PGR-8800 Arc-Flash Relay Rev 3-A-112913 Manual

Arc-Flash Relay
PGR-8800
PGR-8800
ARC-FLASH RELAY
REVISION 3-A-112913
ARC-FLASH RELAY
PGR-8800 SERIES
Document Number: PM-1400-EN
www.littelfuse.com
• © 2013 Littelfuse •
• 1/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
This page intentionally left blank.
www.littelfuse.com
• © 2013 Littelfuse •
• 2/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
TABLE OF CONTENTS
1 INTRODUCTION ............................................................................................................. 7
1.1
1.2
1.3
1.4
1.5
1.6
1.7
Current-Supervised Arc-Flash Protection .................................................................. 7
Definite-Time Overcurrent Protection ........................................................................ 7
Fail-Safe Operation .................................................................................................... 7
Fast-Fault Location .................................................................................................... 7
USB Interface ............................................................................................................. 8
Scalable System ........................................................................................................ 8
Upstream Circuit Breaker Tripping ............................................................................ 8
2 INSTALLATION ............................................................................................................... 9
3 POWER SUPPLY .......................................................................................................... 12
3.1
3.2
3.3
3.4
AC Supply ................................................................................................................ 12
DC Supply ................................................................................................................ 12
Low-Voltage DC Supply ........................................................................................... 13
External 24-V Battery Backup .................................................................................. 13
4. OPTICAL SENSORS .................................................................................................... 14
4.1
PGA-LS10 Photoelectric Point Sensor with Sensor Check ..................................... 15
4.1.1 PGA-LS10 Connection .......................................................................................... 16
4.1.2 PGA-LS10 Installation ........................................................................................... 17
4.2
PGA-LS20, PGA-LS25 and PGA-LS30 Fiber-Optic Sensor with Sensor Check .... 18
4.2.1 Fiber Connection ................................................................................................... 18
4.2.2 Receiver Wiring Connections ................................................................................ 18
4.2.3 Transmitter Wiring Connections ............................................................................ 18
4.2.4 PGA-LS20, PGA-LS25, and PGA-LS30 Connection ............................................ 19
5
5.1
5.2
5.3
SENSOR PLACEMENT ............................................................................................. 20
General Guidelines .................................................................................................. 20
Switchgear Protection .............................................................................................. 20
Transformer Protection ............................................................................................ 20
6 CURRENT SENSORS .................................................................................................. 21
6.1
6.2
6.3
Current Inhibit Mode ................................................................................................ 21
Overcurrent Protection ............................................................................................. 21
Current Sensor Characteristics ................................................................................ 22
7 DIGITAL INPUTS .......................................................................................................... 23
7.1
7.2
7.3
7.4
Inhibit ........................................................................................................................ 23
Trip ........................................................................................................................... 23
Reset ........................................................................................................................ 23
Circuit Check ............................................................................................................ 23
8 OUTPUTS ..................................................................................................................... 24
8.1
8.2
8.3
Online ....................................................................................................................... 24
Service ..................................................................................................................... 24
Tripped ..................................................................................................................... 24
www.littelfuse.com
• © 2013 Littelfuse •
• 3/84
PGR-8800 Arc-Flash Relay
8.4
Rev. 3-A-112913
Trip Coil .................................................................................................................... 25
9 LED INDICATION .......................................................................................................... 26
10 PGR-8800 BUTTONS .................................................................................................. 29
10.1
10.2
10.3
10.4
10.5
Mode ........................................................................................................................ 29
Trip ........................................................................................................................... 29
Reset ........................................................................................................................ 29
Mode + Reset........................................................................................................... 29
Mode + Trip .............................................................................................................. 29
11 LINK ............................................................................................................................. 30
11.1
11.2
11.3
Configuration ............................................................................................................ 30
Button Function ........................................................................................................ 30
Modbus Communication .......................................................................................... 31
12 USB INTERFACE ........................................................................................................ 32
12.1 Connecting to a PC .................................................................................................. 32
12.2 Configuration Software ............................................................................................ 33
12.2.1
Configuration Software Tabs....................................................................... 33
12.2.2
Configuration Software Buttons .................................................................. 34
12.2.3
Default Configuration .................................................................................. 34
12.2.4
General Settings.......................................................................................... 35
12.2.5
Optical-Sensor Settings .............................................................................. 35
12.2.6
Current-Sensor Settings .............................................................................. 37
12.2.7
Digital-Input Settings ................................................................................... 39
12.2.8
Output Settings............................................................................................ 40
12.2.8.1 Trip Coil Output ....................................................................................... 40
12.2.8.2 Coordinated Tripping .............................................................................. 41
12.2.9
Communications Settings ........................................................................... 42
12.2.10 Advanced Settings ...................................................................................... 45
12.2.11 About Tab .................................................................................................... 46
12.3 Data Log Drive ......................................................................................................... 46
13 COMMISSIONING ....................................................................................................... 47
13.1 Configuration of Installed Sensors ........................................................................... 47
13.2 Testing the Sensors ................................................................................................. 47
13.3 Testing the Trip Coil ................................................................................................. 48
13.4 Full Operation Test (Online)..................................................................................... 48
13.5 Light Sensitivity Adjustment ..................................................................................... 49
13.6 Fiber-Optic Sensor Adjustment ................................................................................ 49
13.6.1 Sensor Adjustment for a Fiber Length other than 60 cm (24”) ............................ 49
13.6.2 Sensor Adjustment in Small Compartments ........................................................ 50
14 SPECIFICATIONS ....................................................................................................... 51
14.1
14.2
PGR-8800 ................................................................................................................ 51
Sensors .................................................................................................................... 55
15 ORDERING INFORMATION ....................................................................................... 56
16 WARRANTY ................................................................................................................. 56
www.littelfuse.com
• © 2013 Littelfuse •
• 4/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
APPENDIX A PGR-8800 MODBUS RTU PROTOCOL ..................................................... 57
A.1 Protocol ........................................................................................................................ 57
A.1.1 Configuration Setup ........................................................................................ 57
A.2 Message Synchronization ............................................................................................ 57
A.3 Error Checking.............................................................................................................. 57
A.4 Function Codes Supported........................................................................................... 58
A.4.1 Read Input/Holding Registers (Code 04/03) .................................................. 58
A.4.2 Write to Register ............................................................................................. 58
A.4.2.1 Write Single Register (Code 6) ............................................................... 58
A.4.2.2 Write Multiple Registers (Code 16) ......................................................... 59
A.4.3 Exception Responses ..................................................................................... 59
A.5 PGR-8800 Database .................................................................................................... 59
A.6 Specifications ............................................................................................................... 59
APPENDIX B MODBUS COMMUNICATIONS DATABASE TABLE .................................. 60
APPENDIX C COORDINATED TRIPPING OF UPSTREAM BREAKERS ........................ 66
C.1 System Overview ......................................................................................................... 66
C.1.1 Circuit Breaker Feedback Detection .............................................................. 66
C.1.2 Current Sensor Detection ............................................................................... 66
C.1.3 Total Clearing Time ........................................................................................ 66
C.1.3.1 Arc Detection Delay ................................................................................ 66
C.1.3.2 Circuit Breaker Operating Time .............................................................. 67
C.1.3.3 Output Delay ........................................................................................... 67
C.1.3.4 Total Clearing Time Examples ................................................................ 67
C.1.4 Relay Output .................................................................................................. 67
C.1.5 Link Output ..................................................................................................... 67
C.1.6 PGA-1100 Diode Logic Unit ........................................................................... 68
C.2 Application and Configuration ...................................................................................... 68
C.2.1 Single PGR-8800 Configuration ..................................................................... 68
C.2.2 Dual PGR-8800 Configuration using Link Interface ....................................... 72
C.2.3 Single PGR-8800 Configuration with Current Sensor Input........................... 73
C.2.4 Dual PGR-8800 Configuration using Link Interface and
Current Sensor Input ...................................................................................... 76
C.2.5 Configuration of Multiple Inputs and Outputs ................................................. 78
C.2.6 Tripping Common Upstream Circuit Breaker from Several Zones
using PGA-1100 .............................................................................................. 79
APPENDIX D SYSTEM PARAMETERS AND SETUP RECORD ...................................... 80
APPENDIX E PGR-8800 REVISION HISTORY ................................................................. 84
www.littelfuse.com
• © 2013 Littelfuse •
• 5/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
LIST OF FIGURES
1 PGR-8800 Outline and Mounting Details....................................................................... 9
2 PGR-8800 Typical Wiring Diagram .............................................................................. 10
3 PGR-8800 24-Vdc Source Typical Wiring Diagram..................................................... 11
4 Local Sensor Detection Zone for a 3 kA Fault ............................................................. 14
5 PGA-LS10 Detection Range for a 3 kA Fault .............................................................. 15
6 PGA-LS10 Connection Diagram .................................................................................. 16
7 PGA-LS10 Mounting Detail .......................................................................................... 17
8 PGA-LS20, PGA-LS25, and PGA-LS30 Connection Diagram .................................... 19
9 LED Flash Patterns ...................................................................................................... 26
C.1 Single PGR-8800 Application ........................................................................................ 69
C.2 Dual PGR-8800 Configuration using Link Interface ..................................................... 72
C.3 Single PGR-8800 Configuration with Current Sensor Input ........................................ 74
C.4 Dual PGR-8800 Configuration using Link Interface and
Current Sensor Input ................................................................................................... 76
C.5 Tripping Common Upstream Circuit Breaker from Several Zones
using PGA-1100............................................................................................................ 79
LIST OF TABLES
A.1
A.2
A.3
C.1
Read Registers (Code 04/03) ...................................................................................... 58
Write Single Register (Code 6) .................................................................................... 58
Write Multiple Registers (Code 16) .............................................................................. 59
Circuit Breaker Operating Times.................................................................................. 67
www.littelfuse.com
• © 2013 Littelfuse •
• 6/84
PGR-8800 Arc-Flash Relay
1
Rev. 3-A-112913
INTRODUCTION
The PGR-8800 Arc-Flash Relay is a high-speed, arc-detection device for electrical powerdistribution systems. The PGR-8800 has one local sensor and supports both point and fiber-optic
sensor technologies for optical arc detection. There are inputs for six optical sensors and three
current sensors.
On the occurrence of an arc fault, the PGR-8800 detects the fault and pulses the trip contact in
less than one millisecond. The tripping pulse is typically used to trip the circuit breaker(s) supplying
the circuit. The total arcing time is effectively reduced to the mechanical opening time of the circuit
breaker; typically between 30 and 75 milliseconds. The trip contact is a solid-state switch (IGBT),
which provides fast reaction and sufficient drive capability for circuit-breaker trip circuits.
Using optical sensors rather than relying strictly on current measurement allows a much faster
detection time than overcurrent relays or a circuit breaker alone can typically provide. This will
lower the incident energy of an arc flash and increase worker safety, reduce fault damage, and
improve uptime. Since the incident energy is decreased, the hazard risk category (HRC) and
associated level of personal protective equipment (PPE) may also be lowered, subject to an arcflash study modeling the system parameters.
The MODBUS RTU protocol is implemented in the PGR-8800. This will provide status information
for sensors, analog inputs, digital inputs, digital outputs, and numerous event and error flags. It
also provides the ability to remotely reset the PGR-8800. See Section 11.3 and Appendices A and
B.
The PGR-8800 can be used on any electrical system with any voltage (ac or dc) and can be
powered from either an ac or dc supply, or both. If it is powered from line supply, it can charge a
backup battery to power the PGR-8800 when the line supply is lost.
1.1 Current-Supervised Arc-Flash Protection
The PGR-8800 has three phase-current inputs which can be used to prevent optical trips when the
measured current is below a user-specified level. This makes it possible to avoid nuisance tripping
from external light sources such as lightning or welding arcs.
1.2 Definite-Time Overcurrent Protection
Using the phase-current inputs, the PGR-8800 can be configured to trip on overcurrent, with a
minimum reaction time of one millisecond. There are two user-adjustable levels of overcurrent
protection with independent trip times to coordinate with other protective devices. This provides
protection from long-lasting overload conditions and fast reaction to overcurrent even when no arc
is detected.
1.3 Fail-Safe Operation
The PGR-8800 continuously monitors its internal circuitry as well as the connected optical sensors.
Any system faults, including a sensor-cable fault, are indicated by a flashing LED and can be
logged. A redundant trip circuit ensures that the PGR-8800 will trip on an arc flash even if a
primary trip-circuit component fails. The solid-state design of the redundant trip circuit also
provides a significantly faster response to an arc on power-up (for example, after maintenance
during a shutdown) than is possible with microprocessor-only relays.
1.4 Fast-Fault Location
The optical sensors used with the PGR-8800 include LED indication of health and, if it has
detected an arc flash, of fault location. The PGR-8800 also has one LED per optical sensor to
indicate which sensor(s) have caused a trip.
www.littelfuse.com
• © 2013 Littelfuse •
• 7/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
1.5 USB Interface
A USB interface on the front of the PGR-8800 provides easy PC access to configuration settings
and access to an event log which provides detailed diagnostic information about measurements
before and after a trip. No PC driver or software installation is required.
1.6 Scalable System
Up to four PGR-8800 modules can be connected into a single system, allowing a total of 24 optical
sensors per system.
