100W 0-10V Dimmable Constant Current Mode 100

100W 0-10V Dimmable
Constant Current Mode
100-DBFE Series
FEATURES:
● AC Input 100~277Vac
● Built-in Active PFC Function
● Protection: SCP / OVP / OTP / OCP
● High Operating Ambient Temp.: -30℃~+50℃
● Input Line Surges: 6KV
● Safety: Meet UL 8750 / Class 2 power unit
● EMI: Meet FCC Part15
● Comply with Indoor/Outdoor Waterproof (IP 67)
● Warranty: 3 years (refer to warranty policy)
● RoHS Compliant
PRODUCT SPECIFICATION
MODEL
DC OUTPUT
POWER(W)
DC OUTPUT
VOLTAGE(V)
OUTPUT
CURRENT(A)
OUTPUT
CURRENT
TOLERANCE
EFFICIENCY
O/P NOISE(P-P,V)
96
18-24
4
±3%
88%
1% Vo(max.)
DBFE-100U402-00
ELECTRICAL SPECIFICATION
INPUT VOLTAGE RANGE
90-305Vac, 127-431Vdc, Normal: 100-277Vac
INPUT FREQUENCY
Range: 47-63Hz, Normal: 50-60Hz
>0.9@Full Load 100-277Vac
ACTIVE POWER FACTOR
<20% at 80%-Full Load 100-277Vac
THD
TURN ON DELAY TIME
<1S at Full Load 100-277Vac
AC CURRENT
1.5A / 100Vac 0.6A/277Vac
INRUSH CURRENT (typ)
Cold Start 65A@230Vac
<0.75mA
LEAKAGE CURRENT
SHORT CIRCUIT PROTECTION
OVER VOLTAGE PROTECTION
OVER TEMP. PROTECTION
OVER CURRENT PROTECTION
SCP and OVP will restart automatically after the fault condition is removed
shut down and latch off o/p voltage , re-power on to recover
120%~160% rated output power ; Hiccup mode
OPERATING TEMP.
-30℃~+50℃@Full Load 100-277Vac
STORAGE TEMP.
-40℃~+80℃
RELATIVE HUMIDITY
10% to +90%, non-cond.
SAFETY
Meet UL 8750 / Class 2 power unit
Meet FCC Part15
EMI
WITHSTAND VOLTAGE
I/P-O/P:3.75KVAC, O/P-Grnd:0.5KVAC, I/P-Grnd:1.88KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG,O/P-FG :100M Ohms / 500VDC / 25℃ / 70% RH
DIMENSION (L*W*H)
232 * 46.5 * 31 mm【9.13 * 1.83 * 1.22 inch】
(1) All parameters not specially mentioned are measured 230VAC input.
(2) All specifications Typical @25℃, unless otherwise noted, at normal line and load.
(3)Ripple and Noise measured directly at pins/terminals at nom. load, 0.1uF bypass and 47uF electrolytic, pk-pk @20MHz bandwidth.
(4) Specified for free-air convection cooling.
(5) Minimum load is NOT required for proper operation .
(6) 100% Production Tested.
*REFERENCE: www.linkcom.com.tw
*Please contact [email protected], [email protected] for more information
Linkcom Manufacturing Co., Ltd.
5F., No. 127, Ln. 235, Baoqiao Rd., Xindian Dist., New Taipei City 231-45, Taiwan ▪ T: +886-2-8919-1380 ▪ F: +886-2-8919-1370 ▪ www.linkcom.com.tw
100-DBFE Series
100W 0-10V Dimmable
Constant Current Mode
DERATING CURVE
DIMENSIONS
*REFERENCE: www.linkcom.com.tw
Linkcom Manufacturing Co., Ltd.
5F., No. 127, Ln. 235, Baoqiao Rd., Xindian Dist., New Taipei City 231-45, Taiwan ▪ T: +886-2-8919-1380 ▪ F: +886-2-8919-1370 ▪ www.linkcom.com.tw
100W 0-10V Dimmable
Constant Current Mode
100-DBFE Series
DIMMING OPERATION
Parameters
Minimum
Typical
Absolute maximum voltageon on the 0-10(+) Purple Wire
-2V
─
Maximum
12V
Source current on the 0-10V(+) Purple Wire
0mA
─
1mA
0-10V Analog Dimming Typical Circuit
Dim(+) Purple
(Levition) IP710 Dimmer
PDBFE0100■XXX-00G
V
(Lutron) WTSTV-DV Dimmer
Dim(-) Gray
Output Current / 0-10VDC Dimming Input
100
Output Current %
80
60
40
20
0
0
1
2
3
4
5
6
7
8
9
10
11
12
Dimming Input(VDC)
Notes:
1. 0-10V Dimmable must be connect to extra two wires +Purple/-Gray on the output side.
2. When connected to different Dimmers, 0-10V dimmable version will have a ±10% output current tolerance.
3. Recommended dimmers are Leviton IP710,Lutron NTSTV-DV or equivalent.
4. If output side wires +Purple/-Gray are open, the output current Io will be 100%.
Linkcom Manufacturing Co., Ltd.
5F., No. 127, Ln. 235, Baoqiao Rd., Xindian Dist., New Taipei City 231-45, Taiwan ▪ T: +886-2-8919-1380 ▪ F: +886-2-8919-1370 ▪ www.linkcom.com.tw