View the LDM-1000 Operation Manual here.

Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
Operation Manual
LDM-1000
LVDT/RVDT Signal Conditioning Module
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
1 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
Table of Contents
1
Introduction
3
2
Product Specifications
3
3
Product Description
4
4
Initial Setup Procedure
4.1
Supply Voltage
4.2
Internal Switches
4.3
Oscillator Frequency:
4.4
Oscillator Mode
4.5
Oscillator Drive Capability
4
5
6
6
7
7
5
Setting the Amplifier Gain
8
6
Dimensions and Wiring Terminals
9
7
Connection Diagrams
10
8
Calibration Procedure
11
9
Additional Information
12
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
2 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
1 Introduction
The LDM-1000 is an extremely versatile LVDT/RVDT (Linear or Rotary Variable Differential Transformer)
signal conditioning module. The module supplies an AC sine wave excitation to the LVDT or RVDT, and
demodulates, filters, and amplifies the output. It is the perfect choice for industrial applications requiring the
DIN standard rail mount.
2 Product Specifications
For complete specifications and ordering information, please refer to the datasheet at:
http://www.meas-spec.com/product/t_product.aspx?id=2588
ELECTRICAL SPECIFICATIONS
Supply voltage
Supply current
Output types and ranges
Temp. coefficient of output
Voltage output noise/ripple
Current output noise/ripple
Current loop resistance
Frequency response
Non-linearity
Input sensitivity range
18 to 30VDC or 10 to 18VDC (jumper selectable, 18 to 30VDC as shipped)
65mA maximum
±5VDC, 0 to 5VDC, 0 to 10VDC, and 4~20mA (DIP switch selectable, ±5VDC as shipped)
±0.02% of FSO per °F [±0.036% of FSO per °C] over the operating temperature range
5mV RMS maximum
25µA RMS maximum
700Ω maximum (with 18 to 30VDC supply voltage)
250 or 1000Hz @ -3 dB (3-pole Butterworth, DIP switch selectable, 250Hz as shipped)
±0.02% of FSO
0.05 to 2.50 VRMS
Transducer excitation
Voltage
Current
Frequency
1 or 3 VRMS (DIP switch selectable; 3VRMS as shipped, with 18 to 30VDC supply voltage only)
25mA RMS
2.5, 5 or 10kHz (DIP switch selectable, 2.5kHz as shipped)
Transducer type
LVDT/RVDT input impedance
LVDT/RVDT full scale output
LVDT or RVDT with 4, 5 or 6 electrical connections
50Ω minimum @ 1 VRMS excitation ; 150Ω minimum @ 3 VRMS
0.05 to 2.50 VRMS
Transducer requirements
ENVIRONMENTAL AND MECHANICAL SPECIFICATIONS
Operating temperature range
Storage temperature range
Mounting
Size
Wire terminal size
IEC 60529 rating
-13°F to +185°F [-25°C to 85°C]
-67°F to +257°F [-55°C to 125°C]
Standard DIN-3 rail mount
3.90 [99.0] high x 0.89 [22.5] wide x 4.51 [114.5] Deep
24 to 12 AWG [0.2 to 2.5mm]
IP60
Notes: All values are nominal unless otherwise noted; dimensions are in inch [mm]
FSO (Full Scale Output) is the largest absolute value of the outputs measured at the range ends.
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
3 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
3 Product Description
DIP switches are provided to allow selection of three transducer excitation frequencies (2.5, 5 and 10 kHz),
two signal bandwidths (250 or 1,000 Hertz), and two excitation voltages (1 or 3 Volts RMS). Switches are
also provided to select seven coarse gain ranges, three DC output voltage ranges, two offsets, and
master/slave operation. The 4 to 20mA output will operate regardless of the DC output voltage dip switch
settings.
Three multi-turn potentiometers located on the front panel allow precise gain (SPAN), offset (ZERO) and
phase shift (PHASE) adjustments.
An internal jumper allows changing the input voltage range from 18~30 VDC to 10~18 VDC.
The LDM-1000 is designed to be mounted to a standard number 3 DIN rail. Input/output connections are
made through plug-in screw terminal barrier strips. These plug-in strips are keyed to prevent improper
connections in the unlikely event that the LDM-1000 should require field replacement.
The next few pages will take you, step by step, through the simple set-up and calibration process. This
device may be set-up for several different full scale analog outputs; some of the potential configurations are
listed below:

±5 VDC output

0 to 5 VDC output

0 to 10 VDC output

4 to 20mA DC output

Standalone and Master/Slave operation
4 Initial Setup Procedure
To properly configure the LDM-1000 for the LVDT or RVDT you are using, you must access the internal dip
switches. To open the housing, depress the two latches with a screwdriver (see photos below); the housing
will spring open. You can slide the front panel and PC board assembly forward approximately 1.6 inch (4cm)
to access the dip switches and input voltage jumper. A spring stop prevents the PCB from being removed
completely.
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
4 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
In order to begin the setup process, you must first know a few basic characteristics about the LVDT or RVDT
you intend to use with the LDM-1000. The information may be obtained from the transducer calibration sheet,
catalog literature, or the MEAS (Measurement Specialties, Inc.) web site at:
http://www.meas-spec.com/position-sensors.aspx
The list below is the minimum information required to perform a successful calibration:





Recommended LVDT or RVDT excitation frequency (to set the oscillator frequency)
LVDT or RVDT Output sensitivity at the excitation frequency (to set the gain)
Primary (input) impedance at the excitation frequency (to set the oscillator output voltage)
The ± full scale linear or angular range over which you intend to perform the calibration
Analog output signal required by your application
4.1 Supply Voltage
The LDM-1000 supply voltage range is 18~30 VDC with the JP1 jumper in the storage position (as
shipped position). Only this range (18~30VDC) can be used for 4-20mA output operation. The operating
voltage may be changed to 10~18 VDC by installing internal jumper JP1 across both pins. See the
diagrams below for jumper settings.
CAUTION: Operating the unit at voltages above +18 volts with the jumper in the low voltage position will
overheat the internal voltage regulators and reduce the operational life of the LDM-1000.
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
5 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
4.2 Internal Switches
There are two internal DIP switch sets (SW1 and SW2) on the PC board assembly of the LDM-1000. The
tables below explain the switch positions and functions.
Switch Set SW1
Function:
Switch No:
Switch ON:
Switch OFF:
Offset
1
2
Positive
Negative
None
None
Signal Bandwidth
3
4
5
1 kHz
1 kHz
1 kHz
250 HZ 250 HZ 250 HZ
Note: Switches 3, 4 & 5
must be in same position
Gain 2
6
LOW
HIGH
Gain 1
8
Switch
Gain
position
OFF
OFF
x0.4
OFF
ON
x1.2
ON
OFF x3.63
ON
ON
x4.43
7
Switch Set SW2
Function:
Oscillator Frequency
Sync
Osc. V
1
2
Switch Position
ON
ON
OFF
ON
OFF
OFF
3
INT
EXT
4
1 VRMS
3 VRMS
Switch No:
Frequency
10 kHz
5 kHz
2.5 kHz
Switch ON:
Switch OFF:
Output Range VDC
5
6
7
8
0~5
±5
0~10
Only one switch ON
4 to 20mA output
works with any setting
Notes: Default factory settings are noted in BLUE in the above tables. Switch No. 5 of SW2 is not used.
3VRMS excitation is available only with the 18~30VDC supply voltage setting.
4.3 Oscillator Frequency:
Once you have established the proper excitation frequency for your transducer, refer to the tables below
to set the LDM-1000 oscillator frequency.
For 2.5 KHz excitation (default factory setting):
Switch Set SW2
Function:
Switch No:
2.5kHz
Switch Set SW1
Oscillator Frequency
1
2
OFF
OFF
Function:
Switch No:
250 HZ
3
OFF
Signal Bandwidth
4
5
OFF
OFF
For 5 KHz excitation:
Switch Set SW2
Function:
Switch No:
5kHz
Switch Set SW1
Oscillator Frequency
1
2
OFF
ON
Function:
Switch No:
250 HZ
3
OFF
Signal Bandwidth
4
5
OFF
OFF
For 10 KHz excitation:
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
6 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
Switch Set SW2
Function:
Switch No:
10 kHz
Switch Set SW1
Oscillator Frequency
1
2
ON
ON
Function:
Switch No:
1 kHz
Signal Bandwidth
3
4
5
ON
ON
ON
Note: The 1 kHz bandwidth setting is not recommended for excitation frequencies other than 10 kHz,
otherwise significant noise will be present on the output signal and performance will be degraded.
4.4 Oscillator ‘Sync’ Mode
The Oscillator ‘Sync’ mode setting will depend on the number of LDM-1000’s and transducers in your
system, and their physical locations. For a single LVDT or RVDT system you will be running the LDM1000 in the Master (INT) mode. For systems with multiple LDM-1000’s, especially when they are colocated, and/or the interconnect cables between the LDM-1000’s and the transducers run identical paths,
it is recommended to Master and Slave the LDM-1000 oscillators to prevent beat frequencies and
crosstalk between amplifiers and transducers. You will be selecting one LDM-1000 to serve as the
Master oscillator (INT), and the balance will be set-up in the Slave mode (EXT).