1.7 Upstream Circuit Breaker Tripping
The PGR-8800 can be configured to trip an upstream circuit breaker as a backup to local circuitbreaker failure. Circuit-breaker failure can be detected with a discrete input (such as a local circuit
breaker feedback signal), current measurement, or the Link function. See Appendix C for more
information.
www.littelfuse.com
• © 2013 Littelfuse •
• 8/84
PGR-8800 Arc-Flash Relay
2
Rev. 3-A-112913
INSTALLATION
The PGR-8800 can be surface mounted using four 5-mm (10-32) screws, or it can be DIN-rail
mounted using the optional mounting brackets (PGA-0031).
Ensure there is enough clearance around the module to allow the plug-in terminals to be removed
and inserted.
Do not install modules which have been damaged in transport.
See the PGR-8800 Arc-Flash Relay Application Guide for additional installation information.
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MINIMUM CLEARANCE REQUIRED FOR CONNECTOR
INSERTION AND REMOVAL.
3. CERTIFICATIONS NOT SHOWN.
ARC-FLASH RELAY
SIDE
(0.79)
20.0
(0.79)
10.0
(0.39)
200.0
(7.88)
160.0
(6.30)
20.0
4 OPEN SLOTS
5.6 X 6.8 (0.22 x 0.27)
PGR-8800 SERIES
FRONT
4.0
(0.16)
20.0
(0.79)
122.2
(4.81)
130.2
(5.13)
200.0
(7.88)
160.0
(6.30)
20.0
(0.79)
4.0
(0.16)
54.3
(2.14)
38.8
(1.53)
TOP
NOTE 2
(0.39)
10.0
130.0
(5.13)
5.0
(0.20)
6.0
(0.24)
NOTE 2
BOTTOM
MOUNTING DETAIL
FIGURE 1. PGR-8800 Outline and Mounting Details.
www.littelfuse.com
• © 2013 Littelfuse •
• 9/84
PGR-8800 Arc-Flash Relay
LINK OR MODBUS CONNECTION (OPTIONAL)
+
UP TO 4
PGR-8800 MODULES
CAN BE CONNECTED. SEE
SECTION 11.
-
ALARM
ONLINE
R
OPTIONAL
24 VDC BATTERY
SEE SECTION 3
G
Rev. 3-A-112913
R
A B C
TRIP
TRIP
COIL
RESET
ARC-FLASH RELAY
PGR-8800 SERIES
PGA-LS10
POINT SENSOR
WHITE
SHIELD / BLACK
RED
YELLOW
SHIELD / BLACK
RED
NOTE 3
WHITE
SHIELD / BLACK
YELLOW
RED
WHITE
NOTE 4
OPTIONAL
5-A-SECONDARY
PHASE CT’S
PGA-LS20 / PGA-LS25/ PGA-LS30
FIBER OPTIC SENSOR
NOTES:
1. RELAY OUTPUTS SHOWN DE-ENERGIZED.
2. CURRENT SENSOR INPUTS MUST BE CONFIGURED. SEE SECTION 12.
3. A TOTAL OF SIX POINT OR FIBER-OPTIC SENSORS CAN BE CONNECTED.
4. USB ‘B’ CONNECTOR. FOR CONFIGURATION, SEE SECTION 12.
FIGURE 2. PGR-8800 Typical Wiring Diagram.
www.littelfuse.com
• © 2013 Littelfuse •
• 10/84
PGR-8800 Arc-Flash Relay
LINK OR MODBUS CONNECTION (OPTIONAL)
+
Rev. 3-A-112913
UP TO 4
PGR-8800 MODULES
CAN BE CONNECTED. SEE
A B C
SECTION 11.
-
+24 VDC
0V
ALARM
ONLINE
R
G
TRIP
R
TRIP
COIL
RESET
ARC-FLASH RELAY
PGR-8800 SERIES
PGA-LS10
POINT SENSOR
WHITE
SHIELD / BLACK
RED
YELLOW
SHIELD / BLACK
RED
NOTE 3
WHITE
SHIELD / BLACK
YELLOW
RED
WHITE
NOTE 4
OPTIONAL
5-A-SECONDARY
PHASE CT’S
PGA-LS20 / PGA-LS25 / PGA-LS30
FIBER OPTIC SENSOR
NOTES:
1. RELAY OUTPUTS SHOWN DE-ENERGIZED.
2. CURRENT SENSOR INPUTS MUST BE CONFIGURED. SEE SECTION 12.
3. A TOTAL OF SIX POINT OR FIBER-OPTIC SENSORS CAN BE CONNECTED.
4. USB ‘B’ CONNECTOR. FOR CONFIGURATION, SEE SECTION 12.
FIGURE 3. PGR-8800 24-Vdc Source Typical Wiring Diagram.
www.littelfuse.com
• © 2013 Littelfuse •
• 11/84
PGR-8800 Arc-Flash Relay
3
Rev. 3-A-112913
POWER SUPPLY
The PGR-8800 Arc-Flash Relay can be supplied by a single ac or a single dc source – not both.
3.1 AC Supply
Connect an ac supply to terminals 31 and 32. The supply voltage must be 100 to 240 Vac.
100-240 VAC
N
L
31
L2/
N
32
L1
GND
33
LINE
3.2 DC Supply
Connect a dc supply to terminals 31 and 32, ensuring correct polarity. The supply voltage must be
110 to 250 Vdc.
110-250 VDC
-
31
L2/
N
+
32
L1
GND
33
LINE
www.littelfuse.com
• © 2013 Littelfuse •
• 12/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
3.3 Low-Voltage DC Supply
Connect a dc supply to terminals 34 and 36, ensuring correct polarity. The supply voltage must be
14 to 48 Vdc. This input will not charge the backup battery.
14-48 VDC
+
34
+
V
-
35
B
A
T
36
0
V
POWER
3.4 External 24-V Battery Backup
Connect a 24-Vdc battery to terminals 35 and 36, ensuring correct polarity. The PGR-8800 will
only charge the battery when there is rated voltage on power-supply terminals 31 and 32 (ac or
dc). The PGR-8800 supplies a constant-current, constant-voltage (CCCV) of 27 V with no load and
maximum available current of 200 mA. A sealed lead-acid battery with a capacity between 2 and
15 Ah, such as a pair of Panasonic VRLA LC-R122R2P, should be used and exchanged regularly
according to the manufacturer’s recommendations.
If the PGR-8800 is supplied by the backup battery and the battery voltage drops below 20 V, the
PGR-8800 will shut down to protect the battery.
Do not combine external battery backup and the low-voltage DC supply. The DC supply will not
charge the battery.
NOTE: Arc monitoring is disabled when the PGR-8800 is powered down.
24 VDC
BATTERY
34
+
V
+
-
35
B
A
T
36
0
V
POWER
www.littelfuse.com
• © 2013 Littelfuse •
• 13/84
PGR-8800 Arc-Flash Relay
4
Rev. 3-A-112913
OPTICAL SENSORS
The PGR-8800 has one local sensor and six inputs for external optical sensors. The local sensor
is primarily used for commissioning and can also be enabled for arc-flash protection. Its lightdetection zone is illustrated in the diagram below.
1m
(3.3 ft)
ARC-FL
ARC-FLASH
RELAY
PGR-8800 SERIES
2m
(6.6 ft)
150°
70°
FIGURE 4. Local Sensor Detection Zone for a 3 kA Fault.
Two external sensor types are supported:

PGA-LS10 Photoelectric Point Sensors with sensor check

PGA-LS20, PGA-LS25, and PGA-LS30 Fiber-Optic Sensors with sensor check
The sensors can be used together, in any combination.
Both sensor types have LED indication of sensor health and fault location. A sensor-check circuit
tests the sensor to verify that the sensor assembly is functioning correctly. A healthy sensor will
indicate two fast flashes of its internal red LED every few seconds. A sensor that has detected an
arc will slowly flash red.
The sensors connect to the PGR-8800 with shielded three-wire 20 AWG (0.5 mm2) electrical cable.
Each sensor includes 10 m (33 ft) of cable which can be shortened or extended up to 50 m
(164 ft). These cables should be considered to be at ground potential when determining electrical
clearances in the cabinet.
Any connected optical sensor with circuit check will be automatically detected and cause the
PGR-8800 to report an error if it is subsequently disconnected.
PGA-LS10
PGA-LS20 / PGA-LS25 / PGA-LS30
www.littelfuse.com
• © 2013 Littelfuse •
• 14/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
4.1 PGA-LS10 Photoelectric Point Sensor with Sensor Check
This sensor has a detection area of a 2-m (7 ft) half-sphere for arcs of 3 kA or more.
A built-in LED enables the PGR-8800 to verify the function of the light sensor, wiring, and
electronics. If the sensor does not detect the sensor-check LED, a sensor-fail alarm will occur -the ONLINE output will change state and the ONLINE LED will begin to short flash. See Section 9.
The sensor includes 10 m (33 ft) of shielded three-wire electrical cable which can easily be
shortened or extended to a maximum of 50 m (164 ft). Use Belden 85240 or equivalent cable (wire
colors may vary).
2.5 m (8.2 ft)
3 kA
2 m (6.6 ft)
2 m (6.6 ft)
PGA-LS10
2 m (6.6 ft)
2 m (6.6 ft)
FIGURE 5. PGA-LS10 Detection Range for a 3 kA Fault.
www.littelfuse.com
• © 2013 Littelfuse •
• 15/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
4.1.1 PGA-LS10 Connection
9.6
(0.38)
8.3
(0.33)
14.2
(0.56)
ARC-FLASH RELAY
2.4
(0.09)
23.8
SHIELD / BLACK
YELLOW
RED
Ø4.25(0.167)
MOUNTING HOLES
WHITE
SHIELD / BLACK
YELLOW
RED
10 m
(32.8 ft)
WHITE
(0.94)
NOTE 2
52.0
(2.05)
44.0
(1.73)
Ø8.3(0.33)
SENSOR LENS
4.0
(0.16)
RED LED FOR
CIRCUIT CHECK AND
VISUAL DIAGNOSTICS
24.0
(0.94)
32.0
(1.26)
NOTES
1. DIMENSIONS IN MILLIMETERS (INCHES) UNLESS OTHERWISE STATED.
2. UP TO 6 PGA-LS10 PHOTOELECTRIC POINT SENSORS WITH BUILT-IN
CIRCUIT CHECK CAN BE CONNECTED.
3. THE PGA-LS10 SENSOR SHIPS ASSEMBLED WITH A PLUG-IN CONNECTOR.
IT MAY BE NECESSARY TO DISCONNECT THE PLUG-IN CONNECTOR
DURING INSTALLATION.
TERMINAL
FUNCTION
COLOR
5V
SUPPLY
RED
TX
CIRCUIT CHECK TRANSMIT
WHITE
RX
RECEIVE
YELLOW
SHIELD
BLACK/COPPER
0V
FIGURE 6. PGA-LS10 Connection Diagram.
www.littelfuse.com
• © 2013 Littelfuse •
• 16/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
4.1.2 PGA-LS10 Installation
Point sensors include an adhesive-backed drill template for easy surface or panel-mount
installation.
PANEL
SURFACE
NOTE 3
PANEL
Ø9(0.354)
PGA-LS10
DRILL TEMPLATE
SURFACE
PANEL
SURFACE
Ø9(0.354)
DRILL TEMPLATE
SURFACE-MOUNTED
PGA-LS10
PANEL-MOUNTED
PGA-LS10
NOTES AND INSTALLATION:
1. ALL DIMENSIONS IN MILLIMETERS (INCHES).
2. AFFIX THE DRILL TEMPLATE WHERE THE SENSOR IS TO BE
MOUNTED.
3. MOUNTING SCREWS ARE M4 OR 8-32.
4. THE PGA-LS10 CAN BE SURFACE OR PANEL MOUNTED. SELECT
THE APPROPRIATE HOLES AND DRILL THROUGH THE TEMPLATE.
FIGURE 7. PGA-LS10 Mounting Detail.
www.littelfuse.com
• © 2013 Littelfuse •
• 17/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
4.2 PGA-LS20, PGA-LS25 and PGA-LS30 Fiber-Optic Sensors with Sensor Check
The PGA-LS20, PGA-LS25, and PGA-LS30 have a 360° detection zone along the fiber’s length. A
built-in LED enables the PGR-8800 to verify the function of the light sensor, wiring, and electronics.
If the sensor does not detect the sensor-check LED, a sensor-fail alarm will occur -- the ONLINE
output will change state and the ONLINE LED will begin to short flash. See Section 9.
The PGA-LS20, PGA-LS25, and PGA-LS30 sensor have three components:
1. A fiber-optic cable, with one end covered with a black sleeve. The PGA-LS20 has 8 m
(26 ft) of active fiber and 2 m (7 ft) of covered fiber. The PGA-LS25 has 5 m (16 ft) of active
fiber and 3 m (10 ft) of covered fiber. The PGA-LS30 has 18 m (59 ft) of active fiber and
2 m (7 ft) of covered fiber.
2. A transmitter with a white enclosure and a white thumb nut.
3. A receiver with a white enclosure, a black thumb nut, and an adjustment screw behind an
access hole.
Both the receiver and the transmitter connect to one PGR-8800 input using shielded three-wire
electrical cable. All three components are monitored to ensure correct operation.
4.2.1 Fiber Connection
The fiber is the light-collecting element of the PGA-LS20, PGA-LS25, and PGA-LS30. It must be
installed so it has line-of-sight to all current-carrying parts. In some cases this may be
accomplished by following the bus bars along the back wall of the cabinets.
