OPERATIONS & MAINTENANCE MANUAL

LPS Series Shunt-Trip Disconnect Switch
OPERATIONS & MAINTENANCE MANUAL
Overview
The Littelfuse POWR-Switch® LPS series disconnect switch is an integrated power controller designed to meet the
requirements of NFPA®70 (National Electrical Code®), NFPA 72 (National Fire Alarm Code®), ANSI/ASME A17.1 (Safety Code for
Elevators and Escalators), NFPA 13 (Installation of Sprinkler Systems) and other state and local jurisdiction requirements with
regard to AC power for elevators.
The Littelfuse POWR-Switch LPS series disconnect switch may be ordered in 30 A, 60 A, 100 A, 200 A or 400 A configurations,
for 208, 240, 480 or 600 VAC (60 Hz), 3 or 4 wire systems. The Littelfuse POWR-Switch LPS series disconnect switch may be
configured for use as Service Equipment with the addition of a 2-port ground lug and the appropriate label per NEC 230.66
(option S).
Enclosures are available for The Littelfuse POWR-Switch LPS series disconnect switches which meet NEMA 1,
NEMA 3R, NEMA 4/4X and NEMA 12 standards.
The Littelfuse POWR-Switch LPS series disconnect switch is designed to interrupt the source of incoming AC power for a
single cable or hydraulic elevator, upon a signal from the Fire Alarm Control Panel (FACP). This is primarily to minimize the risk
of electric shock, and to prevent impact to the mechanical safety features of an elevator, caused by water released from the fire
sprinkler system.
800.TEC.FUSE | littelfuse.com
1 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
LPS SERIES POWR-SWITCH
Shunt Trip Disconnect Switch
Specifications (POWR-Switch)
Supply Voltage Rating*
208 V, 240 V, 480 V
Ampere Range
30 A, 60 A, 100 A, 200 A, 400 A
Interrupting Rating
200 kA
Enclosures
NEMA 1 (standard)
NEMA 3R, NEMA 4, NEMA 12 (optional)
ApprovalsUL Listed (File: E219511)
*Contact factory for 600 V options.
Specifications (Shunt Trip)
Voltage Rating
Max Inrush
Max On time
Momentary Inrush
120 V, 60 Hz
4A
1.5 cycles
140 VA
Features/Benefits
• Pre-engineered single unit, which makes
procurement easier than systems with
multiple components
• Reduces labor costs up to 66% and total
installation costs by over 30%
• Pre-installed UL listed Class J fuse holder – unique
Class J size eliminates the need for any rejection type
fuse clips
• Optional features offer flexibility for a variety
of applications
Description
The Littelfuse® POWR-Switch provides a simple
and economical solution for applications that require
selective coordination and shunt trip capabilities.
• Control power terminal block
Utilizes Class J time-delay fuses that are easily
coordinated with other system overcurrent devices.
The shunt trip capability allows the POWR-Switch
to meet the ANSI/ASME standard that requires
power to be automatically disconnected before
water is turned on by the fire safety system.
• Pre-wired control circuits lower installation time
• UL Listed package
• Cu and AI wire rated
• L
ockable operating handle meets all code and
safety requirements (Accepts up to 3 locks)
• Every unit is fully tested before delivery
Options
Applications
• Control power transformer with fuses and blocks
• Elevator circuits
• Data processing rooms
• Building emergency systems
• Fire safety interface relay
• Key to test switch
• Pilot light ”On”
Web Resources
• Isolated neutral lug
Download technical information: littelfuse.com/lps
• M
echanical interlock auxiliary contact for hydraulic
elevators with automatic recall (5 amp 120 Vac rated)
• Fire alarm voltage monitoring relay
• Option to bypass alarm when performing
maintenance (-AZ option)
• XPress-Ship™ service offers 48 Hours direct shipment
service on select fully loaded LPS POWR-Switches
800.TEC.FUSE | littelfuse.com
2 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
LPS SERIES POWR-SWITCH
Shunt Trip Disconnect Switch
Ordering Information
Complete catalog numbers consist of switch catalog numbers and the desired options. See example below.
