LPS Series Datasheet

Pre-Engineered Solution Datasheet
LPS SERIES POWR-SWITCH
Shunt Trip Disconnect Switch
Specifications (POWR-Switch)
Supply Voltage Rating*
208 V, 240 V, 480 V
Ampere Range
30 A, 60 A, 100 A, 200 A, 400 A
Interrupting Rating
200 kA
Enclosures
NEMA 1 (standard)
NEMA 3R, NEMA 4, NEMA 12 (optional)
ApprovalsUL Listed (File: E219511)
*Contact factory for 600 V options.
Specifications (Shunt Trip)
Voltage Rating
Max Inrush
Max On time
Momentary Inrush
120 V, 60 Hz
4A
1.5 cycles
140 VA
Features/Benefits
• Pre-engineered single unit, which makes
procurement easier than systems with
multiple components
• Reduces labor costs up to 66% and total
installation costs by over 30%
• Pre-installed UL listed Class J fuse holder – unique
Class J size eliminates the need for any rejection type
fuse clips
• Optional features offer flexibility for a variety
of applications
Description
The Littelfuse® POWR-Switch provides a simple
and economical solution for applications that require
selective coordination and shunt trip capabilities.
• Control power terminal block
Utilizes Class J time-delay fuses that are easily
coordinated with other system overcurrent devices.
The shunt trip capability allows the POWR-Switch
to meet the ANSI/ASME standard that requires
power to be automatically disconnected before
water is turned on by the fire safety system.
• Pre-wired control circuits lower installation time
• UL Listed package
• Cu and AI wire rated
• L
ockable operating handle meets all code and
safety requirements (Accepts up to 3 locks)
• Every unit is fully tested before delivery
Options
Applications
• Control power transformer with fuses and blocks
• Elevator circuits
• Data processing rooms
• Building emergency systems
• Fire safety interface relay
• Key to test switch
• Pilot light ”On”
Web Resources
• Isolated neutral lug
Download technical information: littelfuse.com/lps
• M
echanical interlock auxiliary contact for hydraulic
elevators with automatic recall (5 amp 120 Vac rated)
• Fire alarm voltage monitoring relay
• Option to bypass alarm when performing
maintenance (-AZ option)
• XPress-Ship™ service offers 48 Hours direct shipment
service on select fully loaded LPS POWR-Switches
littelfuse.com
1 of 2
© 2015 Littelfuse POWR-GARD® Products
Rev: 051915
Pre-Engineered Solution Datasheet
LPS SERIES POWR-SWITCH
Shunt Trip Disconnect Switch
Ordering Information
Complete catalog numbers consist of switch catalog numbers and the desired options. See example below.
Example Catalog Number from Desired Options
LPS1 T20 R1 K G N1 BF3 U – AZ = Littelfuse Catalog Number LPS1T20R1KGN1BF3U-AZ
K
Red
R
Green
G
100 A
N1 2 NO & 2 NC
LPS1* 100 A 480 V
T48
White W
200 A
N2
400 A
N4
LPS2* 200 A
30–60 A N6 1 NO & 1 NC
OPTION
CODE
120 V
OPTION
CODE
R2
AZ OPTION
(BYPASS
FIRE
ALARM
DURING
MAINT.
TEST)
OPTIONAL
RATING
24 VDC Coil
—
OPTION
CODE
T20
T24 120 VAC Coil R1
RATING
LPS3* 30 A 208 V
LPS6* 60 A 240 V
OPTION
CODE
OPTIONAL
RATING
OPTIONAL
OPTION
CODE
REQUIRED
RATING
OPTION
CODE
RATING
OPTIONAL
OPTION
CODE
OPTIONAL
RATING
OPTIONAL
OPTIONAL
ENCLOSURES
OPTION
CODE
REQUIRED
ISOLATED
NEUTRAL
LUG
FIRE ALARM
SHUNT TRIP
VOLTAGE
MONITORING
RELAY
RATING
REQUIRED
KEY TO
PILOT LIGHT
TEST SWITCH
“ON”
MECHANICAL
INTERLOCK AUX.
CONTACT FOR
HYDRAULIC
ELEVATORS W/
AUTOMATIC RECALL
(5 A ,120 VAC)
OPTION
CODE
RATING
BASE
CATALOG #
REQUIRED
CONTROL
POWER
FIRE SAFETY
TRANSFORMER
INTERFACE RELAY
STD. 100VA WITH
(3 PDT, 10 A, 120 V)
PRI & SEC FUSE
(120 V SEC.)
RATING
LITTELFUSE
SWITCH
CATALOG
NUMBER
A
1-Pole
F1
NEMA 3R
U
–
B
3-Pole
F3
NEMA 4
Y
–
NEMA 12
Z
–
AZ
–
LPS4* 400 A
–
*Part Numbers: Any voltage can be paired with any amperage. Options can be any combination but the ratings must match the option code. Not all options are required.
Contact factory for 600 V control power transformer option.
Note: When ordering - desired options must be listed in the order shown above. Typical options include Control Power Transformer, Fire Safety Interface Relay,
Mechanical Interlock Auxiliary Contact and Fire Alarm Voltage Monitoring Relay.
Dimensions of Enclosure
CATALOG SERIES AMPERE RATING
LPS3
NEMA 1 DIMENSIONS
NEMA 3R DIMENSIONS NEMA 4, 12 DIMENSIONS
LUG SIZE
30
24”H x 20”W x 9”D
24”H x 20”W x 8”D
24”H x 20”W x 10”D
#14 - #8 AL or CU
LPS6
60
24”H x 20”W x 9”D
24”H x 20”W x 8”D
24”H x 20”W x 10”D
#14 - #2 AL or CU
LPS1
100
24”H x 20”W x 9”D
24”H x 20”W x 8”D
24”H x 20”W x 10”D
#8 - 1/0 AL or CU
LPS2
200
30”H x 20”W x 9”D
30”H x 24”W x 8”D
30”H x 20”W x 10”D
#6 - 250kcmil AL or CU
LPS4
400
48”H x 36”W x 11”D
Contact Factory
Contact Factory
3/0 AL or CU
Note: Over-size enclosures used to accommodate control power transformer, interface relay and terminal blocks.
XPress-Ship™
US Only
Littelfuse XPress-Ship™ service offers 48 Hours** direct-shipment
service on select fully-loaded LPS POWR-Switch to meet your
urgent system requirements on time.
XPress-Ship™ switches include three JTD_ID Series
fuses rated at the device’s maximum ampacity.
AMPERE
RATING
VOLTAGE
RATING
CATALOG NUMBER
XPress-Ship™
ORDERING NUMBER
60 A
480 V
LPS6T48R1KGN6BF3-AZ
XPS6T48R1KGN6F3-AZ*
100 A
480 V
LPS1T48R1KGN1BF3-AZ
XPS1T48R1KGN1F3-AZ*
100 A
480 V
LPS1T48R1KGN1BF3
XPS1T48R1KGN1BF3
200 A
208 V
LPS2T20R1KGN2BF3-AZ
XPS2T20R1KGN2F3-AZ*
200 A
480 V
LPS2T48R1KGN2BF3
XPS2T48R1KGN2BF3
*AZ option includes B & F3 options.
**XPress-Ship™ 48 hour service requires ordering from XPress-Ship Ordering Numbers shown above and is subject to a maximum of any combination of three switches per customer order.
XPress-Ship service offers 48 hour shipment from the factory through standard ground transportation. For expedited delivery, contact your local Littelfuse Representative.
littelfuse.com
2 of 2
© 2015 Littelfuse POWR-GARD® Products
Rev: 051915