ZL-1906-15 The ZL-1906-15 is a 3PH, Y filter developed to meet the requirements of MIL-STD-461D, E or F. This filter has the maximum insertion loss possible for a very small package. This filter will perform well for the CE102 conducted emissions and will help some for the CE101 emissions. The filter also has significant transient suppression to ensure meeting the requirements of CS116 or a nearby lightening strike. If the filter will be used only with a 125Vac input, some adjustment can be made to the transient suppression devices to lower the clamping voltage. Operating Voltage = ________3Ph,125 Vac, 50 - 400 Hz = _________ 3Ph, 250 Vac, 50/60 Hz Max. Operating Current = _________ 15 Amp per Phase Operating Temperature = ________________ -40 - 50ºC Storage Temperature = _________________-55 - 100ºC Diel. Withstand (Line - Case) = ______ 1500 Vac (1 Min) Diel. Withstand (Line - Neut) = _______1500 Vdc (1 Min) Capacitance (Each line - case) = ________ 0.02 µF Max Transient Energy Absorption 8/20 µsec = 130 Joule/Line Minimum Varistor clamping Voltage = ________354 Volt No load Current (Line - Neut) = 0.25A max @ 125V, 60Hz 1.60A max @ 125V,400Hz Leakage Current = ________125V, 60 Hz, 2.25 mA Max = _______125V, 400 Hz, 15.1 mA Max = ______ 250 V, 50 Hz = 3.75 mA Max (L/L) Discharge Voltage after Disconnect from Power = 110V: 30 Volt Max after 2.0 sec Calculated MTBF = __________489,004 hrs GB @ 30ºC USA JMK Inc 15 Caldwell Dr. Amherst, NH 03031 EUR JMK Inc Glasgow G13 1DN Scotland UK INSERTION LOSS vs. FREQUENCY PH: 603 886-4100 FX: 603 886-4115 email: [email protected] PH: 44-(0) 7785310729 Fax: 44-(0) 141 589 1884