Example Catalog Number from Desired Options
LPS1 T20 R1 K G N1 BF3 U – AZ = Littelfuse Catalog Number LPS1T20R1KGN1BF3U-AZ
K
Red
R
Green
G
100 A
N1 2 NO & 2 NC
LPS1* 100 A 480 V
T48
White W
200 A
N2
400 A
N4
LPS2* 200 A
30–60 A N6 1 NO & 1 NC
OPTION
CODE
120 V
OPTION
CODE
R2
AZ OPTION
(BYPASS
FIRE
ALARM
DURING
MAINT.
TEST)
OPTIONAL
RATING
24 VDC Coil
—
OPTION
CODE
T20
T24 120 VAC Coil R1
RATING
LPS3* 30 A 208 V
LPS6* 60 A 240 V
OPTION
CODE
OPTIONAL
RATING
OPTIONAL
OPTION
CODE
REQUIRED
RATING
OPTION
CODE
RATING
OPTIONAL
OPTION
CODE
OPTIONAL
RATING
OPTIONAL
OPTIONAL
ENCLOSURES
OPTION
CODE
REQUIRED
ISOLATED
NEUTRAL
LUG
FIRE ALARM
SHUNT TRIP
VOLTAGE
MONITORING
RELAY
RATING
REQUIRED
KEY TO
PILOT LIGHT
TEST SWITCH
“ON”
MECHANICAL
INTERLOCK AUX.
CONTACT FOR
HYDRAULIC
ELEVATORS W/
AUTOMATIC RECALL
(5 A ,120 VAC)
OPTION
CODE
RATING
BASE
CATALOG #
REQUIRED
CONTROL
POWER
FIRE SAFETY
TRANSFORMER
INTERFACE RELAY
STD. 100VA WITH
(3 PDT, 10 A, 120 V)
PRI & SEC FUSE
(120 V SEC.)
RATING
LITTELFUSE
SWITCH
CATALOG
NUMBER
A
1-Pole
F1
NEMA 3R
U
–
B
3-Pole
F3
NEMA 4
Y
–
NEMA 12
Z
–
AZ
–
LPS4* 400 A
–
*Part Numbers: Any voltage can be paired with any amperage. Options can be any combination but the ratings must match the option code. Not all options are required.
Contact factory for 600 V control power transformer option.
Note: When ordering - desired options must be listed in the order shown above. Typical options include Control Power Transformer, Fire Safety Interface Relay,
Mechanical Interlock Auxiliary Contact and Fire Alarm Voltage Monitoring Relay.
Dimensions of Enclosure
CATALOG SERIES AMPERE RATING
LPS3
NEMA 1 DIMENSIONS
NEMA 3R DIMENSIONS NEMA 4, 12 DIMENSIONS
LUG SIZE
30
24”H x 20”W x 9”D
24”H x 20”W x 8”D
24”H x 20”W x 10”D
#14 - #8 AL or CU
LPS6
60
24”H x 20”W x 9”D
24”H x 20”W x 8”D
24”H x 20”W x 10”D
#14 - #2 AL or CU
LPS1
100
24”H x 20”W x 9”D
24”H x 20”W x 8”D
24”H x 20”W x 10”D
#8 - 1/0 AL or CU
LPS2
200
30”H x 20”W x 9”D
30”H x 24”W x 8”D
30”H x 20”W x 10”D
#6 - 250kcmil AL or CU
LPS4
400
48”H x 36”W x 11”D
Contact Factory
Contact Factory
3/0 AL or CU
Note: Over-size enclosures used to accommodate control power transformer, interface relay and terminal blocks.
XPress-Ship™
US Only
Littelfuse XPress-Ship™ service offers 48 Hours** direct-shipment
service on select fully-loaded LPS POWR-Switch to meet your
urgent system requirements on time.
XPress-Ship™ switches include three JTD_ID Series
fuses rated at the device’s maximum ampacity.
