Datasheet

ATA-2001 – Analog LVDT/RVDT Signal Conditioner with digital calibration
•
•
•
•
•
•
•
•
•
115 or 220 VAC line powered
Microprocessor controlled calibration
Superior digital filtering
Selectable excitation frequencies & amplitudes
Voltage and current outputs
250 to 1000Hz selectable frequency response
Auto fall-back synchronization
Splash-proof front panel with status LEDs
1/8 DIN standard panel mounting
DESCRIPTION
The ATA-2001 is a general purpose, AC line-powered, LVDT/RVDT analog signal conditioner with digital setup
and calibration. The embedded microprocessor generates a PWM-shaped sine wave and handles all calibration
functions. It also controls the demodulation, filtration and synchronization of the LVDT or RVDT transducer
signal. All settings are stored in non-volatile memory for restoration on power up. Zero, Gain and Phase
adjustments are accomplished via the use of splash-proof front panel pushbuttons and digital voltage dividers.
Intended for the most demanding industrial applications, the ATA-2001 is CE certified, and has been rigorously
tested to the highest industrial standards for EMI, RFI and ESD.
Designed for universal compatibility with 4, 5 and 6 electrical connection transducers, the ATA-2001 provides a
wide range of oscillator frequencies, gains and two excitation voltages, affording maximum interface versatility.
The very high drive current of 45mA allows operation with transducer input impedances as low as 12 Ohms
(with 0.5 VRMS excitation). With high gain capability and low noise, the ATA-2001 provides measurement
resolutions beyond most products currently available.
The unique auto fall-back synchronization feature allows reliable master/slave operation, for prevention of
amplifier cross talk, without the worry of sync signal loss. If the internal processor in a slave amplifier detects an
unstable or missing sync signal, the internal clock will take over, continuing at the pre-selected nominal
frequency. Upon restoration of a normal sync pulse, the oscillator will return to the slave mode.
The ATA-2001 is contained within a rugged, one-piece, extruded aluminum housing which provides optimal
amplifier performance under the most rigorous EMI and RFI conditions. An integral panel mounting system
provides for convenient 1/8 DIN standard, panel installation. A pre-punched 19” rack adapter is also available to
accommodate up to eight amplifiers per adapter installation.
Also see our other signal conditioner models, LDM-1000 (DIN rail mount, VDC and 4-20mA output), LVM-110
(VDC input/output), LiM-420 (4-20mA transmitter), PML-1000 (1/8th DIN panel meter, VDC, current and RS485
outputs), and our IEM-422 (NEMA-13 rated 4-20mA transmitter).
Measurement Specialties, Inc. (NASDAQ MEAS) offers many other types of sensors and signal conditioners.
Data sheets can be downloaded from our web site at: http://www.meas-spec.com/datasheets.aspx
MEAS acquired Schaevitz Sensors and the Schaevitz
TM
FEATURES
•
•
•
•
trademark in 2000.
APPLICATIONS
Microprocessor controlled & non-volatile memory
Phase shift compensation
Auto fall-back synchronization
Rugged extruded aluminum housing
ATA-2001 Rev. 5
www.meas-spec.com
1/5
•
•
•
•
Power-gen turbine control
Head box slice lip position control
Roller gap position feedback
Precision metrology labs
2015-July
ATA-2001 – Analog LVDT/RVDT Signal Conditioner with digital calibration
PERFORMANCE SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
Line power requirements
Line voltage regulation
115VAC ±10%, 50-400Hz; 220VAC ±10%, 50-400Hz (switch selectable)
±10%, with no change in output
Voltage output
Unipolar voltage output range
Bipolar voltage output range
Noise and ripple (voltage output)
Output impedance (voltage output)
0 to 10VDC, with 10mA maximum current capability
±10VDC (using 100% zero suppression), with 10mA maximum current capability
3mV RMS maximum @ 2.5KHz excitation frequency
1Ω maximum
Current output
Current output range
Internal loop supply voltage
Maximum loop resistance
Noise and ripple (current output)
4 to 20mA
18VDC
700Ω with internal loop supply; 1000Ω with 24VDC external supply (32vdc MAX)
10µA rms (max)
Analog outputs frequency response
Frequency response @ -3db
250Hz @ 2.5kHz excitation
500Hz @ 5.0kHz excitation
1000Hz @ 10kHz excitation
Transducer FSO for 10 VDC output
Input impedance
Zero suppression range
