypress
(requires 24VAC connection)
0300
Manual/Auto
changeover
0
1
Manual changeover (Heat/Cool/Off)
Automatic changeover (Heat/Cool/Auto/Off)
0310
Auto changeover
deadband
3
Heat/cool temperature 3°F apart (1.5°C)
[Other options: 2-9 (2°F to 9°F/1°C to 5°C)])
0320
Temperature
display
0Fahrenheit
1
Celsius
0330
Daylight savings
1
0500
Furnace filter
change reminder
0Off
1
10-day run time (about 1 month)
2
30-day run time (about 3 months)
3
60-day run time (about 6 months)
4
90-day run time (about 9 months)
5
120-day run time (about 1 year)
6
180-day run time (about 1.5 years)
7
270-day run time (about 2 years)
8
365-day run time (about 3 years)
9
30 calendar days
10 60 calendar days
11 90 calendar days
12 120 calendar days
13 180 calendar days
14 365 calendar days
0502
Furnace filter
for Run time
0
1
0520
UV Lamp
Replacement
Reminder
0Disabled
1
365 days
2
730 days
0530
Adaptive Intelligent
Recovery™
1
On
0Off
0
Auto-change to daylight savings time (through 2007, and for
areas that do not use the new 2008 DST calendar)
Daylight savings time is turned off
Counts both heat and cool
Counts cool only
Continued on next page
69-2486—09
8
TH8320ZW
Installer setup
Setup functions
Settings & Options (factory default in bold)
0540
Program periods
4
2
4 program periods (Wake, Leave, Return, Sleep)
2 program periods (Wake, Sleep)
0580
Compressor
protection
5
0600
Heat temperature
range stop
90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40-89°F (4°C to 32°C)]
0610
Cool temperature
range stop
50 Min. cool temperature setting is 50°F (10°C)
[Other options: 51-99°F (11°C to 37°C)]
0615
Energy Saving
Heat Setpoint
65 65°F (18.5°C)
40-90°F (4.5°C to 32°C)
0616
Energy Saving
Cooling Setpoint
78 78°F (25.5°C)
50-99°F (10°C to 37°C)
0640
Clock format
12 12-hour time (i.e., “3:30 pm”)
24 24-hour time (i.e., “15:30”)
0650
Extended fan
timer (heat)
0Off
90 Fan runs for 90 seconds after call for heat ends
[Other options: 30, 60, 120]
0660
Extended fan
timer (cool)
0Off
90 Fan runs for 90 seconds after call for cooling ends
[Other options: 30, 60, 120]
0670
Keypad lock
0
1
2
Keypad unlocked (fully functional)
Partially locked (access to temperature settings only)
Fully locked
0680
Heat temperature
control
2
1
3
Standard temperature control (recommended)
Choose if room is warmer than set temperature
Choose if room does not reach set temperature
0690
Cool temperature
control
2
1
3
Standard temperature control (recommended)
Choose if room is cooler than set temperature
Choose if room does not reach set temperature
0700
Temperature
display offset
0
Thermostat displays actual room temperature
[Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)]
0710
Reset
0
1
No reset
Reset installer options, the Z-Wave Radio module, & programming schedule to factory default (only date and time settings
are retained)
rf10
Z-Wave Network
Connection
0Remove
1Add
rf20
Z-Wave Node
Connection
0Idle
1
Send Node
5 minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
9
69-2486—09
Installation Guide
Installer system test
Test
number
During installer setup, press t
repeatedly until “Test” appears.
System
status
1
20
0120
DONE
0
TEST
DONE
Press DONE to terminate testing.
System test
Press t to
select test
M29488
Press t to
change status
System status
1
Cooling system
0
1
2
Compressor and fan turn off
Compressor and fan turn on
Second stage compressor turns on
2
Fan system
0
1
Fan turns off
Fan turns on
3
Heating system
0
1
2
Heat and fan turn off
Heat turns on (fan on if Function 0170 is set for heat pump,
or if Function 0180 is set to “1”)
Second stage heat turns on
0
1
2
Em Heat and fan turn off
Em Heat and fan turn on
Second stage heat turns on (Auxiliary heat)
4
Emergency
heating system
CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
Z-Wave enrollment
The TH8320ZW is powered by Z-Wave
technology so it is compatible with
Z-Wave enabled devices from other
manufacturers.
1.
To join a Z-Wave
network, set the
Z-Wave controller
to INCLUDE mode.
2.
Select 1 to add
thermostat to
Z-Wave network.
F 10
0
DONE
M32423A
69-2486—09
10
TH8320ZW
Z-Wave enrollment
Wait
F 10
M32422
3.
To remove the
thermostat from the
Z-Wave network
select 0.
14
F 10
1
DONE
M32424A
F 10
M32425
11
69-2486—09
Installation Guide
Z-Wave enrollment
4.
To share the
thermostat Node
information with
additional Z-Wave
devices select 1.
F20
0
DONE
M32421
Z-Wave messages
Add/ Remove
The thermostat can be included or excluded from the Z-Wave network. This action requires the
controller set in inclusion mode. The device is included to the Z-Wave network after sending the
node information to the controller. The controller is responsible for assigning the home ID and
device ID to the included device. The thermostat can also act as a repeater to forward messages
to other devices in the Z-Wave network. Repeating messages allows communication of devices
that are not in the direct reach of Z-wave protocol.
Association
The thermostat can be associated with other devices in the system. Being associated means that
the thermostat is able to send messages directly to any other device. During the association process the return route is acquired from the primary controller. The thermostat then uses this return
route to access the distant node. The association is a connection between primary and secondary devices. It is used to determine the relationship of devices in the network. Both primary and
secondary controllers can set up associations.