AMPERE
RATING
VOLTAGE
RATING
CATALOG NUMBER
XPress-Ship™
ORDERING NUMBER
60 A
480 V
LPS6T48R1KGN6BF3-AZ
XPS6T48R1KGN6F3-AZ*
100 A
480 V
LPS1T48R1KGN1BF3-AZ
XPS1T48R1KGN1F3-AZ*
100 A
480 V
LPS1T48R1KGN1BF3
XPS1T48R1KGN1BF3
200 A
208 V
LPS2T20R1KGN2BF3-AZ
XPS2T20R1KGN2F3-AZ*
200 A
480 V
LPS2T48R1KGN2BF3
XPS2T48R1KGN2BF3
*AZ option includes B & F3 options.
**XPress-Ship™ 48 hour service requires ordering from XPress-Ship Ordering Numbers shown above and is subject to a maximum of any combination of three switches per customer order.
XPress-Ship service offers 48 hour shipment from the factory through standard ground transportation. For expedited delivery, contact your local Littelfuse Representative.
800.TEC.FUSE | littelfuse.com
3 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
OPERATION & MAINTENANCE
Shunt-Trip Operation
The disconnecting means is a shunt-trip operated switch. The control power source for the shunt-trip operator is a 120 Vac
supply originating in the Littelfuse POWR-Switch LPS Series disconnect. Current to the shunt-trip device is switched by an
isolation relay, which is in turn controlled by the FACP.
The control signal may be either 24 Vdc from the FACP (option R2) or a “dry” contact closure in the FACP (option R1).
In the case of a “dry” contact closure, the sensing voltage is 120 VAC originating in the Littelfuse POWR-Switch
LPS Series disconnect.
CAUTION: When using the “dry” contact closure, option 1, DO NOT supply 120 Vac from the FACP as equipment
damage or personnel injury may occur.
A key test option (option K) is available to test the shunt-trip circuit.
Supervisory Indication
Additionally, an optional separate relay can be specified to monitor the 120 Vac control power source in the Littelfuse
POWR-Switch LPS Series disconnect. This relay (option FR) is used to provide supervisory indication of “Control Power
Available” as required by NFPA 72 Section 6.15.4.4.
Fuse Table
POWR-SWITCH VOLTAGE/
TRANSFORMER TYPE
PRIMARY FUSES (2)
FUSE TYPE
FUSE RATING
208/120
240/120
480/120
600/120
KLDR001
KLDR500
KLDR400
KLDR250
SECONDARY FUSE (1)
FUSE TYPE
FUSE RATING
1
1/2
4/10
1/4
FLM1.12
FLM1.12
FLM1.12
FLM1.12
1-1/8
1-1/8
1-1/8
1-1/8
Other Options
Optional features include contact closure for control of auxiliary power, i.e. battery lowering/door opening system (options A and
B). Support for state of Arizona, Oregon and Texas requirements to prevent “nuisance” fire alarms by over-riding the “Control
Power not Available” signal when the Littelfuse POWR-Switch LPS Series disconnect is manually (intentionally) turned off, and
distinctive signaling for ON-OFF-TRIPPED conditions (option AZ).
All Littelfuse POWR-Switch LPS Series disconnect switches are UL-Listed and designed for safe access by qualified personnel.
When maintenance or shutdown service is required, no energized parts are exposed inside the enclosure when the disconnect
switch is manually turned to the OFF position. For proper maintenance safety precautions, always turn off incoming power
to the Littelfuse POWR-Switch LPS Series switch when possible. When servicing any live electrical equipment, always wear
appropriate personal protective equipment.
Power Wiring Torque Specifications
CHARACTERISTICS
LPS3
LPS6
LPS1
LPS2
LPS4
Amps
AWG
MCCB Mfr.
MCCB Catalog No.
MCCB Lug Type
MCCB Lug Torque (in-lbs)
Fuse Block Mfr.
Fuse Block Catalog No.
Fuse Lug Torque (in-lb)
Neutral Lug Mfr.
Neutral Lug Catalog No.
Neutral Lug Torque (in-lbs)
Ground Lug Mfr.
Ground Lug Catalog No.
