Cooper Bussmann® Quik-Spec™ Power Module™ Panel

Cooper Bussmann® Quik-Spec™ Power Module™ Panel
PMP All-In-One Module
Power Module Panel
Ratings (Amps) (Panelboard Bus)
400
600
800
Catalog Number
PMP-400
PMP-600
PMP-800
Panel Components
Voltage/Amp
Ratings
Component 1 (Required)
Control power transformer (CPT) Std. 100VA with PRI &
SEC Fuse (120V secondary)
Component 2 (Required)
Fire safety interface Relay (3PDT, 10 amp, 120V)
Component 3 (Optional)
Key to test switch
Component 4 (Optional)
Pilot light – “ON”
Red
Green
White
Features and Options
400-800 amp Bus MLO and/or Main Switch*
200,000 amp RMS Short-Circuit Current Rating
Feeder switches 30-200 amp, 600Vac with Class J Clips1
Copper Bus
* Contact Cooper Bussmann for applications greater than 800 amps
Optional Features
•
•
•
•
•
•
•
•
•
•
24Vdc Coil
120Vac Coil
120Vac
Component 5 (Optional)
Isolated neutral lug (full capacity)2
•
•
•
•
208Vac
240Vac
480Vac
600Vac
Component 6 (Required)
Mechanically interlocked auxiliary contact for hydraulic
elevators with battery back-up (5 amp 120Vac rated)
Component 7 (Optional)
Fire alarm voltage monitoring relay
(To monitor shunt trip voltage)
30-60A
100A
200A
1 NO & 1 NC
Single-Pole
Control power transformer with fuses and blocks
Fire safety interface relay
Key to test switch
Pilot light – “ON”
Isolated neutral lug2
Mechanically interlocked auxiliary contact for hydraulic elevators with
battery backup (5 amp 120Vac rated)
Fire Alarm Voltage Monitoring Relay (to monitor Shunt Trip Voltage)
NEMA 3R enclosures available (consult factory)
Phase failure and undervoltage relay available (consult factory)
For added safety, use the Cooper Bussmann® SAMI™ fuse covers to
improve maintenance personnel protection [OSHA 1910.335(A)(2)(ii)]3
Agency Information
• UL 98 Enclosed and Dead-Front Switches
1
Class J fuses not included.
Oversized 200% rated neutral option available where required by excessive non-linear loads.
Through 100A.
2
3
0608
BU-SB08354
Page 1 of 6
Data Sheet 1146
Module Switch Options, X Dimensions and Lug Data
Switch
Amp Rating
Mounting
600 Volt – Branch Switch Uni t 1
30
Horizontal
30-30
Horizontal
60
Horizontal
60-60
Horizontal
100
Horizontal
100-100
Horizontal
200
Horizontal
200-200
Horizontal
600 Volt - Main Switch
400
Horizontal
600
Horizontal
800
Vertical
“X” Units
Conductors
per Phase
Terminal Wire Range
6X
6X
6X
6X
6X
6X
6X
6X
1
1
1
1
1
1
1
1
#14 - 1/0 Al or Cu
#14 - 1/0 Al or Cu
#14 - 1/0 Al or Cu
#14 - 1/0 Al or Cu
#14 - 1/0 Al or Cu
#14 - 1/0 Al or Cu
#4 - 300 kcmil Al or Cu
#4 - 300 kcmil Al or Cu
1X
3X
9X
1 or 2
1 or 2
1 or 2
(1) 250 - 750kcmil (2) 3/0 - 250 kcmil Al or Cu
(1) #4 - 600kcmil (2) 1/0 - 250 kcmil Al or Cu
(1) 250 - 750kcmil (2) 3/0 - 250 kcmil Al or Cu
May mix switch amps 30 to 200A: 30/60, 30/100, 30/200, etc.
1
Top
Main Lugs Terminal Data Standard Mechanical Lugs
Main Amp
Rating
400
600
800
Conductors
per Phase
1
2
2
4
Min. Wire Bending Space (inches)2
A
B
C
Terminal Wire Range
3/0 - 750 kcmil Al or Cu
3/0 - 250 kcmil Al or Cu
#4 - 500 kcmil Al or Cu
#2 - 600kcmil Al or Cu
14.00
10.625
7.00
14.00
18.00
10.625
10.625
7.00
7.00
A
C
2
Wire bending space can vary per local codes and standards requirements.
C
B
Standard Panel Box Dimension with Available Panel Space
Dimensions (Inches)
HxWxD
57 x 40 x 10.4
73.5 x 44 x 10.4
90 x 44 x 10.4
Amps
400
600
800
40"
X
“X” Units3
18X
30X
40X
MLO Incoming* - Top or Bottom
Branch
Unit
Mounting
Space
3
Where X Units exceed panel space, use feed-through lugs and second enclosure.