Drill holes using the included drill template and fasten the transmitter and receiver to the cabinet
walls using rivets or screws. Connect the attached cables to the PGR-8800. The wires of the
transmitter and receiver must be connected as shown in Fig. 8.
Connect the black-sleeve-covered end to the receiver using the black thumb nut, and the white
uncovered end to the transmitter using the white thumb nut. Ensure the fiber is inserted
completely into the transmitter and receiver and the nuts are tightened. Pull gently on the cable to
verify a secure connection. The maximum pull strength of the fiber is 30 N (6.7 lbf).
The fiber should not be sharply bent or pinched. The minimum bending radius is 5 cm (2”).
Ensure that any drilled holes are free of any sharp edges or burrs. Use grommets for further
protection.
4.2.2 Receiver Wiring Connections
Connect the red wire to 5V.
Connect the yellow wire to RX.
Connect the white wire and the shield to 0V.
4.2.3 Transmitter Wiring Connections
Connect the red wire to 5V.
Connect the white wire to TX.
Connect the shield to 0V.
The yellow wire is not used.
www.littelfuse.com
• © 2013 Littelfuse •
• 18/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
4.2.4 PGA-LS20, PGA-LS25, and PGA-LS30 Connection
The sensor is shipped with the wires mounted in a terminal block. See Fig 8.
The transmitter and receiver include 10 m (33 ft) of shielded three-wire electrical cable which can
be shortened or extended up to 50 m (164 ft). Transmitter and receiver cables can be different
lengths and must be independently shielded. Use Belden 85240 or equivalent cable (wire colors
may vary). Failure to independently shield transmitter and receiver cables can lead to an incorrect
circuit check – a faulty sensor could be falsely detected as continuous. However, if there is no
sensor fault, arc-flash detection will function normally in this condition.
SHIELD / BLACK
YELLOW
RED
WHITE
SHIELD / BLACK
RED
WHITE
46.0
(1.81)
2.0
(0.08)
18.8
(0.74)
24.0
(0.94)
4.0
(0.16)
Ø4.25(0.167)
MOUNTING HOLES
BLACK SLEEVE
(PGA-LS20: 2 m, 6.5 ft)
(PGA-LS25: 3 m, 9.8 ft)
(PGA-LS30: 2 m, 6.5 ft)
RECEIVER
SENSITIVITY
ADJUSTMENT
SCREW
42.0
(1.65)
FIBER
(PGA-LS20: 8 m, 26.2 ft)
(PGA-LS25: 5 m, 16.4 ft)
(PGA-LS30: 18 m, 59 ft)
46.0
(1.81)
4.0
(0.16)
DECREASE
SENSITIVITY
NOTES
1. DIMENSIONS IN MILLIMETERS (INCHES) UNLESS OTHERWISE
STATED.
2. UP TO 6 PGA-LS20 / PGA-LS25 / PGA-LS30 FIBER-OPTIC SENSORS
WITH BUILT-IN CIRCUIT CHECK CAN BE CONNECTED.
THUMB NUT
32.0
(1.26)
3. THE PGA-LS20, PGA-LS25, AND PGA-LS30 SENSORS SHIP
ASSEMBLED WITH A PLUG-IN CONNECTOR. IT MAY BE NECESSARY
TO DISCONNECT THE PLUG-IN CONNECTOR DURING INSTALLATION.
TERMINAL
FUNCTION
COLOR
5V
SUPPLY (TRANSMITTER AND
RECEIVER)
RED
TX
SENSOR CHECK (TRANSMITTER)
WHITE
RX
SIGNAL (RECEIVER)
YELLOW
SENSOR CHECK (RECEIVER) AND
BOTH SHIELDS
BLACK/COPPER
0V
FIGURE 8. PGA-LS20, PGA-LS25, and PGA-LS30 Connection Diagram.
www.littelfuse.com
• © 2013 Littelfuse •
• 19/84
PGR-8800 Arc-Flash Relay
5
Rev. 3-A-112913
SENSOR PLACEMENT
5.1 General Guidelines
Optical sensors require line-of-sight to points being monitored. Ensure that the point sensors and
fiber are not blocked by fixed or moveable objects. Areas that will be accessed for maintenance or
with moveable parts (such as draw-out circuit breakers) should be considered a high priority for
installation. Do not place sensors or cables on bare components that will be energized and avoid
sharp bends in the cable, particularly when using the PGA-LS20, PGA-LS25, and PGA-LS30 fiberoptic sensors. The electrical cables and sensors should be considered to be at ground potential
when determining electrical clearances.
Sensors should be mounted in a location that will minimize the chance of debris or dust build-up
and with easy access for maintenance if needed. A point sensor mounted at the top of an
enclosure and facing down is optimal for reducing dust build-up. It should be noted that most
enclosures are metallic and the reflectivity combined with the high intensity of an arc mean that
even a dirty sensor will collect adequate light.
Sensors can be tested individually by putting the PGR-8800 into service mode by pressing the
MODE button and shining a bright light on the sensor. A trip will be indicated if the sensor detects
the light, but a trip signal will not be sent to the circuit breaker. If the LED on the sensor or relay
isn’t indicating a trip, cleaning is necessary. Note that in service mode, the PGR-8800 will not trip if
an arc flash occurs. Remember to return the PGR-8800 to online mode after testing is completed.
In dusty environments, sensor cleaning should be part of a regular maintenance schedule and can
be performed using compressed air or a dry cloth.
5.2 Switchgear Protection
The sensors used for arc-flash detection are optical sensors. Line-of-sight between the points
where an arc could occur and the sensor is crucial.
Often one point sensor is sufficient to monitor a complete switchgear compartment. However, if
there are large components such as circuit breakers that cast shadows over wider areas, more
than one point sensor is required.
SENSOR 5
SENSOR 4
DE
VI
N CE
SH OT S
OW
N
FIB
ER
S
A- ENS
LS
OR
20
PG
PGA-LS10
G
PGA-LS10
IN
POINT SENSOR
CO
M
DE
VI
N CE
SH OT S
OW
N
POINT SENSOR
IN
POINT SENSOR
DE
VI
N CE
SH OT S
OW
N
MA
EA IN
KE
R
BR
POINT SENSOR
IP
TR
PGA-LS10
PGR-8800 SERIES
PGA-LS10
(C
ARC-FLASH RELAY
T
EN
RR S
CU SOR T3)
N
SE T2,C
,C
T1
SENSOR 3
SENSOR 2
SENSOR 1
5.3 Transformer Protection
The PGR-8800 can also be used for the protection of transformers. Two or more point sensors
should be used per transformer to monitor the primary and secondary connection terminals. For
the placement of the sensors, the same considerations apply as for switchgear protection.
www.littelfuse.com
• © 2013 Littelfuse •
• 20/84
PGR-8800 Arc-Flash Relay
6
Rev. 3-A-112913
CURRENT SENSORS
The PGR-8800 has three phase-current inputs which can be configured in a current-supervised trip
inhibit mode and for overcurrent protection.
The current inhibit mode prevents the module from tripping on a light signal, unless the current is
above a threshold. This can prevent nuisance tripping e.g. photo flashes or welding in the area.
The overcurrent protection provides a fast, but less accurate ANSI 50 overcurrent protection
function.
The current-sensor inputs can also be used to verify that the local circuit breaker has tripped
successfully, providing an ANSI 50BF circuit breaker failure function. See Appendix C for more
information.
6.1 Current Inhibit Mode
If the current-supervised trip inhibit mode is enabled, the PGR-8800 will only trip when the
following conditions apply:
-
An arc is detected by an optical sensor, and
-
Current detected by a current sensor exceeds the inhibit threshold.
The PGR-8800 will trip after the programmed delay time for the light as soon as the absolute value
of the current on any phase exceeds the inhibit setting. Thus, the current inhibit does not add any
delay to the trip if the arc is drawing current.
6.2 Overcurrent Protection
In addition, two definite-time overcurrent protection levels are provided that will trip on current
detection alone. Overcurrent levels can be set from 150 to 1,000% of rated nominal load current.
Overcurrent protection is not active by default, and must be set using the configuration software.
Overcurrent trip times can be set between 1 and 20,000 milliseconds. The trip decision is based on
an internal counter. The PGR-8800 will increment the counter if a sample exceeds the trip-level
setting and decrement it when a sample is below the setting. When the counter exceeds the
number of samples necessary to exceed the time delay, the PGR-8800 will trip. The time for the
trip coil IGBT (insulated-gate bipolar transistor) to operate is approximately 0.2 milliseconds, which
happens after the time delay.
NOTE: Using overcurrent trip on a system with fewer than three phase current sensors can
significantly increase trip times and levels. This does not apply to the inhibit system, which will
function at no added delay, also in single phase systems.
www.littelfuse.com
• © 2013 Littelfuse •
• 21/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
6.3 Current Sensor Characteristics
The current-sensor inputs require 5-A-secondary current sensors. Three phase-current sensors
are required for optimal performance. For best performance, select current sensors with a primary
rating approximately equal to the system’s rated current and protection class 10P5 or better. The
current sensors can be placed in series with other equipment as long as the total burden of the
wiring and inputs are within the current sensor rating.
The PGR-8800 measures instantaneous currents and is insensitive to phasing and polarity. The
current-sensor inputs have a burden of less than 0.25 VA at 5 A, will withstand up to 75 A for one
second, and are isolated from all other terminals up to 500 Vac.
ØA
ØB
ØC
5A SECONDARY CT’S REQUIRED
OPTIONAL 3-PHASE
OVERCURRENT PROTECTION
www.littelfuse.com
• © 2013 Littelfuse •
• 22/84
PGR-8800 Arc-Flash Relay
7
Rev. 3-A-112913
DIGITAL INPUTS
The PGR-8800 has three digital-input functions; trip inhibit, trip and reset. Each function has two
inputs to simplify wiring.
By default, the inputs are considered active when connected to COM (terminal 45). The inputs can
also be configured to be active when not connected to terminal 45 and to use circuit check in the
configuration software. See Section 12.2.7.
7.1 Inhibit
The INHIBIT function suppresses a trip signal.
There are two INHIBIT inputs: terminals 39 and 40.
RESET
TRIP
RESET
TRIP
INHIBIT
Inhibit can also block a digital-input if so configured. See
Section 12.2.7. The INHIBIT input is enabled by default.
INHIBIT
When inhibit is activated, the PGR-8800 will indicate that an arc fault is being detected, but will not
pulse the trip-coil output. If the PGR-8800 detects an arc fault while inhibited, the sensor LED and
INHIBIT LED will flash.
7.2 Trip
The TRIP input is used to remotely trip the PGR-8800. Once
activated, the PGR-8800 will pulse the TRIP COIL output
instantaneously.
There are two TRIP inputs: terminals 41 and 42.
In SERVICE mode, this input does not affect the TRIP COIL
output.
The TRIP input can also be configured to connect to the auxiliary
contact of a circuit breaker to verify that the circuit breaker has
tripped successfully. See Appendix C.
The TRIP input is enabled by default.
7.3 Reset
The RESET input is used as a remote reset after a fault has been detected.
There are two RESET inputs: terminals 43 and 44.
Activating this input will reset an alarm or error, clear the TRIPPED and TRIP COIL outputs, clear
the indicators, and place the unit back in service or online mode, depending on the mode it was
operating in prior to the trip.
If the reset input is permanently connected to COM, the
PGR-8800 will auto reset after a trip has occurred. The reset
input is enabled by default.
CABLE-MONITORING
82 kΩ RESISTOR
TO TERMINAL 45,
COM
7.4 Circuit Check
A circuit-check feature can be enabled for each digital input in
the configuration software. This feature will cause the module
to report an error if the connection to the digital input is open
or broken. Circuit check requires an 82 kΩ resistor connected
in parallel with the external contact. This resistor must be
connected as close as possible to the contact to ensure the
full-length of the cable is protected.
www.littelfuse.com
• © 2013 Littelfuse •
• 23/84
PGR-8800 Arc-Flash Relay
8
Rev. 3-A-112913
OUTPUTS
An LED provides visual indication of each output
status. The output contacts are shown on the
faceplate in the powered-off state.
8.1 Online
The ONLINE output consists of two contact sets:
-
A change-over (Form C) contact (terminals 46-48)
-
A normally-open status contact, STO (terminal 49) with reference to COM (terminal 45)
The ONLINE output is energized unless the PGR-8800:
-
detects an optical sensor fault,
-
detects a cable fault on a digital input if cable monitoring is activated in the configuration
software,
-
detects loss of trip coil supply voltage,
-
loses supply voltage, or
-
is in service mode
8.2 Service
The SERVICE output consists of two contact sets:
-
A change-over (Form C) contact (terminals 50-52)
-
A normally-open status contact STS (terminal 53) with reference to COM (terminal 45)
The SERVICE output signals that the PGR-8800 is being commissioned or set up. The output is
energized when the PGR-8800:
-
is in service mode, or
-
is connected via USB to a PC
The SERVICE output can also be configured to trip an upstream device after a local circuit-breaker
failure or to follow the Trip Coil output. See Appendix C.
8.3 Tripped
The TRIPPED output consists of two contact sets:
-
A change-over (Form C) contact (terminals 54-56)
-
A normally-open status contact STT (terminal 57) with reference to COM (terminal 45)
NOTE: The TRIPPED output is used for signalling a trip condition to a remote monitoring system
or to trip an upstream circuit breaker. It is not intended to trip the local circuit breaker due to the
slower response time of a mechanical relay.