Ground Lug Torque
30
10
ABB
S3H150DBBS4
K4TB
50 in-lb*
LITTELFUSE
LFJ60030-3
25 in-lb†
LITTELFUSE
LS21211
35 in-lb†
PANDUIT
LAMA 1/0-14-Q
35 in-lb‡
60
6
ABB
S3H150DBBS4
K4TB
50 in-lb*
LITTELFUSE
LFJ60060-3
45 in-lb†
LITTELFUSE
LS21211
45-120 in-lb†
PANDUIT
LAMA 1/0-14-Q
45 in-lb‡
100
3
ABB
S3H150DBBS4
K4TB
50 in-lb*
LITTELFUSE
LFJ60100-3
120 in-lb†
LITTELFUSE
LS21211
120 in-lb†
PANDUIT
LAMA 1/0-14-Q
50 in-lb‡
200
3/0
ABB
S3H225DDDS4
K4TD
200 in-lb*
LITTELFUSE
LFJ60200-3
275 in-lb†
LITTELFUSE
LS31231
275 in-lb†
PANDUIT
LAMA 250-56-Q
375 in-lb‡
400
(2) 3/0
ABB
S5H400DWS4
K5TG
275 in-lb*
LITTELFUSE
LFJ60400-3
275 in-lb†
LITTELFUSE
LS455712
500 in-lb†
PANDUIT
LAMA-350-38-Q
375 in-lb‡
Note: Torque specs apply only to wire compression screws. Other requirements may exist for attachment of lugs and accessories to these devices. See manufacturer data.
* ABB.com
† Littelfuse Device nameplate data
‡ Panduit, “Torque Chart for Aluminum Mechanical Connectors”
800.TEC.FUSE | littelfuse.com
4 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
OPERATION & MAINTENANCE
R1 Wiring Diagram (No AZ Option)
800.TEC.FUSE | littelfuse.com
5 of 13
© 2015 Littelfuse POWR-GARD Products
®
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
OPERATION & MAINTENANCE
R2 Wiring Diagram (No AZ Option)
800.TEC.FUSE | littelfuse.com
6 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
OPERATION & MAINTENANCE
R1 Wiring Diagram (With AZ Option)
POWRSWITCH
SCHEMATIC
R1-AZ
TERMINOLOGY
LINE -Connection to the input source of power.
LOAD -Connection to the protected circuit load.
DISCONNECT -Main switch that disconnects power
via manual, or shunt trip.
CONTROL TRANSFORMER -Converts the incoming line voltage to 120vac.
-An
optional door pilot light used to indicate
PL
the presence of control voltage.
Fire Alarm Supervisory Relay -Optional relay (FR) for monitoring control voltage.
N.O.F.A. -Abbreviation for Normally Open Fire Alarm
(contact closure initiates shunt trip).
Fire Alarm Isolation Relay -Provides fire alarm initiating circuit isolation.
KEY TEST -Optional door key-switch used for testing,
to trigger a shunt trip disconnect.
SHUNT TRIP -Mechanism, triggered by CR closure, that
opens the disconnect.
SW -Internal to the shunt trip mechanism that
opens when the switch is tripped.
120vac IS PROVIDED FROM
WITHIN THE POWRSWITCH.
ONLY A CONTACT CLOSURE
IS NEEDED.
OPTION B:
Auxiliary contacts are mechanically interlocked to the main
switch contacts. These auxiliary contacts follow the main switch
contacts.
OPTION AZ:
These contacts indicate the presence or absence of shunt
control voltage. However, if the main switch is turned off, these
contacts will indicate that shunt control voltage is present.
800.TEC.FUSE | littelfuse.com
7 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
OPERATION & MAINTENANCE
R2 Wiring Diagram (With AZ Option)
POWRSWITCH
SCHEMATIC
R2-AZ
TERMINOLOGY
LINE -Connection to the input source of power.
LOAD -Connection to the protected circuit load.
DISCONNECT -Main switch that disconnects power
via manual, or shunt trip.
CONTROL TRANSFORMER -Converts the incoming line voltage to 120vac.
PL -An optional door pilot light used to indicate
the presence of control voltage.
Fire Alarm Supervisory Relay -Optional relay (FR) for monitoring control voltage.
-Abbreviation
for Normally Open Fire Alarm
N.O.F.A.
(contact closure initiates shunt trip).