Feed-Through Lugs
Amps
400
600
800
Accessory Control Enclosure
(ACE)**
6
“X” Space
3X
3X
7X
6
30A
30A
6
60A
60A
6
100A
100A
6
200A
200A
***
Feed-Through Lugs
Wire bending space per NEC® Table 312.6(A)
* MLO standard, x-space does not affect brand x-space available.
Accessory Control Enclosure
ACE
** One ACE unit per four shunt trip module switches.
*** See table.
6X
Each ACE will handle individual control power transformers and isolation relays for up to four switch units.
0608
BU-SB08354
Page 2 of 6
Data Sheet 1146
Maximum Horsepower Rating of Switch
Voltage
208Vac-3P
240Vac-3P
480Vac-3P
600Vac-3P
30A
5
5
10
15
Feeder Switch Amp Rating
60A
100A
10
15
10
20
25
40
30
50
200A
40
40
75
100
400A
75
75
150
200
Main Switch Amp Rating
600A
100
125
250
350
800A
150
150
350
450
Maximum horsepower rating of switch with Class J fuses, medium-duty inrush (NEC® Code Max 175%). Recommended Hp to calculate fuse and switch size.
The above table can be used for estimating switch size for motor loads based upon the motor horsepower. Size the switch so that the Class J, time-delay fuses
are used at a minimum of 150% of motor full-load amps or next size up. For general applications, excluding wound rotor and DC motors, NEC® 430.52 allows
sizing at 175% of motor full-load amps or the next standard size per NEC® 240.6.
Note:
In sizing the fuses, the motor FLA, is per NEC® Table 430.250, not per nameplate information. Inrush currents of motors may vary, consult motor
manufacturer data for correct sizing. On elevator applications, motor load plus auxiliary loads need to be considered. Follow elevator manufacturer’s
recommendation for correct fuse sizing.
Standard Shunt Trip Ratings: 30-100A, 200A & 400-800A
Voltage
120Vac, 60Hz
1
Max Inrush
4 amps
Max Ontime1
1.5 cycles
Momentary Inrush
140VA
Will handle up to 447VA inrush.
0608
BU-SB08354
Page 3 of 6
Data Sheet 1146
Typical Control with Wiring Options for Fire Safety Interface (Option R1)
Legend
N.O.F.A. Normally Open Fire Alarm contacts supplied from the fire alarm system to initiate the shunt trip.
Shunt Trip Solenoid for remote trip of switch, which is activated by the closing of the fire alarm contacts or key test switch.
Option R1 Fire Safety Interface Relay that is operated at 120Vac from secondary of transformer. No additional power needed.
CR Control Relay used to isolate the N.O.F.A. contacts from the duty of the shunt trip.
FR Fire Alarm Voltage Monitoring Relay used to monitor presence of voltage in switch from a remote location (Fire Alarm Control Panel).
PL Pilot Light to visually indicate presence of voltage on outside of switch enclosure.
CPT Control Power Transformer used to step down line voltage to 120VAC to power shunt trip coil.
SW Aux. Normally closed contact when switch is closed. Opens as power switch opens.
Key Test Key-to-Test switch used to operate shunt trip from the outside of switch enclosure. Can be used for trouble-shooting and inspection.
Mechanically Interlocked Auxiliary Contact – Contact used to disconnect secondary source of power.
Terminal block connection point.
Pre-wired connection point.
0608
BU-SB08354
Page 4 of 6
Data Sheet 1146
Typical Control with Wiring Options for Fire Safety Interface (Option R2)
Legend
N.O.F.A. Normally Open Fire Alarm contacts supplied from the fire alarm system to initiate the shunt trip.
Shunt Trip Solenoid for remote trip of switch, which is activated by the closing of the fire alarm contacts or key test switch.
Option R2 Fire Safety Interface Relay that is operated at 24Vdc from fire alarm system. May require an additional power source to be needed.
CR Control Relay used to isolate the N.O.F.A. contacts from the duty of the shunt trip.
FR Fire Alarm Voltage Monitoring Relay used to monitor presence of voltage in switch from a remote location (i.e., Fire Alarm Control Panel).
PL Pilot Light to visually indicate presence of voltage on outside of switch enclosure.
CPT Control Power Transformer used to step down line voltage to 120Vac to power shunt trip coil.
SW Aux. Normally closed contact when switch is closed. Opens as power switch opens.
Key Test Key-to-Test switch used to operate shunt trip from the outside of switch enclosure. Can be used for trouble-shooting and inspection.