The thermostat supports one association grouping and five nodes can be associated with this
grouping. Following messages are sent to associated nodes for grouping #1:
· Basic
· Multilevel Sensor
· Thermostat Mode
· Thermostat Setpoint
· Thermostat Fan Mode
· Thermostat Operating State
· Thermostat Fan State
Enter/leave Power Saving Mode
When requested from the Z-Wave controller, the thermostat adjusts its setpoint in order to
decrease the power consumption of the HVAC equipment.
In addition, using an Internet gateway enables the person to control the thermostat remotely
through the Internet.
Thermostat Fan Mode Change
The thermostat can send the message containing the actual fan mode position.
Thermostat Fan Mode
The other devices are able to change the fan mode of the thermostat. After the message is
69-2486—09
12
TH8320ZW
Z-Wave messages
received, the fan mode is changed to the desired value (if this value is possible).
For the thermostat the possible values are On, Auto and Circ.
Indoor Temperature
The thermostat sends the indoor temperature using the Multilevel Sensor command class.
Report upon GET request
Upon request (GET command) the thermostat sends the corresponding report.
Setpoint Value
The thermostat can send the message containing the actual setpoint value based on setpoint
change.
Setpoint Change
Other Z-Wave devices are able to modify the setpoint of the thermostat. The absolute value can
be sent by the controller and thermostat will change the setpoint to this value.
Thermostat Mode Change
The thermostat can send the message containing the actual thermostat mode based on thermostat mode change.
Thermostat Mode
Other devices (controllers) are able to change the thermostat mode change of the thermostat.
After the message is received by the thermostat, the thermostat mode change is changed to
desired value (if this value is possible).
Seven possible modes are available for the thermostat: Heat / Cool / Off / Auto / Energy Saving
Heat / Energy Saving Cool / Em Heat. The number of allowed selections depends on the actual
configuration of the thermostat. The thermostat uses "Thermostat Mode Supported" report
command class to tell other devices the actually supported thermostat modes.
Thermostat Operating State
The thermostat can send the message containing the actual state of the HVAC equipment based
on equipment state change.
The thermostat provides the following operating states:
•
•
•
•
•
Idle - no equipment on
Heating - heating equipment on
Cooling - cooling equipment on
Pending Heat - minimum off time applied to protect the heat pump compressor
Pending Cool - minimum off time applied to protect the heat pump compressor
Unsolicited Report Message
Sending the message is possible only if the thermostat is associated with any other node. The
thermostat will send the message using assigned node ID and return route.
13
69-2486—09
Installation Guide
Special functions
Auto Changeover (Setup Function 0300): When set to Auto, the thermostat automatically selects heating or cooling depending on the indoor temperature. Heat and cool settings must be at least 2 degrees
apart.
Adaptive Intelligent Recovery (Setup Function 0530): Allows the thermostat to “learn” how long the
furnace and air conditioner take to reach programmed temperature settings, so the temperature is
reached at the scheduled time.
Compressor Protection (Setup Function 0580): Forces the compressor to wait a few minutes before
restarting, to prevent damage. During this time, the message “Wait” is on the display.
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Cover plate*.............................................................. Part Number 32003796-001
*(Use to cover marks left by old thermostats.)
Specifications
Temperature Ranges
• Heat: 40° to 90°F (4.5° to 32°C)
• Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature
• 0° to 120°F (-18° to 48.9°C)
Shipping Temperature
• -30° to 150°F (-34° to 66°C)
Operating Relative Humidity
• 5% to 90% (non-condensing)
Physical Dimensions
• 4-23/25” H x 6-2/5” W x 1-19/46” D
• 125 mm H x 166 mm W x 36 mm D
Electrical Ratings
Terminal
Voltage (50/60Hz)
Running Current
W Heating
20-30 Vac
(Powerpile)
750 mV DC
100 mA DC
W2 Heating
20-30 Vac
0.02-0.6 A
Y Cooling
20-30 Vac
0.02-1.0 A
Y2 Cooling
20-30 Vac
0.02-0.6 A
Aux Auxiliary heat
20-30 Vac
0.02-1.0 A
O/B Changeover
20-30 Vac
0.02-0.6 A
E Emergency heat
20-30 Vac
0.02-1.0 A
L Heat pump reset
20-30 Vac
0.02-0.6 A
0.02-1.0 A
Optional THP9045 Wiring Module
The THP9045 Wiring Module is designed to be used with applicable thermostats in 1 Heat/1
Cool retrofit applications where only 4 wires are available. The K terminal on the thermostat can
be used to operate both the fan and compressor on a single wire, and the module is designed to
receive the signal from the K terminal, split that signal and reroute it to operate the compressor,
and/or fan for normal operation. See the THP9045 manual for further details.
69-2486—09
14
TH8320ZW
Regulatory information
FCC Compliance Statement (Part 15.19) (USA only)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions:
1) This device may not cause harmful interference, and
2) This device must accept any interference received, including interference that may cause
undesired operation.
FCC Warning (Part 15.21) (USA only)
Changes or modifications not expressly approved by the party responsible for compliance could
void the user’s authority to operate the equipment.
FCC Interference Statement (Part 15.105 (b)) (USA only)
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by one of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
• Consult the dealer or an experienced radio/TV technician for help.
Section 7.1.2 of RSS-GEN
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of
a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce
potential radio interference to other users, the antenna type and its gain should be so chosen that
the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful
communication.
Section 7.1.3 of RSS-GEN
This Device complies with Industry Canada License-exempt RSS standard(s). Operation is subject
to the following two conditions: 1) this device may not cause interference, and 2) this device must
accept any interference, including interference that may cause undesired operation of the device.
15
69-2486—09
Z-Wave is a registered trademark of Zensys, Inc. and/or its subsidiaries.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North