Phase shift compensation range
Non-linearity and hysteresis
Stability
Temperature coefficient of output
High gain: 0.04 to 0.9 VRMS; Low gain: 0.5 to 10 VRMS (switch selectable)
100kΩ
±110% of FSO
±120 degrees maximum
±0.05% of FSO, maximum
±0.05% of FSO, maximum, after 20 minute warm up
±0.02% of FSO per °F [±0.036% per °C] over the operating temperature range
Amplifier characteristics
Transducer excitation
Voltage
Current
Frequency
0.5 or 3.5 VRMS, sine wave (switch selectable)
45mA RMS maximum
2.5, 5 or 10kHz (switch selectable)
Transducer requirements
Transducer type
Input impedance (Primary)
Full scale output
LVDT or RVDT with 4, 5 or 6 electrical connections
12Ω minimum with 0.5 VRMS excitation; 80Ω minimum with 3.5 VRMS excitation
High gain: 0.04 to 0.9 VRMS; Low gain: 0.5 to 10 VRMS
ENVIRONMENTAL AND MECHANICAL SPECIFICATIONS
Operating temperature range
Storage temperature range
Weight
Transducer electrical connections
Output and sync connections
Mounting
IEC 60529 rating
-40°F to +185°F [-40°C to 85°C]
-40°F to +257°F [-40°C to 125°C]
2.1lbs [950 grams]
DB-9S (See our transducer data sheets for jumper cables or connector option)
Barrier terminal strip
1/8 DIN standard panel mounting (19” rack adapter for 8-up available)
IP61 (Front panel only)
Notes:
All values are nominal unless otherwise noted
FSO (Full Scale Output) is the largest absolute value of the outputs measured at the range ends
ATA-2001 Rev. 5
www.meas-spec.com
2/5
2015-July
ATA-2001 – Analog LVDT/RVDT Signal Conditioner with digital calibration
WIRING – INPUT (TRANSDUCER)
WIRING – OUTPUT
ATA-2001 Rev. 5
www.meas-spec.com
3/5
2015-July
ATA-2001 – Analog LVDT/RVDT Signal Conditioner with digital calibration
DIMENSIONS
DIMENSIONS - RACK ADAPTOR (SOLD SEPARATELY)
Accommodates up to eight ATA-2001 Amplifiers
Dimensions are in inch (mm)
ATA-2001 Rev. 5
www.meas-spec.com
4/5
2015-July
ATA-2001 – Analog LVDT/RVDT Signal Conditioner with digital calibration
ORDERING INFORMATION
Description
ATA-2001 LVDT/RVDT Signal Conditioner
Rack Adaptor for up to 8 signal conditioners (ATA-2001 conditioners not included)
Cable to connect HCA/HCI Series LVDTs, GCA Series Gage Heads, and R36AS RVDT to ATA-2001 (1)
(PTO6A-10-6S to DB-9P connector)
Extension cable to connect LBB Series (option -004) Gage Heads to ATA-2001 (1)
Part Number
02291327-000
05290032-000
04290457-000
04290565-000
(DB-9S to DB-9P connector)
Extension Cable to connect LBB (option -001) to ATA-2001 (1)
04290577-000
(PTO6A-10-6S to DB-9P connector)
(1) All cables are shielded, 10 foot long, and are rated 80°C [176°F] operating. Consult factory for other lengths.
Download the operation manual: http://www.meas-spec.com/manuals.aspx
TECHNICAL CONTACT INFORMATION
NORTH AMERICA
EUROPE
ASIA
Measurement Specialties, Inc.
1000 Lucas Way
Hampton, VA 23666
United States
Phone: +1-800-745-8008
Fax: +1-757-766-4297
Email: [email protected]
Web: www.meas-spec.com
MEAS Deutschland GmbH
Hauert 13
D-44227 Dortmund
Germany
Phone: +49-(0)231-9740-0
Fax: +49-(0)231-9740-20
Email: [email protected]
Web: www.meas-spec.com
Measurement Specialties China Ltd.
No. 26, Langshan Road
High-tech Park (North)
Nanshan District, Shenzhen 518057
China
Phone: +86-755-33305088
Fax: +86-755-33305099
Email: [email protected]
Web: www.meas-spec.com
The information in this sheet has been carefully reviewed and is believed to be accurate; however, no responsibility is assumed for
inaccuracies. Furthermore, this information does not convey to the purchaser of such devices any license under the patent rights to the
manufacturer. Measurement Specialties, Inc. reserves the right to make changes without further notice to any product herein. Measurement
Specialties, Inc. makes no warranty, representation or guarantee regarding the suitability of its product for any particular purpose, nor does
Measurement Specialties, Inc. assume any liability arising out of the application or use of any product or circuit and specifically disclaims
any and all liability, including without limitation consequential or incidental damages. Typical parameters can and do vary in different
applications. All operating parameters must be validated for each customer application by customer’s technical experts. Measurement
Specialties, Inc. does not convey any license under its patent rights nor the rights of others.
ATA-2001 Rev. 5
www.meas-spec.com
5/5
2015-July