Fire Alarm Isolation Relay -Provides fire alarm initiating circuit isolation.
KEY TEST -Optional door key-switch used for testing,
to trigger a shunt trip disconnect.
SHUNT TRIP -Mechanism, triggered by CR closure, that
opens the disconnect.
SW -Internal to the shunt trip mechanism that
opens when the switch is tripped.
THIS WIRE IS USED ONLY IF KEY
TEST OPTION IS INSTALLED
OPTION B:
Auxiliary contacts are mechanically interlocked to the main
switch contacts. These auxiliary contacts follow the main switch
contacts.
OPTION AZ:
These contacts indicate the presence or absence of shunt
control voltage. However, if the main switch is turned off, these
contacts will indicate that shunt control voltage is present.
800.TEC.FUSE | littelfuse.com
8 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
Preventive Maintenance
• Periodically check torque on the wire compression screws in the power circuit. The chart included has the torque values for
the various models.
• Annual review of POWR-Switch is recommended. ABB has no specific maintenance recommendations. Otherwise, predictive
maintenance could be done by thermal-scan, either with an IR imager or a non-contact temperature sensor.
• Any unexpected temperature increase, not related to load variations or ambient temperature could signal a problem with
lug torque.
• Maximum temperature at any lug should never exceed 75 degrees C under any conditions.
• Clean and periodically dust product throughout the year.
Frequently Asked Questions
What UL listings does the Littelfuse
POWR-Switch have?
The POWR-Switch unit is UL-Listed to UL 98. The molded case switch used within
the POWR-Switch is UL-Listed to UL 489.
What codes and standards does the
Littelfuse POWR-Switch meet?
The POWR-Switch meets several NEC, NFPA 72, and ANSI/ASME standards.
Please refer to Littelfuse product literature for
more details.
How does the Mechanical Auxiliary
Contact Option (Option A) work?
The “A” Option is a set of auxiliary contacts that are mechanically interlocked to the
main switch. These contacts are generally used for auxiliary power interface such
as battery lowering. The contacts are used to signal initiation of auxiliary power in
the event of power loss. The contact is a single pole, double throw (SPDT) contact.
It is important to note that these contacts differentiate between manually turned
off or shunted off (refer to the table below).
MAIN SWITCH
STATE OF AUX CONTACTS
NO (9 & 10)
NC (8 & 9)
Off
On
Shunted
O
X
X
O = Off
How does the Mechanical Auxiliary
Contact Option (Option B) work?
X = On
The “B” Option is two sets of auxiliary contacts that are mechanically interlocked
to the main switch. These contacts are generally used to monitor the status of the
switch. The contacts are double pole, double throw (DPDT) contacts. It is important
to note that these contacts will follow the state of the switch.
(Refer to the table below).
STATE OF CONTACTS
MAIN SWITCH
NO
NC (
Off
On
Shunted
O
X
O
O = Off
How does the AZ Option
(Option -AZ) work?
X
O
X
X = On
Internal wiring between the molded case switch’s auxiliary contacts and the fire
relay’s contacts implements a logic circuit that monitors the availability of shunt trip
power. Terminals 15-16 close only if the main switch is on and the shunt trip power
fails. They will not close if the main switch is manually turned off for maintenance,
preventing a false alarm. (Refer to table below).
MAIN SWITCH
STATE OF AUX CONTACTS
NO (15 & 16)
NC (14 & 15)
Off, Power Available
On, Power Available
Off, No Power
On, No Power
O
o
O
X
O = Off
800.TEC.FUSE | littelfuse.com
X
O
O
9 of 13
X
x
X
O
X = On
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
Does the instantaneous trip feature built
into the molded case switch create the
potential to strand passengers when used
on circuits with hydraulic elevators and
auxiliary battery lowering?
The shunt trip mechanism within the switch is utilized, not the instantaneous trip
feature of the switch. Even in the event of an instantaneous trip condition, the
alarm relay will respond the same as when the switch is shunted off. There is no
potential for stranding passengers when Littelfuse POWR-Switch units are installed
with the Mechanical Interlock Auxiliary Contact Option
(Option A, battery back-up feature).