In default configuration, the TRIPPED output will energize if the PGR-8800 detects a fault during
regular operation or in service mode.
The TRIPPED output can also be configured to trip an upstream device (with a delay of
approximately five milliseconds) after a local circuit-breaker failure, or to follow the TRIP COIL
output. See Appendix C.
www.littelfuse.com
• © 2013 Littelfuse •
• 24/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
8.4 Trip Coil
Use the TRIP COIL output to trip a shunt or undervoltage circuit breaker. The operating mode is
programmable using the PGR-8800 configuration software. See Section 12.2.8.
The TRIP COIL output can be used for trip coils with a 24 to 300 Vac/Vdc supply voltage. The
output is monitored to verify that there is voltage available to the tripping circuit. If voltage is not
detected, the ONLINE output will change state and its LED will flash green.
The TRIP COIL output is a pulsed output when in shunt trip mode. When an arc flash is detected,
the TRIP COIL output is activated in less than one millisecond. When overcurrent protection is
enabled and an overcurrent is detected, the TRIP COIL output is activated after an adjustable
delay. The TRIP COIL output is deactivated after the adjustable pulse period delay. The output is
an IGBT that can carry 10 A ac or dc for five seconds.
The TRIP COIL output is isolated up to 1,000 Vac.
NOTE: The TRIP COIL output is an IGBT switch. There is a voltage drop of 2-4 V across the
TRIP COIL output when energized. See Section 14.
The TRIP COIL output consists of a rectifier bridge and an IGBT. The IGBT is able to switch large
currents and high voltages. In combination, this creates a very fast relay-like switch which is able
to trip even large circuit breakers without the added delay of a mechanical relay.
NOTE: The TRIP COIL output functions as a momentary switch and is protected against thermal
overload. It will gradually lower the time the trip coil is active if the PGR-8800 is tripped repeatedly.
By default, when the PGR-8800 is in service mode, the TRIP COIL output will not operate when an
arc-flash or overcurrent trip occurs, but it will operate when the TRIP button is pressed for at least
one second. The TRIP COIL output can also be programmed to trip while in service mode using
the configuration software.
0A
0B
0C
TRIP VOLTAGE
24-300 VAC / VDC
www.littelfuse.com
• © 2013 Littelfuse •
• 25/84
PGR-8800 Arc-Flash Relay
9
Rev. 3-A-112913
LED INDICATION
FAST FLASHING
LINE
On, green
Supply voltage is connected
ON
Off
Supply voltage is not connected
OFF
100 ms
200 ms
1s
POWER
On, green
PGR-8800 is running from a
supply other than battery
Slow green flashing PGR-8800 is running from the
Battery input. The PGR-8800
will shut down at 20 V to protect
the battery from damage
SLOW FLASHING
ON
OFF
800 ms
1200 ms
SHORT FLASHING
Short green flashing PGR-8800 is charging a battery
ON
Off
OFF
PGR-8800 is not powered
400 ms
1500 ms
100 ms
1600 ms
2s
FIGURE 9. LED Flash Patterns.
LINK
On, green
Link mode is enabled and active
Green flashing
(intermittent)
Network traffic indication
Slow red flashing
A relay in the system is tripping. If the trip is locally inhibited, the Link LED
will revert to green when the trip source is removed
Short red flashing
Link mode is enabled but not all relays are being detected
Off
Link mode is disabled
INHIBIT
On, red
INHIBIT input is active or current sensing is inhibiting trips (current not above
setting)
Fast red flashing
The PGR-8800 detects an arc (light), but the INHIBIT input or current
sensing is preventing a trip
Short red flashing
Digital-input circuit check failed; check the wiring of the inputs, or use the
configuration software to disable circuit check
Off
INHIBIT input is inactive
TRIP
On, red
TRIP input or another trip source is active
Fast red flashing
TRIP input is causing a trip
Slow red flashing
Last trip was caused by this input or by the TRIP button on the front panel.
Press RESET in Online mode to clear the trip
Short red flashing
Digital-input circuit check failed; check the wiring of the inputs, or use the
configuration software to disable circuit check
Off
TRIP input is inactive
www.littelfuse.com
• © 2013 Littelfuse •
• 26/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
RESET
On, red
RESET input or another reset source is active
Short red flashing
Digital-input circuit check failed; check the wiring of the inputs, or use the
configuration software to disable circuit check
Off
RESET input is inactive
ONLINE
On, green
PGR-8800 is online, active and operational; the TRIP COIL output will pulse
if trip conditions are met
Short green flashing PGR-8800 has detected an error. The front-panel LED’s will provide error
information. The TRIP COIL output will still operate if trip conditions are met
Off
PGR-8800 is off or in service mode
SERVICE
On, red
PGR-8800 is in service mode. Please note it will switch to and stay in service
mode if a USB cable and PC are connected. In service mode, the
TRIP COIL output can be activated from the front-panel TRIP button but not
by an arc fault, overcurrent, or TRIP input, unless configured to trip in service
mode. See Section 12.2.8.
Press and hold RESET to configure the sensors. See Section 13.1.
Short red flashing
PGR-8800 is in service mode, and has detected an error. The front-panel
LED’s will provide error information
Slow red flashing
PGR-8800 is in the process of auto set up or firmware update
Off
PGR-8800 is off or in online mode
TRIPPED
On, red
The TRIP COIL output is or has been active or was prevented from
activating while in service mode. Press RESET to clear the trip
Off
No unacknowledged trips
TRIP COIL
On, green
TRIP COIL output is ready and detects trip voltage of 5 V or more in shunt
mode
Fast red flashing
TRIP COIL output is activated due to an existing trip event and is currently
pulsing the output
Slow red flashing
TRIP COIL output has been activated and has completed the pulsed output.
Press RESET to clear the trip
Short red flashing
TRIP COIL output is blocking less than 5 V. The trip voltage is missing;
check the wiring and the power supply to the trip coil
www.littelfuse.com
• © 2013 Littelfuse •
• 27/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
LOCAL
On, green
Online mode. The front-panel sensor is configured for use as a trip sensor
The LED may also indicate that the PGR-8800 is powering up if it is the only
lit LED. If this condition remains for an extended period, it indicates unit
error
Slow green flashing If the SERVICE LED is also flashing, the PGR-8800 is awaiting manual
confirmation of the connected sensors. See Section 13.1
Fast green flashing
The internal supervisor or a USB host is reading or writing to internal
memory, or the light detected on the front sensor is close to trip level
SENSORS
On, green
SENSOR input is active and has a connected sensor
Fast green flashing
Sensor is currently detecting more than 50% of the light level needed to trip.
The level at which this occurs is programmable. This is a warning only. If
this warning is active during normal condition, it may indicate that the system
Trip Level is set too low, which could lead to unintentional tripping
Slow red flashing
Sensor caused a trip event. Press RESET to clear the trip
Short red flashing
Sensor check of the sensor failed; check the wiring and, if using a PGALS20, PGA-LS25, or PGA-LS30 ensure the small metal adjustment screw is
not set to minimum sensitivity. See Section 13.
Off
SENSOR input is inactive
CURRENT SENSORS
On, green
Current sensors are activated and configured
On, red
Current is above the inhibit level
Fast green flashing
Current sensors are detecting more than 50% of the current level needed to
trip. The level at which this occurs is programmable. This is a warning only.
If this warning is active during normal condition, it may indicate that the
system Trip Level is set too low, which could lead to unintentional tripping
Fast red flashing
Current sensor is causing a trip event
Slow red flashing
The PGR-8800 has tripped on overcurrent. Press RESET in online mode to
clear the trip
Off
Current sensors are inactive
PGA LS10, PGA-LS20, PGA-LS25, PGA-LS30
Short red flashing
Sensor is operating normally. Double flashes occur every few seconds.
Slow red flashing
Sensor has detected an arc
Off
Sensor inactive
www.littelfuse.com
• © 2013 Littelfuse •
• 28/84
PGR-8800 Arc-Flash Relay
10
Rev. 3-A-112913
PGR-8800 BUTTONS
10.1 Mode
The MODE button switches the PGR-8800 between online and service mode.
10.2 Trip
In service mode, when the TRIP button is pressed for more than one second, the TRIP COIL
output is activated. In online mode, the TRIP button is disabled.
10.3 Reset
In online mode, press the RESET button to clear a trip (if trip conditions are no longer present). In
service mode, when the RESET button is pressed for more than one second, the optical sensor
detection process will begin. See Section 13.1.
10.4 Mode + Reset
When MODE and RESET are pressed for more than 20 seconds, a file system reset will occur.
This will erase the logged information.
10.5 Mode + Trip
When MODE and TRIP are pressed for more than 20 seconds, a reset of all configuration settings
to factory defaults will occur. This will not clear the logged information on the file system.
www.littelfuse.com
• © 2013 Littelfuse •
• 29/84
PGR-8800 Arc-Flash Relay
11
Rev. 3-A-112913
LINK
The PGR-8800 Link function allows up to four PGR-8800 modules to be connected to form a single
system. This enables the PGR-8800 to share sensor inputs and relay outputs as if they were one
unit. The maximum link cable length is 10 m (33 ft).
It is necessary to configure the Link function before use. See Section 12.2.9.
11.1 Configuration
Set the Link interface, address, and number of connected modules with the configuration software.
Each PGR-8800 must have a unique link address, starting from one for the module connected to
the local circuit breaker.
The PGR-8800 Link function continuously monitors link-cable-break faults.
11.2 Button Function
When a PGR-8800 is configured for the Link function, the front buttons can be shared with all
modules in the system or set to apply only to the local module. For example, if one PGR-8800 is
set to service mode and Link user interface is enabled, all the linked modules will be placed in
service mode. This also applies to the RESET button.
The TRIP button is only applied locally. If the TRIP button is pressed in service mode, only the
local module will trip.
ARC-FLASH RELAY
ARC-FLASH RELAY
ARC-FLASH RELAY
ARC-FLASH RELAY
PGR-8800 SERIES
PGR-8800 SERIES
PGR-8800 SERIES
PGR-8800 SERIES
When connecting modules using the Link interface, connect terminals 37 and 38 as shown using
Belden 3105A cable, or equivalent.
www.littelfuse.com
• © 2013 Littelfuse •
• 30/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
11.3 Modbus Communication
®
The MODBUS RTU protocol is implemented in the PGR-8800, and allows up to four modules to
be connected using a 2-wire TIA-485 bus. The PGR-8800 can also be connected to a local HMI or
SCADA system. This will provide status information for sensors, analog inputs, digital inputs, digital
outputs, and numerous event and error flags. It also provides the ability to remotely reset the
PGR-8800. A converter for TIA-485 to Ethernet, IEC-61850, or other network type can be used for
remote network connections and many other communications options.
TIA-485
ARC-FLASH RELAY
PGR-8800 SERIES
ARC-FLASH RELAY
TIA-485
ARC-FLASH RELAY
PGR-8800 SERIES
PGR-8800 SERIES
ARC-FLASH RELAY
PGR-8800 SERIES
Set the Modbus interface and address with the configuration software. Each PGR-8800 must have
a unique Modbus address. See Section 12.2.9 and Appendices A and B.
Terminal
Description
Signal
Connection
37
38
B+
A-
TIA-485 B
TIA-485 A
B signal of the TIA-485 bus
A signal of the TIA-485 bus
The 2-wire multi-drop TIA-485 bus requires common terminals to be connected (terminals 37 to 37,
38 to 38). The maximum cable length is 10 m (33 ft) and must be shielded twisted pair. Use Belden
3105A cable, or equivalent.
www.littelfuse.com
• © 2013 Littelfuse •
• 31/84
PGR-8800 Arc-Flash Relay
12
Rev. 3-A-112913
USB INTERFACE
The PGR-8800 contains configuration software, data logs, and event records that can be accessed
through the USB Interface. No drivers or software installation is required to access configuration or
data. Use a USB A-B cable as shown below to connect the PGR-8800 to a computer.
The PC application for configuring the PGR-8800 is pre-installed on
the internal Configuration drive. When the PGR-8800 is connected to a
PC, the Configuration drive (wrench icon) and the Log drive (notepad
icon) will appear in the file manager as shown in Section 12.1.
This makes it possible to automate configuration if several relays with
the same configuration are needed. Contact Littelfuse for more
information.
NOTE: The configuration and log-viewer applications are HTML
Applications (HTA). HTA is a proprietary Microsoft™ technology
and is only supported by Internet Explorer 5.0 or later on
Microsoft Windows systems. Once configured, the data log file
can be accessed on any platform.
12.1 Connecting to a PC
The PGR-8800 requires supply voltage before connecting the USB cable. Although some LED’s
may light when connecting a USB cable to an unpowered PGR-8800, the USB interface does not
supply adequate power to allow proper operation.
A powered PGR-8800 will enter service mode when a PC is connected with a USB cable. In
service mode, arc-flash protection is inactive by default, but can be configured to trip in service
mode. See Section 12.2.8. The PGR-8800 will
remain in service mode until the USB cable is
disconnected and the MODE button is pressed to
return to online mode. When connected to a PC,
the PGR-8800 appears as two mass-storage
devices and two drives will be displayed in the file
manager. These drives are internal to the
PGR-8800 and behave like any standard drive. Files
can be copied to or from the drives or even dragged
and dropped.
NOTE: The changes made in the configuration
software will not be stored unless saved. The
configuration changes will be activated when
the USB cable is disconnected.