Mechanically Interlocked Auxiliary Contact Contact used to disconnect secondary source of power.
Terminal block connection point.
Pre-wired connection point.
0608
BU-SB08354
Page 5 of 6
Data Sheet 1146
Section 16XXX – Cooper Bussmann® Quik-Spec™ Power Module™ Panel
Elevator – Computer Room – Emergency Systems
Part 2 – Products
Part 1 – General
2.01
Manufacturers
A. Cooper Bussmann® Quick-Spec™ Power Module™ Panel - PMP
2.02
General Conditions & Requirements
A. Provide Power Module Panel as shown on drawings. The Power
Module Panel shall be constructed, listed and certified to the
standards as listed in 1.05. The Power Module Panel shall be
____ amp (MLO) (main switch) with copper bus (120/208V,
3-phase, 3W or 4W) (277/480V, 3 phase, 3W or 4W). The Power
Module Panel shall have individual horsepower-rated fusible feeder
switches with shunt trip capabilities (unless indicated). Feeder
switches shall have ampere ratings based upon elevator
manufacturer requirements (if elevator load is present) and utilize
Class J fuses (provided separately). All shunt trip fusible feeder
switches shall have as an accessory a relay, control power
transformer and other options (as listed below). The control power
transformer shall be 100VA with primary and secondary fuses. The
primary voltage rating shall be ____ volts with a 120 volt
secondary. The isolation relay shall be 3PDT, 10 amp, 120V. The
coil of the isolation relay shall be ______ (120Vac or 24Vdc). A
normally open dry contact shall be provided by the Fire Alarm
Safety System to energize the isolation relay and activate the shunt
trip solenoid (140VA inrush at 120V). (Note: If 24Vdc coil is
selected, a separate 24Vdc source and contact may need to be
provided in order to comply with the Fire Alarm Safety System
power requirements.)
Additional accessories provided for each fusible shunt trip switch
include:
_____ Key to Test Switch
_____ “On” Pilot Light (Green, Red or White)
_____ 1P NC Mechanical Interlock (required for hydraulic elevators
with automatic recall)
_____ Fire Alarm Voltage Monitoring Relay (Needed to comply with
NFPA 72)
The module shall have been successfully tested to a shortcircuit rating with Cooper Bussmann® Low-Peak® Class J
fuses at 200,000 amps RMS Symmetrical. All switches shall
have shunt trip capabilities at 120Vac from remote fire safety
signal. Branch feeders shall be selectively coordinated and
fed with an upstream supply overcurrent protective device at
a minimum of 2:1 size ratio utilizing Low-Peak (Class J, RK1,
or L) fuses.
1.01
Description
A. Work of this section shall conform to the requirements of the
Contract Documents.
1.02
Section Includes
A. Provide Elevator Power Module Panel, fuses and accessories as
required and specified on Contract Drawings to distribute electrical
power to all Elevators.
1.03
Related Systems
A. (Reference other sections of the specification which cover Elevator
installation)
1.04
Codes
A. All work shall be performed in accordance with the latest edition of
applicable standards, codes and laws.
1. NFPA-70 (NEC®) 2008 Edition- Section 620.51(A)-(C), 620.62,
620.91(C)
2. Canadian Electric Code Part 1 (2006 Edition) Section 38-051,
38-062
3. ANSI/ASME A17.1-2007 - Section 2.8.3.3.2
4. NFPA-72 2007 Edition - Section 6.16.4.4
A. Except as modified by governing codes, all equipment shall be
manufactured in accordance with the latest applicable standards:
1. Panelboards, UL 67 and CSA - C22.2 No. 29
2. Switchboards, UL 891 and CSA – C22.2 No. 31
1.06 Substitutions
A. Substitutions shall comply with the requirements of the General
Conditions and General Requirements. The names of manufacturers
and model numbers have been used to establish types of
equipment and standards of quality. A submittal shall contain
`
sufficient information to prove compliance with Contract
Documents. This includes compliance with all pertinent sections of
codes and standards as specified above.
1.07
Submittals
A. Submit shop drawings and product data under the provisions of the
General Conditions.
B. Product Data: Provide manufacturer’s catalog information showing
dimensions, configurations, and methods of mounting and
installation.
C. Submit listing of all types, sizes and quantity of fuses which will be
installed including the location of each.
D. Spare fuses shall be supplied as required by (reference fuse
specification section).
Part 3 – Execution
3.01
Installation
A. All material installation shall be in accordance with manufacturers
recommendations and the provisions of applicable codes.
B. Fuses shall not be installed until equipment is ready to be
energized.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive
product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any
products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
0608
BU-SB08354
Page 6 of 6
Data Sheet 1146