During a power loss, will the state of the
switch change state?
The POWR-Switch will not change state. However, units installed with the
Mechanical Interlock Auxiliary Contact Option (Option A) will distinguish between
turned off and shunted off and send a signal accordingly to the fire alarm controller.
How does the POWR-Switch decide
when the elevator needs to be lowered?
The Littelfuse POWR-Switch does not make that decision. The POWR-Switch
provides a signaling means to the fire alarm controller. The fire alarm controller
makes all decisions regarding when and where the elevator is to be lowered.
Does the fire safety relay monitor the
voltage required by NFPA 72?
No, the fire safety relay option (Littelfuse option R1 or R2) does not monitor
voltage. Littelfuse offers both a fire safety relay and fire alarm voltage monitoring
relay options. The Littelfuse Fire Alarm Voltage Monitoring Relay (F1/F3 option)
does meet NFPA 72 (National Fire Alarm Code) requiring control circuits to be
monitored for presence of voltage. The Littelfuse unit is wired to sense the voltage
available to initiate the shunt-trip. It will change state if a power loss occurs. It does
not rely on the shunt-trip itself.
Does the Littelfuse POWR-Switch
require any periodic maintenance?
No specific maintenance is required. However, like most electrical equipment, it
is always a good idea to periodically check wire connections for proper torque and
ensure fuse clips are clean and tight. Please refer to the Preventive Maintenance
section of this document for more details.
How do you hook up the dry contacts for
the battery back-up option?
This will depend on how the Mechanical Auxiliary Contact (Option A) will be
connected. The A Option will follow the ON/OFF of the switch when the handle is
in the off position. Terminals 8 & 9 will be used when following the NC contacts.
Terminals 9 &10 will be used when following the NO contacts.
Where do you land the power for the
shunt trip on the terminal strip?
Where does the fire alarm get
connected for monitoring the status of
the switch?
How do I connect to the fire alarm
voltage-monitoring relay?
800.TEC.FUSE | littelfuse.com
This will vary if using the R1 Option (120 VAC) or the R2 Option (24 Vdc). Terminals 1
& 3 will be used for the R1 Option. Terminal 3, 7, & 24 will be used for the R2 Option.
This will vary on which option is being utilized (A or B). Option A will use terminals
8, 9, & 10. Option B will use terminals 14, 15, & 16.
This is commonly referred to as the FR relay and is Littelfuse Option F1 or F3.
Terminals 11, 12, & 13 are used for this purpose.
10 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
FREQUENTLY ASKED QUESTIONS
If a POWR-Switch is ordered with a
wrong component, can the component
be changed in the field?
No. To comply with UL guidelines, product modifications can only be completed by
authorized factory personnel. Other modifications will void the Littelfuse UL listing.
Can the POWR-Switch be used as a
service entrance switch?
The Littelfuse POWR-Switch is UL-Listed per UL 98. Yes, it can be used as a service
entrance if properly labeled as such.
Can the POWR-Switch be fed in reverse
with the line from the bottom and load
out the top of the switch?
When connecting the POWR-Switch
to the fire alarm, what do you do
with the neutral?
Can the POWR-Switch be used in an
application with no fire alarm and can a
smoke detector be connected instead?
Does the FR Relay (Option F1 or F3)
change state during a power loss?
Is the operating handle of the
POWR-Switch lockable in the
“off” position only?
What enclosures are available for the
POWR-Switch?
Is a CPT always required in a
POWR-Switch?
No, the POWR-Switch will not properly function.
There is no need to tie into the neutral. POWR-Switch units equipped with a
Control Power Transformer (CPT) will supply 120 volts.
No, this is not in accordance with the fire code.
Yes, the FR relay will always change state. The FR relay is designed to monitor
voltage that is available for the shunt trip. This is a requirement of NFPA 72.
Yes, the handle can only be locked from the “off” position and can accommodate a
maximum of three padlocks.
All ratings of the POWR-Switch come standard with a UL (NEMA) type 1 enclosure.
Optional enclosures include UL (NEMA) type 3R, 4, and 12.