CAUTION: Attempting to synchronize two LDM-1000 set as masters (factory default setting) may
damage one or both units. Only one unit can be set to Master mode (INT, SW2 Switch 3 ON), otherwise
damage to the electronics may result (See connection diagrams). All other units must be in the Slave
mode (EXT, SW2 Switch 3 OFF).
Connecting Pins 11 (Sync OUT) and 12 (Sync COM) of the barrier strip, from unit to unit, will complete
the sync bus circuit (See connection diagrams). The power common serves as the return line. Use the
table below to configure your oscillator mode:
SW2-3
Mode
OFF
ON
SLAVE
MASTER
4.5 Oscillator Drive Capability
To ensure LVDT/RVDT compatibility with the LDM-1000 you must know the transducer current draw. The
LDM-1000 is designed with a robust sine wave oscillator; it is rated for a maximum drive current of 25mA
RMS with a voltage amplitude of 1 or 3 VRMS.
Therefore, you will need to know the LVDT/RVDT transducer input impedance for the frequency at which
you intend to operate it. With the (factory default) 3 VRMS oscillator voltage, the transducer input
impedance must be equal to or greater than 120 Ohms, which will result in current draw of 25mA or less.
If the impedance of the transducer is lower, the 1 VRMS setting must be selected; with this setting, the
LDM-1000 will be able to operate with impedances as low as 40 Ohms. The input impedance information
is available on the datasheets for all MEAS LVDTs and RVDTs.
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
7 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
5 Setting the Amplifier Gain
You will need to calculate the LVDT or RVDT full scale output, using the simple formula below:
LVDT/RVDT sensitivity (in V/V/inch or V/V/degree), at the selected frequency, multiplied with
the excitation voltage, (1 or 3 VRMS for the LDM-1000), multiplied with
the full scale of the LVDT in inches (or RVDT in degrees).
As an example, the calculation for a MEAS HR1000 LVDT (±1 inch range; 1 inch full scale), with a sensitivity
of 0.39V/V/inch at 2.5KHZ, with 3 VRMS excitation would be done as follows:
0.39 x 3 x 1 = 1.17 VRMS full scale output or 1.17 VRMS at ± 1 inch
Using the table below, select the gain settings (switch numbers 6, 7 and 8 of SW1) for the range your full
scale output falls into. In our example, you would use x0.4 HIGH.
Gain 1
Gain 2
Gain
SW1-7
SW1-8
Gain Lo/Hi
SW1-6
LVDT Full Scale
Output, VRMS
x0.4
x0.4
x1.2
x1.2
x3.63
x3.63
x4.43
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
LOW
HIGH
LOW
HIGH
LOW
HIGH
HIGH
ON
OFF
ON
OFF
ON
OFF
OFF
1.20 to 2.50
0.78 to 1.20
0.40 to 0.78
0.26 to 0.40
0.13 to 0.26
0.10 to 0.13
0.05 to 0.10
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
8 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
6 Dimensions and Wiring Terminals
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
9 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
7 Connection Diagrams
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
10 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
8 Calibration Procedure
Using the P1 and P2 terminal blocks according to the “Connection Diagrams” section of this manual, connect
the LVDT or RVDT, a DC voltmeter, and a power supply (see “Supply Voltage” under the “Initial Setup
Procedure” section of this manual) to the LDM-1000. Turn the power on and allow a 15 minute warm-up.
1. Disconnect the LVDT/RVDT primary wire from Terminal 1 of P1.
2. Adjust the ZERO potentiometer on the front panel until:
 the DC voltage output between terminals 9 (SIGNAL COM) and 10 (SIGNAL OUT)
 or the DC current between terminals 15 (CURRENT COM) and 16 (CURRENT OUT)
reads in the middle of the range (see “Internal Switches” under the “Initial Setup Procedure” section
of this manual for output DC voltage range selection); the middle of the ranges are as follows:
a. 0.0 VDC mid-range reading for ± 5 VDC Output
b. 2.5 VDC mid-range reading for 0 to +5 VDC output
c. 5.0 VDC mid-range reading for 0 to +10 VDC output
d. 12.0mA mid-range reading for 4 to 20mA output
3. Reconnect the LVDT/RVDT primary wire to Terminal 1 or P1
4. Insert the LVDT core into the middle of the bore, or rotate the RVDT shaft to the approximate center
of the mechanical range, until the output reads as close to the mid-range DC voltage or current as
possible (see mid-range readings in Step 2. above). If this adjustment is mechanically difficult or
impractical, approximate the correct position as closely as possible, and then adjust the ZERO
potentiometer until the output reads the middle of the range (see mid-range readings in Step 2.
above).
Note: Changing course gain settings (DIP switches) after this step may result in a zero shift. Should
you find it necessary to change the gain, you should repeat steps 1 through 4.