NOTE: The Log drive operates as a First-In,
First-Out (FIFO) log. When the Log drive is full,
the oldest entry will be removed to make room
for a new event.
www.littelfuse.com
• © 2013 Littelfuse •
• 32/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2 Configuration Software
The configuration software for the PGR-8800 is located on the Configuration drive (the wrench
icon). To run the software, open the Configuration drive in the PC file manager and double-click on
the config.hta file. The program will open in Internet Explorer regardless of the default browser.
The features of the software are outlined in subsequent sections of this manual.
For any setting or button, hovering the mouse cursor over it will display the possible values of the
setting or the function of the button.
12.2.1 Configuration Software Tabs
The configuration software is displayed in a window with eight tabs along the top of the screen.
Click on a tab to display the relevant configuration options.
General
Set the date, time, and a general description of the relay.
Optical Sensors
Configure optical sensors and arc-detection time before tripping.
Current Sensors
Set overcurrent and current-supervised arc-flash protection parameters.
Digital Inputs
Configure or disable the operation of the digital inputs.
Trip Output
Define the behaviour and pulse time of the Trip Coil output.
Communications
Link multiple PGR-8800 relays together into a single system or configure
Modbus.
Advanced
Enable data logging or restore configuration and factory defaults.
About
View information on firmware and hardware versions.
www.littelfuse.com
• © 2013 Littelfuse •
• 33/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2.2 Configuration Software Buttons
There are five buttons along the bottom of the configuration software window that are common to
every tab.
Save All
Save all configuration settings made in every tab.
Reset (This Tab)
Reset all configuration settings in this tab to the factory default. Changes
will not be stored until they are saved.
Undo (This Tab)
Undo any changes that have been made to the current tab since opening
the configuration software.
Save and Exit
Save all configuration settings made in every tab and exit the configuration
software.
Exit
Exit the configuration software. No changes will be saved unless the Save
All button has been pressed. If the Save All button is clicked accidentally,
use the Undo (This Tab) button on any tab where changes were made and
then Save and Exit.
There are two buttons for each configuration setting, Undo and Reset. The Undo button will cancel
any changes made to the value before the configuration software was opened. The Reset button
will load the factory default for that setting.
12.2.3 Default Configuration
It is possible to use the basic protection features of the PGR-8800 without using the configuration
software. Any connected optical sensors with circuit-check will be automatically detected and
cause the relay to report an error if subsequently disconnected.
The initial configuration can be stored permanently without use of the configuration software by
using the commissioning procedure outlined in Section 13.1. By default, the local sensor will not
cause a trip on excess light.
The PGR-8800 current sensors are disabled by default; sufficient light alone will cause an arc-flash
trip and overcurrent conditions will not cause a trip.
The amount of time that light must be detected to cause a trip is set at the factory to one
milliseconds. The cable-check feature for the digital inputs is disabled by default, but the inputs will
function if they are connected to terminal 45.
The default trip pulse time is one second.
The configuration software is required to enable data logging, Link, MODBUS, and current sensor
functions.
www.littelfuse.com
• © 2013 Littelfuse •
• 34/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2.4 General Settings
System Name
The system name can help identify the PGR-8800 (up to 25 characters) e.g. name and number of
the switchboard section in which the unit is mounted.
Date and Time
This section will show the current date and time on the PGR-8800 and provides the option to
synchronize with the connected PC.
12.2.5 Optical-Sensor Settings
Common Settings
These settings apply to all optical sensors. The arc detection time specifies the amount of time
light from an arc must be detected to cause a trip.
Valid settings are 0 to 20,000 milliseconds and the default setting is 1 millisecond. If set to zero
milliseconds, the effective trip time is less than 0.8 milliseconds. If a sensor detects light
approaching the trip level, the LED for that sensor will begin to flash. The threshold for the warning
flashes can be set to 50%, 75% (default), or 90% of the trip-level setting.
www.littelfuse.com
• © 2013 Littelfuse •
• 35/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
Individual Sensor Settings
Optical sensors are individually configurable with a 25-character description. The PGR-8800 scans
all optical sensor terminals periodically for sensors.
Sensor description
A name for the sensor (such as the switchboard section it is
monitoring) to aid in troubleshooting.
Ignore sensor check errors The PGR-8800 will not report if a sensor is removed. Check this
box to disable sensor check. The corresponding sensor-check
LED will still flash if connected.
Change configuration
Once a sensor is connected to a terminal, the PGR-8800 will
report an error if it is removed. If a sensor is removed, this allows
the sensor expected status to be reset.
NOTE: Sensor status can also be reset by placing the PGR-8800 in service mode and then
pressing the RESET button.
Local Sensor
The local sensor is located on the front of the PGR-8800 and is primarily intended for
commissioning of sensors. The configuration software allows a 25-character description.
The local sensor can also be used to trip the circuit breaker if the checkbox is marked.
www.littelfuse.com
• © 2013 Littelfuse •
• 36/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2.6 Current-Sensor Settings
Setup
The current sensors can be configured for use as current-supervised trip inhibit and/or overcurrent
protection.
By default, overcurrent protection and current-supervised trip inhibit are disabled. The value of the
rated-current set point will not affect the operation of the PGR-8800 until one of these functions is
enabled using the checkboxes.
When using current sensors, the signal being applied to the sensors (ac or dc) must be defined.
The module will automatically track the zero point if AC is selected.
The rated nominal load current is the typical current level that will be observed on the current
sensor primary and is the reference for the Inhibit and Overcurrent functions.
The current sensor ratio must also be defined. The PGR-8800 only accepts current sensors with a
5-A-secondary current. The accuracy of the reading is 1 A (current-sensors-secondary current).
Due to the fast reaction time of the PGR-8800 to an arc flash, it is important to set all levels and
time delays with this in mind.
www.littelfuse.com
• © 2013 Littelfuse •
• 37/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
Current-Supervised Trip Inhibit
The primary function of the current-sensor inputs is to provide current-supervised arc-flash
protection. If light is detected by the optical sensors but the current is below the Trip Inhibit setting,
the PGR-8800 will not trip. This value is adjustable from 10 to 1,000% of the rated nominal load
current. This feature is disabled by default. See Section 6.
When Current Inhibit is enabled, the INHIBIT LED on the front of the PGR-8800 will be on when
current is below the set point. When the current is above the set point, the INHIBIT LED will be off.
Overcurrent Protection
The PGR-8800 has two definite-time overcurrent set points which can be used for instantaneous,
short-, and long-time overcurrent protection. This feature is disabled by default.
The current level required to trip is set as a percentage of the rated nominal load current. The
overcurrent trip levels can be set from 150 to 1,000% and the time delay is adjustable from 1 to
20,000 milliseconds. See Section 6.
Overcurrent protection operates independently from arc-flash protection and the optical sensors.
www.littelfuse.com
• © 2013 Littelfuse •
• 38/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2.7 Digital-Input Settings
By default, the digital inputs are considered active when connected to COM (terminal 45). Using
the drop-down lists, the inputs can be disabled, circuit-check can be enabled (see Section 7) and
the inputs can be configured to be inactive when connected to COM (inverted).
The Trip inputs can also be inhibited if enabled. Otherwise, a Trip input is allowed to occur
regardless of the Inhibit Inputs function selection.
When the PGR-8800 sends a trip signal to the local circuit breaker, the status of the circuit breaker
can be monitored using the Trip input. In the case of a local circuit breaker failure, the PGR-8800
can be configured to trip an upstream circuit breaker. See Appendix C.
www.littelfuse.com
• © 2013 Littelfuse •
• 39/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2.8 Output Settings
12.2.8.1 Trip Coil Output
The Trip Coil Output can be configured to operate a shunt or an undervoltage circuit breaker. In
shunt mode, power is required to cause the circuit breaker to trip. Most installations will use this
type of circuit breaker because the trip times are typically faster than undervoltage circuit breakers.
However, the undervoltage circuit breaker has the advantage of tripping when supply voltage is
lost, making it a fail-safe device.
The amount of time that supply voltage will be applied to a shunt circuit breaker or removed from
an undervoltage circuit breaker is defined by the circuit-breaker pulse time and can be set from 1
to 5 s.
An external trip voltage is applied to one side of the Trip Coil output. If voltage is not present while
in shunt mode, the PGR-8800 will deactivate the ONLINE output, and flash the Trip Coil red LED.
This feature can be disabled by deselecting the Report an error if trip coil is not detected checkbox.
For more information on trip-coil operation, see Section 8.4.
By default, the PGR-8800 does not send a trip signal when in service mode because this mode
can be used for verifying sensor operation. Service-mode tripping can be selected by the Trip in
service mode checkbox. There is no indication of this setting on the front panel, so work
procedures should make a note of this.
www.littelfuse.com
• © 2013 Littelfuse •
• 40/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2.8.2 Coordinated Tripping
The PGR-8800 relies on the circuit breaker to extinguish an arc flash. The PGR-8800 can be
programmed to trip a secondary device further upstream if the local circuit breaker fails. Circuitbreaker failure is detected by connecting the auxiliary contact to the PGR-8800 Trip input or by
measuring the current using the current sensors, or both.
The Service and Tripped outputs can be configured to match the Trip Coil output or to trip an
upstream circuit breaker on a clearing failure.
The Link interface can also be used for coordinated tripping by sending a trip signal via the
interface when the primary circuit breaker fails.
For more on this topic, see Appendix C.
www.littelfuse.com
• © 2013 Littelfuse •
• 41/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2.9 Communications Settings
Link Interface
The Link input on the PGR-8800 (terminals 37, 38) is a multi-function communications port. The
port is disabled by default and can be configured as follows through the Link Interface drop-down
list:
Nothing
Disable communications port.
Link multiple units
Connect up to four PGR-8800 relays.
Modbus
Enable remote communication using the Modbus protocol.
Factory test
Not intended for customer use.
Selecting each option in the drop-down list will reveal further options.
www.littelfuse.com
• © 2013 Littelfuse •
• 42/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
Link Configuration
Up to four PGR-8800’s can be linked in this mode, but each must be given a unique Unit address
and the total Number of linked units in the system must be configured in all linked units.
The PGR-8800 can be programmed to send an alarm signal over the link interface:
Never
The PGR-8800 will receive alarm signals but not send them.
Light above threshold
An alarm signal will be sent when light is above the trip level regardless
of the local inhibit status.
Trip
An alarm signal will only be sent when all local conditions such as light
level and inhibit are satisfied.
Clearing failure
The PGR-8800 will send an alarm signal when the local circuit breaker
does not trip.
Received Link alarm signal trips this unit
If selected, this option will allow the module to receive a Link alarm sent from another unit, and will
trip the module.
Link sends and receives the user interface
This option will allow the module to send and receive button presses. Pressing RESET on one
module will reset all link-enabled modules with this option selected. Modules will also change
mode together. This does not influence the Trip and Inhibit terminal inputs.
Link sends and receives errors
This option shares errors such as sensor-check failure or no voltage on the TRIP COIL to all the
linked units. As a result, an error on one module will change the online mode on all link-enabled
modules.
The PGR-8800 can be configured to share light-sensor information. Although a current-inhibited
PGR-8800 detecting excess light will not trip, it will trip a remote PGR-8800 that is not inhibited by
sharing light intensity.
See Section 11 for more information on linking multiple units.
www.littelfuse.com
• © 2013 Littelfuse •
• 43/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
Modbus Configuration
The Modbus device address, baud rate, and parity must be configured on the device with the
Configuration Software.
Default configuration
Device address
1
Baudrate
19200
Parity
Even
Number of start bits
8
Number of stop bits
(controlled by parity selection)
Even Parity
1
Odd Parity
1
None
2
Allow writes via MODBUS is disabled by default.
Network Termination
Since the PGR-8800 Modbus interface shares the Link interface, the network is already terminated
internally. This limits the number of units which can be connected, and the maximum length of the
connection. See Section 11.3.
See Appendices A and B for the Modbus Protocol description and database table.
www.littelfuse.com
• © 2013 Littelfuse •
• 44/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2.10 Advanced Settings
Logging
The data logging feature is disabled by default. A preliminary version of a waveform capture
feature can also be enabled but this feature is still in a testing stage and is not considered
complete. If the PGR-8800 will be connected in an application where tripping results in a loss of
supply power, use of a backup battery supply is required when using data logging. Power supply
failure while writing to the log drive can lead to loss of data. See Section 12.3.
Internal Drives & Configuration
In addition to the hardware reset procedures outlined in Section 10, the configuration software
allows for partial reset of certain modules and configuration. Every parameter can be individually
reset by using the Reset button associated with it (see Section 12.2.2).
Resetting the configuration drive will retain all settings but any files stored on the drive will be lost.
Resetting the log drive will result in a loss of any logged events and stored data on the log drive.
By using the Reset configuration to factory defaults checkbox, all configuration settings can be
restored to their default values.
www.littelfuse.com
• © 2013 Littelfuse •
• 45/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
12.2.11 About Tab
The About tab displays general information about the PGR-8800 such as the last time the
configuration was saved, the firmware revision number, hardware revision number, and serial
number.
12.3 Data Log Drive
The PGR-8800 can log all significant events including trips, errors and button presses. By default,
data logging is disabled. See Section 12.2.10.