In most cases, a CPT will be required to supply the 120 Vac for shunt tripping.
How is the Littelfuse POWR-Switch
typically shipped and how much do
they weigh?
The form of shipment will depend on the number of units ordered. Large quantities
are typically shipped via truck and smaller quantities shipped via UPS. 30-100 amp
units weigh approximately 70 pounds and 200 amp units weigh around 85 pounds.
400 amp units weigh over 200 pounds and can only be shipped via truck.
What kind of fuses does Littelfuse
recommend?
JTD or JTD_ID fuses. The fuse holders installed in the panels are made to
accommodate this type fuse. These fuses afford good short circuit and motor load
protection. For fuse sizing see NEC Article 430.52 which says “in a nutshell” motor
branch circuit fuses of the time-delay type may be sized for up to 175% of the
motor full load amps.
What is the warranty for the LPS?
Under most circumstances, there is a one-year warranty. Please contact your local
Littelfuse Sales Representative if you have any questions or a unique situation.
800.TEC.FUSE | littelfuse.com
11 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
FREQUENTLY ASKED QUESTIONS
What do I do if the door is stuck?
If the handle is in the ON position, pointing straight down
or at 270 degrees (i.e. south), there should be no problem
opening the door after switching it to the OFF position. If the
handle seems to be in the down position, yet slightly to the
right, it is a good indicator that the MCCB has been shunted.
(See picture). This is easily corrected
Step 1: The technician should place their left hand just to
the left of the handle with the handle between their
index finger and thumb. Then apply pressure with a
majority of body weight.
Step 2: T
urn the handle to the OFF position while
maintaining pressure on the door.
Step 3: T
urn the handle back to the ON position while
maintaining pressure on the door.
Step 4: T
urn the handle back to the OFF position, while
maintaining pressure on the door. At this point the
MCCB should be reset in the correct position, with
no further hindrances in opening the door.
800.TEC.FUSE | littelfuse.com
12 of 13
© 2015 Littelfuse POWR-GARD® Products
Rev: 051815
LPS Series Shunt-Trip Disconnect Switch
XPRESS-SHIP™ FREQUENTLY ASKED QUESTIONS
I need a part number that is not listed on
the XPress-Ship Program. Can I get an
expedited shipment service?
Yes, Littelfuse offers expedite shipment service for part numbers outside the
XPress-Ship Program.
I have a repeat order for a XPress-Ship
Program part number, I have ordered in
the past. Can I get the same part number
in standard shipment service?
Yes, you may request standard shipment service by substituting the ordering part
number prefix ‘XPS’ with ‘LPS’
Can I get the XPress-Ship program
product I ordered air shipped?
Contact your Littelfuse Customer Service Team for pricing and availability.
Example:
XPress-Ship ordering number: XPS6T48R1KGN6F3-AZ
Standard shipment ordering number: LPS6T48R1KGN6F3-AZ
Yes, you may request air shipment when booking the order, however the customer
would be responsible for all charges involved for air shipment.
I need 10 units of a specific part number
from the XPress-Ship Program.
Can I get the program’s 48 hour
service on all units?
No, XPress-Ship 48 hour service is limited to three switches per customer order.
Do I need to order fuses separately,
when I place an order for a Part Number
in XPress-Ship Program?
No, all part numbers offered through XPress-Ship include three pre-installed JTD_
ID Series fuses rated at the device’s maximum ampacity.
Contact your Littelfuse Customer Service Team for availability in scenarios
such as this.
Example:
XPS2T48R1KGN2BF3 is a 200 A switch and ships with three
0JTD200.XXID fuses installed.
Note: When ordering LPS Series in standard shipment service, fuses
must be ordered separately.
Can I receive a fuse rating other than the
maximum rating supplied with the switch
in the XPress-Ship Program?
800.TEC.FUSE | littelfuse.com
No, switches in the XPress-Ship Program are offered with fuses pre-installed and
rated to the maximum ampere rating of the switch.
Customers may request a different fuse rating while booking the order and those
will be charged and shipped separately, but are not included under the XPressShip Program Service Terms.
13 of 13
© 2015 Littelfuse POWR-GARD® Products