5. Displace the core of the LVDT or rotate the RVDT shaft in a positive direction (increasing DC voltage
between terminals 9 and 10 or increasing DC current between 15 and 16) to approximately 80% of
the full scale position you used in your calculation in “Setting the Amplifier Gain”.
6. Adjust the front panel PHASE potentiometer in the direction that increases the DC output signal until
the maximum output is reached; if the output does not peak and the PHASE potentiometer is at the
end of its adjustment range, leave it there and continue the calibration procedure.
Note: If at any point during the phase adjustment the output exceeds the maximum output limit of the
selected range, reduce the output back to a 70-80% level by adjusting the front panel SPAN
potentiometer, then continue with the phase adjust operation.
7. Return the LVDT core or the RVDT shaft back to the original center position. If the exact same midrange DC output as in Step 2 above is not observed, slightly re-adjust of the ZERO potentiometer.
8. Using a precision positioning device, displace the LVDT core or rotate the RVDT shaft in a positive
direction to the full scale position used in your calculation.
Note: The calibration can be made over a percentage of full scale by moving the core xx% of full
scale and adjusting the output for the same percentage.
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
11 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297
Operation Manual
LDM-1000 LVDT/RVDT Signal Conditioning Module
9. Adjust the front panel SPAN potentiometer for the required positive full scale DC output (usually the
maximum output limit of the selected range, in Step 2 above).
Note: If the required full-scale reading cannot be obtained by adjusting the SPAN potentiometer, the
gain of the signal conditioner can be reset by changing the internal switches (see the “Setting the
Amplifier Gain” section): If the SPAN potentiometer is fully counter clockwise, change to the next
higher gain. If the SPAN potentiometer is fully clockwise, change to the next lower gain.
10. Return the LVDT core or the RVDT shaft back to the original center position and re-check the output
reading (should be the same mid-range reading as in Step 2 above). If needed, use the ZERO
potentiometer to make a small adjustment.
11. Displace the LVDT core or rotate the RVDT shaft to the negative full scale position (lowest output DC
voltage or current); it should match the minimum reading for the range selected in Step 2 above. If
needed, use the SPAN potentiometer to make a small adjustment.
Note: Due to symmetry errors of all LVDTs and RVDTs, the exact minimum and maximum output
readings are rarely obtained.
9 Additional Information
Measurement Specialties, Inc. (NASDAQ MEAS) offers many other types of sensors and signal conditioners.
Data sheets can be downloaded from our web site at: http://www.meas-spec.com/datasheets.aspx
MEAS acquired Schaevitz Sensors and the SchaevitzTM trademark in 2000.
TECHNICAL CONTACT INFORMATION
NORTH AMERICA
EUROPE
ASIA
Measurement Specialties, Inc.
1000 Lucas Way
Hampton, VA 23666
United States
Phone: +1-800-745-8008
Fax: +1-757-766-4297
Email: [email protected]
Web: www.meas-spec.com
MEAS Deutschland GmbH
Hauert 13
D-44227 Dortmund
Germany
Phone: +49-(0)231-9740-0
Fax: +49-(0)231-9740-20
Email: [email protected]
Web: www.meas-spec.com
Measurement Specialties China Ltd.
No. 26, Langshan Road
High-tech Park (North)
Nanshan District, Shenzhen 518057
China
Phone: +86-755-33305088
Fax: +86-755-33305099
Email: [email protected]
Web: www.meas-spec.com
The information in this sheet has been carefully reviewed and is believed to be accurate; however, no responsibility is assumed for
inaccuracies. Furthermore, this information does not convey to the purchaser of such devices any license under the patent rights to the
manufacturer. Measurement Specialties, Inc. reserves the right to make changes without further notice to any product herein.
Measurement Specialties, Inc. makes no warranty, representation or guarantee regarding the suitability of its product for any particular
purpose, nor does Measurement Specialties, Inc. assume any liability arising out of the application or use of any product or circuit and
specifically disclaims any and all liability, including without limitation consequential or incidental damages. Typical parameters can and
do vary in different applications. All operating parameters must be validated for each customer application by customer’s technical
experts. Measurement Specialties, Inc. does not convey any license under its patent rights nor the rights of others.
Measurement Specialties Inc.
www.meas-spec.com
1000 Lucas Way, Hampton, VA 23666, United States
12 of 12
Doc P/N 09290100-000 Rev. B / October 2015
phone: +1-800-745-8008
fax: +1-757-766-4297