Once enabled, the raw data is logged in a plain text file on the log drive. This file can be viewed in
any text editor or in the included log.hta log reader. Log.hta requires Internet Explorer 5.0 or
greater and displays the data log in a simplified format.
www.littelfuse.com
• © 2013 Littelfuse •
• 46/84
PGR-8800 Arc-Flash Relay
13
Rev. 3-A-112913
COMMISSIONING
Even without configuration, the PGR-8800 will work using the factory default settings. See
Section 12.2.3. It will always trip if a sensor input exceeds the Trip Level setting, even if the circuit
check is falsely reporting a cable to be broken. However, we recommend doing a few simple tests
on the sensors to ensure that problems on the sensors or cabling will be detected and reported.
The PGR-8800 will detect sensors on power up and report if they disappear, but in most
installations it is advantageous to store the sensor configuration permanently. This is easily done
by configuring the installed sensors either via USB as shown above or with the method described
below.
13.1 Configuration of Installed Sensors
1. Press MODE to switch to service mode (SERVICE LED will be solid red).
2. Press and hold RESET for a few seconds to start the test sequence.
3. The LED’s for sensors 1-6 will flash for 10 seconds while the system tests the optical sensors.
This clears the sensor configuration1.
4. Move a light source of at least 100 lumen (e.g. 300 W halogen lamp) towards the local sensor
until the LOCAL LED turns off. When using fiber sensors, a photo flash with a guide number of
15 m (49 ft) or larger can be used. See Section 15 for ordering information.
5. Observe that all connected sensor LED’s are flashing. Move the light source towards each
sensor until its internal LED turns off. This should happen at approximately the same distance at
which was used before the local sensor reacted. The PGR-8800 LED associated with the sensor
will change to solid green at the same time.
6. Return to the central unit and confirm that all LED’s for connected sensors are showing a solid
green LED. Illuminate the local sensor again to store the results.
7. The system will now flash green on all sensors briefly, store the results in non-volatile memory,
and return to service mode. Sensor errors that may occur when the supply voltage is cycled can
now be detected.
8. Press MODE to switch back to online mode. The sensors are now configured and the system
will alarm if a sensor malfunctions.
13.2 Testing the Sensors
1. Press MODE to switch to service mode (SERVICE LED will be solid red).
2. Confirm that there is a solid PGR-8800 green LED for each connected optical sensor. This
confirms that sensors are connected and healthy.
3. Confirm that a short red flashing light occurs periodically in each sensor. This indicates that the
sensor circuit is being checked.
1
If something is not functioning properly during the test, it can be cancelled by pressing RESET at
any time. Reverting back to the previous configuration requires a power cycle of the unit.
www.littelfuse.com
• © 2013 Littelfuse •
• 47/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
4. Point a light source at a sensor and check that the LED on the sensor and the unit begin to flash
red continuously. On the first sensor tested, the TRIPPED LED will also turn on until the RESET
button is pushed.
5. Repeat step 4 for the remaining sensors.
6. Confirm that all LED’s at connected sensors are flashing red.
7. Press MODE to switch back to online mode (ONLINE LED will be solid green and SERVICE
LED will be off).
The test can be cancelled at any time by pressing MODE, to return to online mode.
13.3 Testing the Trip Coil
1. Ensure that the system is ready for testing. The TRIP COIL output will be tripped during this
procedure.
2. Press MODE to switch to service mode (SERVICE LED will be solid red).
3. Press and hold TRIP for a few seconds to activate the TRIP COIL output.
4. Observe that the connected trip coil operates. The output will reset itself after the configured
pulse time, one second by default.
5. Press RESET. Reset the tripping device if necessary.
6. Press MODE to switch back to online mode (ONLINE LED will be solid green and SERVICE
LED will be off).
13.4 Full Operation Test (Online)
1. Make sure that the system is ready for test. The TRIP COIL output will be tripped during this
procedure.
2. If necessary, press MODE to switch to online mode (ONLINE LED will be solid green).
3. Confirm that there is a solid PGR-8800 green LED for each connected optical sensor. This
confirms that sensors are connected and healthy.
4. Confirm that a short red flashing light occurs periodically in each sensor. This indicates that
the sensor circuit is being checked.
5. Move a light source towards the local sensor and confirm that it starts flashing.
6. Move a light source towards an external sensor. The SENSOR LED will start flashing green
when the light intensity is approaching the Trip Level.
7. Continue to move a light source closer to the sensor. Confirm that the TRIP COIL output trips
and that the LED’s of the TRIP COIL and sensor change to flashing red.
8. Press RESET. Reset the tripping device if necessary.
9. Repeat steps 6 to 8 for the remaining sensors.
www.littelfuse.com
• © 2013 Littelfuse •
• 48/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
13.5 Light Sensitivity Adjustment
1. Adjust the TRIP LEVEL dial; lower numbers result in higher sensitivity and greater detection
range.
13.6 Fiber-Optic Sensor Adjustment
The sensor is calibrated at the factory for 60 cm (24”) of fiber in each monitored compartment.
When using a fiber-optic sensor in compartments with less than 60 cm (24”) of fiber, the sensitivity
may have to be adjusted. The sensor is unable to differentiate between 10,000 lux on 60 cm (24”)
of fiber and 30,000 lux on 20 cm (8”) of fiber – the same amount of light is transmitted through the
fiber to the receiver. To achieve the desired sensitivity, the receiver (with the black thumb nut)
must be adjusted.
13.6.1 Sensor Adjustment for a Fiber Length other than 60 cm (24”)
To adjust for fiber length, a powerful light source of at least 100 lumen (e.g. 300 W halogen lamp)
is required. In some cases, a photo flash with a guide number of 15 m (49 ft) or larger can be
used. Use the following procedure to calibrate the sensor:
1. Switch the PGR-8800 to service mode by pressing the MODE button. The red SERVICE
LED will light.
2. Adjust the TRIP LEVEL setting to 1 on the PGR-8800.
3. Slowly move the lamp towards the local sensor on the front of the PGR-8800.
4. Note the distance from the lamp to the sensor when the LOCAL LED starts blinking.
5. Adjust the receiver (black thumb nut) sensitivity level to the minimum by turning the small
metal screw clockwise until it begins to click. This may be too low to detect the sensorcheck signal and may cause the related LED on the relay to flash red.
6. Place the lamp facing the fiber in the compartment closest to the transmitter end (white
thumb nut) of the fiber at the distance observed in step 4. This allows for loss along the full
length of the fiber.
7. Slowly turn the metal screw on the receiver counter-clockwise until the PGR-8800 sensorindicator LED for that sensor changes to red. If the LED was already flashing red in step 5,
it should change to green first.
8. Adjust the TRIP LEVEL setting back to the desired position.
www.littelfuse.com
• © 2013 Littelfuse •
• 49/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
13.6.2 Sensor Adjustment in Small Compartments
If the fiber-optic sensor is used in multiple compartments of varying size, the sensor must be
calibrated to the compartment with the least fiber. If the lamp cannot be placed far enough away in
the compartment to follow the procedure in Section 13.6.1, the sensitivity-adjustment procedure
can be modified as follows:
1. Switch the PGR-8800 to service mode by pressing the MODE button. The red SERVICE
LED will light.
2. In the compartment with the shortest fiber, measure the distance from the fiber to the lamp
when the lamp is placed at the point in the compartment where it is furthest away.
3. Set the TRIP LEVEL to 9 on the PGR-8800.
4. Place the lamp facing the local sensor on the PGR-8800 at the same distance as measured
in step 2.
5. Turn the TRIP LEVEL dial on the PGR-8800 counter clockwise until the LOCAL LED starts
blinking.
6. Adjust the receiver (black thumb nut) sensitivity level to minimum by turning the small metal
screw clockwise until it begins to click. This may be too low to detect the sensor-check
signal and may cause the related LED on the relay to flash red.
7. Place the lamp in the compartment closest to the transmitter end (white thumb nut) of the
fiber at the distance observed in step 2. This allows for loss along the full length of the
fiber.
8. Slowly turn the metal screw on the receiver counter-clockwise until the PGR-8800 sensorindicator LED for that sensor changes to red. If the LED was already flashing red in step 6,
it should change to green first.
9. Adjust the TRIP LEVEL setting back to the desired position.
www.littelfuse.com
• © 2013 Littelfuse •
• 50/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
14 SPECIFICATIONS
14.1 PGR-8800
Supply:
Universal:
20 VA, 100 to 240 Vac (+10%, -15%) 50/60 Hz,
8 W, 110 to 250 Vdc (+10%, -20%)
Low Voltage:
4 W, 14 to 48 Vdc (+10%, -20%)
Backup Battery (user supplied):
24 Vdc lead-acid, 2 to 15 Ah capacity
Charged at 27.5 Vdc, 200 mA max when universal
supply is used
Optical Settings:
External Sensors:
Up to 24 (6 per unit)
Sensor Types:
PGA-LS10, PGA-LS20, PGA-LS25, PGA-LS30 all with
sensor check
Trip Sensitivity Adjustment:
1 to 9 (corresponding to 9 to 25 klux)
Trip Time Settings:
0 to 20,000 ms (0.8 ms effective minimum)
Trip Coil Output:
Type:
IGBT Switch
Configuration:
Normally Open (Form A)
UL Rating:
120/240 Vac, 1800 VA, 0.75 A maximum continuous,
125/250 Vdc, 138 VA, 0.75 A maximum continuous
Supplemental Rating:
Make/Carry 0.2 s:
1
30 A
Voltage Rating :
24 to 300 Vac, 24 to 300 Vdc
Current Rating:
20 A for 2 s, 10 A for 5 s
Control Voltage Alarm:
5V
Operating Modes:
Shunt or Undervoltage
Protection:
320 Vac MOV, thermally protected
Isolation:
1,000 Vac
Pulse Duration:
1 to 5 s, configurable
On-State Voltage Drop:
2.5 V at 5 A, 25˚C (77˚F)
4.0 V at 10 A, 25˚C (77˚F)
Output Relays:
Main Relays:
Online, Service, Tripped
Contact Configuration:
Change-over (Form C)
UL Contact Rating:
5 A Resistive, 250 Vac
5 A Resistive, 30 Vdc
www.littelfuse.com
• © 2013 Littelfuse •
• 51/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
Supplemental Contact Rating:
Make/Carry 0.2 s:
30 A
Rating Code:
B300, R300
Break:
dc:
28 W Resistive
ac:
1500 VA (PF=1.0)
360 VA (PF=0.4)
Subject to maximums of 5 A and 250 V (ac or dc)
Status Relays:
Online, terminal 49 (STO)
Service, terminal 53 (STS)
Tripped, terminal 57 (STT)
Contact Configuration:
Normally Open (Form A), reference to terminal 45 (COM)
UL Rating:
100 mA, 50 Vac/Vdc
Supplemental Rating:
Contact Rating:
3 A Resistive, 240 Vac
3 A Resistive, 30 Vdc
Terminals:
Wire Clamping, 22-12 AWG (0.14 to 2.5 mm2) copper
conductors
Torque:
4 to 5.5 in-lb
Current Inputs:
Full Scale:
5 A Secondary
Continuous:
10 A Secondary
Thermal Withstand:
75 A for 1 s
Burden:
< 0.25 VA at 5 A
Current Sensor Class:
Protection Class 10P5 or better
Trip Time:
1 to 20,000 ms
Trip Level:
Overcurrent 1:
150 to 1,000% of rated nominal load current
Overcurrent 2:
150 to 1,000% of rated nominal load current
Accuracy:
1 A secondary
Resolution:
100 mA secondary
Isolation:
500 Vac
Local Interface:
USB 1.1
Communications Interface:
Protocol:
Modbus® RTU
Configuration:
TIA-485 Isolated, 2-wire multi-drop
www.littelfuse.com
• © 2013 Littelfuse •
• 52/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
Bus Length:
10 m (32.8 ft)
Cable:
Shielded twisted pair, Belden 3105A or equivalent
System Expansion:
Link up to four units
Internal Real-Time Clock:
Battery2:
Life:
Dimensions:
Height:
CR1632
Minimum 10 years
130 mm (5.1 in)
Width:
200 mm (7.9 in)
Depth:
Shipping Weight:
54 mm (2.1 in)
0.9 kg (2 lbs)
Mounting:
Environment:
Operating Temperature:
35 mm DIN rail or surface mount
-25 to 70°C (-13°F to 158°F)
Storage Temperature:
-40 to 70˚C (-40˚F to 158°F)
Humidity:
93% Non-condensing
Altitude:
Below 2,000 m (6,500 ft):
Normal Operation
Above 2,000 m (6,500 ft):
24 Vdc supply only, shunt trip only
Above 4,000 m (13,000 ft):
EMC Tests:
Contact Littelfuse for further information.
Verification tested in accordance with EN60255-26:2009.
1 MHz Burst:
IEC 60255-22-1
± 1 kV differential mode
(line-to-line)
± 2.5 kV common mode
Electrostatic Discharge:
IEC 60255-22-2
± 6 kV Contact Discharge
(direct and indirect)
± 8 kV Air Discharge
Radiated RF Immunity:
IEC 60255-22-3
10 V/m, 80-1,000 MHz,
80% AM (1 kHz)
10 V/m, 1.4 to 2.7 GHz,
80% AM (1 kHz)
Fast Transient:
IEC 60255-22-4
Class A: ± 4 kV
www.littelfuse.com
• © 2013 Littelfuse •
• 53/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
(on AC mains)
Surge Immunity:
IEC 60255-22-5
± 4 kV differential mode
(on AC lines)
± 2 kV common mode
(on AC lines)
± 2 kV common mode
(on I/O ports)
± 1 kV differential mode
(on I/O ports)
Conducted RF Immunity:
IEC 60255-22-6
10 Vrms, 0.15-80 MHz
80% AM (1 kHz)
Power Frequency:
IEC 60255-22-7
Not applicable
Cables are < 10 m
Magnetic Field Immunity:
IEC 61000-4-8
50 Hz and 60 Hz
30 A/m and 300 A/m
Current Harmonics and Voltage
Fluctuations:
IEC 61000-3-2
and IEC 61000-3-3
Class A
Radiated and Conducted
Emissions:
CISPR 22:2008-09 / EN55022:2010
Class A
Voltage Interruptions:
IEC 60255-11
and IEC 60255-29
100% Interrupts 3 x for 5 ms, 10 ms, 20 ms, 50 ms,
100 ms, 200 ms
Vibration:
IEC 60255-21-1 (Vibration, shock, and seismic)
Safety:
IEC 61010-1: 2010 3rd Edition
Safety Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use – Part I
www.littelfuse.com
• © 2013 Littelfuse •
• 54/84
PGR-8800 Arc-Flash Relay
Certification:
Rev. 3-A-112913
UL Listed
LISTED
IND.CONT.EQ
4YY5
NRGU.E348169
UL508 Industrial Control Equipment3
Australia
N11659
CE, European Union
EMC standards: EN60255-26
FCC
Surge Withstand:
ANSI/IEEE C37.90.1-2002 (Oscillatory and Fast
Transient
14.2 Sensors
PGA-LS10
PGA-LS20, PGA-LS25, and
PGA-LS30
Type:
Point sensor
Fiber-optic sensor
Detection Zone:
180 x 360° (half sphere)
360° along fiber
Output:
0-35 mA
0-35 mA
Electrical Cable:
Shielded 3-wire 20 AWG (0.5
mm2) electrical cable
Shielded 3-wire 20 AWG (0.5 mm2)
electrical cable
Factory Cable Length:
10 m (33 ft) electrical cable
PGA-LS20:
8 m (26 ft) active;10 m (33 ft) total
(2 m (7 ft) shielded),
2 x 10 m electrical cable
PGA-LS25:
5 m (16 ft) active; 8 m (26 ft) total
(3 m (10 ft) shielded),
2 x 10 m (33 ft) electrical cable
PGA-LS30:
18 m (59 ft) active; 20 m (66 ft) total
(2 m (7 ft) shielded),
2 x 10 m (33 ft) electrical cable
Max. Elec. Cable
Length:
50 m (164 ft)
50 m (164 ft)
Sensor Check:
Built-in LED for visual feedback
Built-in LED for visual feedback
www.littelfuse.com
• © 2013 Littelfuse •
• 55/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
Dimensions:
32 x 52 x 24 mm
(1.3 x 2.0 x 0.9 in)
Transmitter and Receiver:
32 x 56 x 19 mm
(1.3 x 2.2 x 0.7 in)
Enclosure:
IP 30
IP 30
PGR-8800 uses the open source components FreeRTOS and FreeMODBUS internally.
license, version, and source-code information please contact [email protected].
15
For
ORDERING INFORMATION
PGR-8800-00(4)
Accessories:
PGA-LS10
Point Sensor
PGA-LS20
Fiber-Optic Sensor, 8 m (26 ft) active length
PGA-LS25
Fiber-Optic Sensor, 5 m (16 ft) active length
PGA-LS30
Fiber-Optic Sensor, 18 m (59 ft) active length
PGA-0031
DIN-rail mounting brackets
PGA-1100
Diode Logic Unit
PGA-FLSH-00
Photo Flash
PGA-FLSH-01
Photo Flash, CE and RoHS
16
WARRANTY
The PGR-8800 Arc-Flash Relay is warranted to be free from defects in material and workmanship
for a period of five years from the date of purchase.
Littelfuse will (at Littelfuse’s option) repair, replace, or refund the original purchase price of a PGR8800 that is determined by Littelfuse to be defective if it is returned to the factory, freight prepaid,
within the warranty period. This warranty does not apply to repairs required as a result of misuse,
negligence, an accident, improper installation, tampering, or insufficient care. Littelfuse does not
warrant products repaired or modified by non-Littelfuse personnel.
NOTES:
1
Contact Littelfuse for trip coil voltages higher than 300 Vac/Vdc.
2
Battery is mounted in an internal socket and should be changed by qualified service personnel
only. Contact your distributor for more information.
3
The PGR-8800 Arc Flash Relay is currently listed as a protective relay (UL category NRGU) and
complies with the UL508 Industrial Control Equipment standard. UL did not evaluate the
functionality of the arc fault protection afforded by this product. A file review will occur when the
requirements for investigation of arc detection and mitigation systems are developed and
additional tests will be performed if required.
4
Hardware revision 2.1 includes UL, CE, and C-Tick certification. Hardware revision 2.0 includes
UL and C-Tick certification. Refer to Appendix E for details.
www.littelfuse.com
• © 2013 Littelfuse •
• 56/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
APPENDIX A PGR-8800 MODBUS RTU PROTOCOL
A.1 PROTOCOL
The MODBUS RTU protocol is implemented in the PGR-8800, and allows up to four modules to be
connected using a 2-wire TIA-485 bus. The MODBUS interface will provide status information for
sensors, analog inputs, digital inputs, digital outputs, and numerous event and error flags. It also
provides the ability to remotely reset the PGR-8800. Writes are not allowed by default.
A.1.1 Configuration Setup
A.2 MESSAGE SYNCHRONIZATION
Message synchronization is accomplished by detection of an idle communication line. The
communication line is considered idle when no communication exists for an equivalent delay of 3.5
characters.
The first byte received after idle-line detection is interpreted as the address byte of the next message.
Message bytes must be transmitted in a continuous stream until the complete message has been
sent. If a delay of more than 3.5 characters exists within the message, the message is discarded.
Response messages from the PGR-8800 are delayed by at least 3.5 character delays.
A.3 ERROR CHECKING
Modbus RTU uses a 16-bit cyclic redundancy check (CRC). The error check includes all of the
message bytes, starting with the first address byte. When a CRC error is detected, the message is
discarded and there will be no response.
www.littelfuse.com
• © 2013 Littelfuse •
• 57/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
A.4 FUNCTION CODES SUPPORTED
The PGR-8800 Modbus Protocol supports the following function codes:
Read Holding registers (Function code 3)
Read Input registers (Function code 4)
Write Single register* (Function code 6)
Read Slave ID (Function code 11)
Write Multiple registers* (Function code 16)
*If writing is enabled in the configuration
A.4.1 Read Input/Holding Registers (Code 04/03)
The first byte of the read message is the slave address. The second byte is the function code. Bytes
three and four indicate the starting register. The next two bytes specify the number of 16-bit registers
to read. The last two bytes contain the CRC code for the message.
TABLE A.1 READ REGISTERS (CODE 04/03)
HEX BYTE
DESCRIPTION
Slave Address
Byte 1
Function Code
Byte 2
MSB Register Address
Byte 3
LSB Register Address
Byte 4
MSB Number of Registers
Byte 5
LSB Number of Registers
Byte 6
LSB CRC
Byte 7
MSB CRC
Byte 8
The two-byte values of starting register and number of registers to read are transmitted with the highorder byte followed by the low-order byte. The CRC value is sent with the LSB followed by the MSB.
A.4.2 Write to Register
Function Code 6 or 16 is used to make set-point changes.
A.4.2.1 Write Single Register (Code 6)
The function code format for writing a single register is shown in Table A.2.
The message consists of the slave address followed by the Function Code 6 and two 16-bit values.
The first 16-bit value specifies the register to be modified and the second value is the 16-bit data.
TABLE A.2 WRITE SINGLE REGISTER (CODE 6)
HEX BYTE
DESCRIPTION
Slave Address
Byte 1
Function Code
Byte 2
MSB Register Address
Byte 3
LSB Register Address
Byte 4
MSB of Data
Byte 5
LSB of Data
Byte 6
LSB of CRC
Byte 7
MSB of CRC
Byte 8
www.littelfuse.com
• © 2013 Littelfuse •
• 58/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
A.4.2.2 Write Multiple Registers (Code 16)
The function-code format in Table A.3 can be used for writing single or multiple registers.
TABLE A.3 WRITE MULTIPLE REGISTERS (CODE 16)
HEX BYTE # DESCRIPTION
Slave Address
Byte 1
Function Code
Byte 2
MSB Register Address
Byte 3
LSB Register Address
Byte 4
MSB of Quantity
Byte 5
LSB of Quantity
Byte 6
Byte Count
Byte 7
MSB of Data
.
LSB of Data
.
LSB of CRC
.
MSB of CRC
Byte n
The slave will reply with the slave address, function code, register address, and the quantity followed
by the CRC code for a total of eight bytes.
A.4.3 Exception Responses
The PGR-8800 will return appropriate error codes as per the standard for malformed or out-ofrange requests.
A.5 PGR-8800 DATABASE
Appendix B contains the Modbus Registers in the Communications Database Table. The table starts
at register 200 and each register is 16-bits wide.
A.6 SPECIFICATIONS
Interface
Isolated TIA-485, 2-wire multi-drop
Protocol
Modbus® RTU
Baud Rate
1,200 to 19,200 bit/s
Bit Format
8 bits, even or odd parity, one or two stop bits
Maximum Cable Length
10 m (33 ft)
Cable Type
Shielded Twisted Pair, Belden 3105A or equivalent
Terminals
22 to 12 AWG, (0.1 to 2.5 mm2) conductors
NOTE: The TIA-485 hardware is shared with the Link function and can either be configured for
Link or Modbus but not both at the same time.
References
[1] "MODBUS over serial line specification and implementation guide V1.02" http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
[2] "MODBUS Application protocol Specification V1.1b" http://www.modbus.org/docs/Modbus_Application_Protocol_V1_1b.pdf
www.littelfuse.com
• © 2013 Littelfuse •
• 59/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
APPENDIX B MODBUS COMMUNICATIONS DATABASE TABLE
PGR-8800
REGISTER
(DECIMAL)
MODBUS
REGISTER
(DECIMAL)
DESCRIPTION
ACCESS
TERMINAL
TYPE
Analog Inputs (Values)
200
40201
Number of analog inputs on system
Read Only
N/A
16-bit word, always 22
201
40202
Light on Sensor 1
Read Only
3
T1
202
40203
Light on Sensor 2
Read Only
7
T1
203
40204
Light on Sensor 3
Read Only
11
T1
204
40205
Light on Sensor 4
Read Only
15
T1
205
40206
Light on Sensor 5
Read Only
19
T1
206
40207
Light on Sensor 6
Read Only
23
T1
207
40208
Current on CT1
Read Only
25 – 26
T2
208
40209
Current on CT2
Read Only
27 – 28
T2
209
40210
Current on CT3
Read Only
29 – 30
T2
214
40215
Light on Front Sensor
Read Only
N/A
T1
Analog Inputs (Max value since last read)
300
40301
Number of analog inputs on system
Read Only
N/A
16-bit word, always 22
301
40302
Light on Sensor 1
Read Only
3
T1
302
40303
Light on Sensor 2
Read Only
7
T1
303
40304
Light on Sensor 3
Read Only
11
T1
304
40305
Light on Sensor 4
Read Only
15
T1
305
40306
Light on Sensor 5
Read Only
19
T1
306
40307
Light on Sensor 6
Read Only
23
T1
307
40308
Current on CT1
Read Only
25 – 26
T2
308
40309
Current on CT2
Read Only
27 – 28
T2
309
40310
Current on CT3
Read Only
29 – 30
T2
314
40315
Light on Front Sensor
Read Only
N/A
T1
Analog Inputs (Min value since last read)
400
40401
Number of analog inputs on system
Read Only
N/A
16-bit word, always 22
401
40402
Light on Sensor 1
Read Only
3
T1
402
40403
Light on Sensor 2
Read Only
7
T1
403
40404
Light on Sensor 3
Read Only
11
T1
404
40405
Light on Sensor 4
Read Only
15
T1
405
40406
Light on Sensor 5
Read Only
19
T1
406
40407
Light on Sensor 6
Read Only
23
T1
407
40408
Current on CT1
Read Only
25 – 26
T2
408
40409
Current on CT2
Read Only
27 – 28
T2
409
40410
Current on CT3
Read Only
29 – 30
T2
414
40415
Light on Front Sensor
Read Only
N/A
T1
Sensor Input Status
500
40501
Number of light sensors on system
Read Only
N/A
16-bit word, always 6
501
40502
Status of Sensor 1
Read Only
3
T3
502
40503
Status of Sensor 2
Read Only
7
T3
503
40504
Status of Sensor 3
Read Only
11
T3
504
40505
Status of Sensor 4
Read Only
15
T3
505
40506
Status of Sensor 5
Read Only
19
T3
506
40507
Status of Sensor 6
Read Only
23
T3
www.littelfuse.com
• © 2013 Littelfuse •
• 60/84
PGR-8800 Arc-Flash Relay
PGR-8800
REGISTER
(DECIMAL)
MODBUS
REGISTER DESCRIPTION
(DECIMAL)
ACCESS
Rev. 3-A-112913
TERMINAL
TYPE
Power Voltages
600
40601
Number of power inputs on system
Read Only
N/A
16-bit word, always 5
601
40602
Output from AC supply
Read Only
35
T4
602
40603
Input from DC terminal
Read Only
34
T5
603
40604
Input from battery
Read Only
35
T6
604
40605
Output from 5 V supply
Read Only
N/A
T7
605
40606
Output from sensor supply
Read Only
N/A
T8
Mode Control
Read Only
N/A
16-bit word, always 3
41102
Number of user-writable mode
selections
Mode
Read/Write
41103
Power
Read Only
N/A
N/A
T10
41104
Error
Read Only
N/A
T11
1200
41201
Number of Digital Inputs on system
Read Only
N/A
16-bit word, always 3
1201
41202
Status of Inhibit Input
Read Only
39 – 40
T12
1202
41203
Status of Trip Input
Read Only
41 – 42
T12
1203
41204
Status of Reset Input
Read/Write
43 – 44
T13
1300
41301
Number of relay outputs on system
Read Only
N/A
16-bit word, always 4
1301
41302
Status of Online output
Read Only
46 – 49
T14
1302
41303
Status of Service output
Read Only
50 – 53
T14
1303
41304
Status of Tripped output
Read Only
54 – 57
T14
1304
41305
Status of IGBT output
Read Only
59 – 60
T14
1500
41501
Number of status flags available
Read Only
N/A
16-bit word, always 58
1501
41502
Not used
Read Only
N/A
T15
1502
41503
Sensor 1
Read Only
N/A
T15
1503
41504
Sensor 2
Read Only
N/A
T15
1504
41505
Sensor 3
Read Only
N/A
T15
1505
41506
Sensor 4
Read Only
N/A
T15
1506
41507
Sensor 5
Read Only
N/A
T15
1507
41508
Sensor 6
Read Only
N/A
T15
1508
41509
Sensor front
Read Only
N/A
T15
1509
41510
Analog OR of all sensors
Read Only
N/A
T15
1510
41511
Current inhibit
Read Only
N/A
T15
1511
41512
Current overload 1
Read Only
N/A
T15
1100
41101
1101
1102
1103
T9
Digital Inputs
Address
Event Flags
1512
41513
Current overload 2
Read Only
N/A
T15
1513
41514
Not used
Read Only
N/A
T15
1514
41515
Inhibit input
Read Only
N/A
T15
1515
41516
Trip input
Read Only
N/A
T15
1516
41517
Reset input
Read Only
N/A
T15
1517
41518
Mode button
Read Only
N/A
T15
1518
41519
Trip button long press
Read Only
N/A
T15
1519
41520
Reset button
Read Only
N/A
T15
1520
41521
Reset button long press
Read Only
N/A
T15
1521
41522
Link trip
Read Only
N/A
T15
1522
41523
Link command inhibit
Read Only
N/A
T15
www.littelfuse.com
• © 2013 Littelfuse •
• 61/84
PGR-8800 Arc-Flash Relay
PGR-8800
REGISTER
(DECIMAL)
MODBUS
REGISTER DESCRIPTION
(DECIMAL)
Rev. 3-A-112913
ACCESS
TERMINAL
TYPE
T15
1523
41524
Link command trip
Read Only
N/A
1524
41525
Link command reset
Read Only
N/A
T15
1525
41526
Modbus command inhibit
Read Only
N/A
T15
1526
41527
Modbus command trip
Read Only
N/A
T15
1527
41528
Modbus command reset
Read Only
N/A
T15
1528
41529
Test or USB active
Read Only
N/A
T15
1529
41530
State timeout
Read Only
N/A
T15
1530
41531
Error timeout
Read Only
N/A
T15
1531
41532
State done
Read Only
N/A
T15
1532
41533
Trip log complete
Read Only
N/A
T15
1533
41534
Link command service
Read Only
N/A
T15
1534
41535
Link command online
Read Only
N/A
T15
1535
41536
Modbus command service
Read Only
N/A
T15
1536
41537
Modbus command online
Read Only
N/A
T15
1537
41538
Error link
Read Only
N/A
T15
1538
41539
Error task failed
Read Only
N/A
T15
1539
41540
Error power failure
Read Only
N/A
T15
1540
41541
Error IGBT missing voltage
Read Only
N/A
T15
1541
41542
Error sensor power failure
Read Only
N/A
T15
1542
41543
Link command error
Read Only
N/A
T15
1543
41544
Link command setup
Read Only
N/A
T15
1544
41545
Trip button
Read Only
N/A
T15
1545
41546
Output trip momentary command
Read Only
N/A
T15
1546
41547
CB closed feedback
Read Only
N/A
T15
1547
41548
CB clearing failure
Read Only
N/A
T15
1548
41549
Current detect for CB failure
Read Only
N/A
T15
1549
41550
Currently AC powered
Read Only
N/A
T15
1550
41551
Currently DC powered
Read Only
N/A
T15
1551
41552
Read Only
N/A
T15
1552
41553
Read Only
N/A
T15
1553
41554
Read Only
N/A
T15
1554
41555
Local CB tripped in this event
Upstream CB tripped via Service
relay
Upstream CB tripped via Tripped
relay
Local CB tripped via Service relay
Read Only
N/A
T15
1555
41556
Local CB tripped via Tripped relay
Read Only
N/A
T15
1556
41557
Link alarm sent due to Light
Read Only
N/A
T15
1557
41558
Read Only
N/A
T15
1558
41559
Link alarm sent due to Trip
Link alarm sent due to Trip fault tripped Upstream
Read Only
N/A
T15
Status Flags
1600
41601
Number of status flags available
Read Only
N/A
16-bit word, always 58
1601
41602
Not used
Read Only
N/A
T15
1602
41603
Sensor 1
Read Only
N/A
T15
1603
41604
Sensor 2
Read Only
N/A
T15
1604
41605
Sensor 3
Read Only
N/A
T15
1605
41606
Sensor 4
Read Only
N/A
T15
1606
41607
Sensor 5
Read Only
N/A
T15
1607
41608
Sensor 6
Read Only
N/A
T15
1608
41609
Sensor front
Read Only
N/A
T15
1609
41610
Analog OR of all sensors
Read Only
N/A
T15
www.littelfuse.com
• © 2013 Littelfuse •
• 62/84
PGR-8800 Arc-Flash Relay
PGR-8800
REGISTER
(DECIMAL)
MODBUS
REGISTER DESCRIPTION
(DECIMAL)
ACCESS
Rev. 3-A-112913
TERMINAL
TYPE
1610
41611
Current inhibit
Read Only
N/A
T15
1611
41612
Current overload 1
Read Only
N/A
T15
1612
41613
Current overload 2
Read Only
N/A
T15
1613
41614
Not used
Read Only
N/A
T15
1614
41615
Inhibit input
Read Only
N/A
T15
1615
41616
Trip input
Read Only
N/A
T15
1616
41617
Reset input
Read Only
N/A
T15
1617
41618
Mode button
Read Only
N/A
T15
1618
41619
Trip button long press
Read Only
N/A
T15
1619
41620
Reset button
Read Only
N/A
T15
1620
41621
Reset button long press
Read Only
N/A
T15
1621
41622
Link trip
Read Only
N/A
T15
1622
41623
Link command inhibit
Read Only
N/A
T15
1623
41624
Link command trip
Read Only
N/A
T15
1624
41625
Link command reset
Read Only
N/A
T15
1625
41626
Modbus command inhibit
Read Only
N/A
T15
1626
41627
Modbus command trip
Read Only
N/A
T15
1627
41628
Modbus command reset
Read Only
N/A
T15
1628
41629
Test or USB active
Read Only
N/A
T15
1629
41630
State timeout
Read Only
N/A
T15
1630
41631
Error timeout
Read Only
N/A
T15
1631
41632
State done
Read Only
N/A
T15
1632
41633
Trip log complete
Read Only
N/A
T15
1633
41634
Link command service
Read Only
N/A
T15
1634
41635
Link command online
Read Only
N/A
T15
1635
41636
Modbus command service
Read Only
N/A
T15
1636
41637
Modbus command online
Read Only
N/A
T15
1637
41638
Error link
Read Only
N/A
T15
1638
41639
Error task failed
Read Only
N/A
T15
1639
41640
Error power failure
Read Only
N/A
T15
1640
41641
Error IGBT missing voltage
Read Only
N/A
T15
1641
41642
Error sensor power failure
Read Only
N/A
T15
1642
41643
Link command error
Read Only
N/A
T15
1643
41644
Link command setup
Read Only
N/A
T15
1644
41645
Trip button
Read Only
N/A
T15
1645
41646
Output trip momentary command
Read Only
N/A
T15
1646
41647
CB closed feedback
Read Only
N/A
T15
1647
41648
CB clearing failure
Read Only
N/A
T15
1648
41649
Current detect for CB failure
Read Only
N/A
T15
1649
41650
Currently AC powered
Read Only
N/A
T15
1650
41651
Currently DC powered
Read Only
N/A
T15
1651
41652
Read Only
N/A
T15
1652
41653
Read Only
N/A
T15
1653
41654
Read Only
N/A
T15
T15
1654
41655
Local CB tripped in this event
Upstream CB tripped via Service
relay
Upstream CB tripped via Tripped
relay
Local CB tripped via Service relay
Read Only
N/A
1655
41656
Local CB tripped via Tripped relay
Read Only
N/A
T15
1656
41657
Link alarm sent due to Light
Read Only
N/A
T15
www.littelfuse.com
• © 2013 Littelfuse •
• 63/84
PGR-8800 Arc-Flash Relay
PGR-8800
REGISTER
(DECIMAL)
MODBUS
REGISTER DESCRIPTION
(DECIMAL)
1657
41658
1658
41659
Link alarm sent due to Trip
Link alarm sent due to Trip fault tripped Upstream
Rev. 3-A-112913
ACCESS
TERMINAL
TYPE
Read Only
N/A
T15
Read Only
N/A
T15
Error Flags
1700
41701
Number of status flags available
Read Only
N/A
16-bit word, always 58
1701
41702
Not used
Read Only
N/A
T15
1702
41703
Sensor 1
Read Only
N/A
T15
1703
41704
Sensor 2
Read Only
N/A
T15
1704
41705
Sensor 3
Read Only
N/A
T15
1705
41706
Sensor 4
Read Only
N/A
T15
1706
41707
Sensor 5
Read Only
N/A
T15
1707
41708
Sensor 6
Read Only
N/A
T15
1708
41709
Sensor front
Read Only
N/A
T15
1709
41710
Analog OR of all sensors
Read Only
N/A
T15
1710
41711
Current inhibit
Read Only
N/A
T15
1711
41712
Current overload 1
Read Only
N/A
T15
1712
41713
Current overload 2
Read Only
N/A
T15
1713
41714
Not used
Read Only
N/A
T15
1714
41715
Inhibit input
Read Only
N/A
T15
1715
41716
Trip input
Read Only
N/A
T15
1716
41717
Reset input
Read Only
N/A
T15
1717
41718
Mode button
Read Only
N/A
T15
1718
41719
Trip button long press
Read Only
N/A
T15
1719
41720
Reset button
Read Only
N/A
T15
1720
41721
Reset button long press
Read Only
N/A
T15
1721
41722
Link trip
Read Only
N/A
T15
1722
41723
Link command inhibit
Read Only
N/A
T15
1723
41724
Link command trip
Read Only
N/A
T15
1724
41725
Link command reset
Read Only
N/A
T15
1725
41726
Modbus command inhibit
Read Only
N/A
T15
1726
41727
Modbus command trip
Read Only
N/A
T15
1727
41728
Modbus command reset
Read Only
N/A
T15
1728
41729
Test or USB active
Read Only
N/A
T15
1729
41730
State timeout
Read Only
N/A
T15
1730
41731
Error timeout
Read Only
N/A
T15
1731
41732
State done
Read Only
N/A
T15
1732
41733
Trip log complete
Read Only
N/A
T15
1733
41734
Link command service
Read Only
N/A
T15
1734
41735
Link command online
Read Only
N/A
T15
1735
41736
Modbus command service
Read Only
N/A
T15
1736
41737
Modbus command online
Read Only
N/A
T15
1737
41738
Error link
Read Only
N/A
T15
1738
41739
Error task failed
Read Only
N/A
T15
1739
41740
Error power failure
Read Only
N/A
T15
1740
41741
Error IGBT missing voltage
Read Only
N/A
T15
1741
41742
Error sensor power failure
Read Only
N/A
T15
1742
41743
Link command error
Read Only
N/A
T15
1743
41744
Link command setup
Read Only
N/A
T15
www.littelfuse.com
• © 2013 Littelfuse •
• 64/84
PGR-8800 Arc-Flash Relay
PGR-8800
REGISTER
(DECIMAL)
MODBUS
REGISTER DESCRIPTION
(DECIMAL)
ACCESS
Rev. 3-A-112913
TERMINAL
TYPE
1744
41745
Trip button
Read Only
N/A
T15
1745
41746
Output trip momentary command
Read Only
N/A
T15
1746
41747
CB closed feedback
Read Only
N/A
T15
1747
41748
CB clearing failure
Read Only
N/A
T15
1748
41749
Current detect for CB failure
Read Only
N/A
T15
1749
41750
Currently AC powered
Read Only
N/A
T15
1750
41751
Currently DC powered
Read Only
N/A
T15
1751
41752
Read Only
N/A
T15
1752
41753
Read Only
N/A
T15
1753
41754
Read Only
N/A
T15
T15
1754
41755
Local CB tripped in this event
Upstream CB tripped via Service
relay
Upstream CB tripped via Tripped
relay
Local CB tripped via Service relay
Read Only
N/A
1755
41756
Local CB tripped via Tripped relay
Read Only
N/A
T15
1756
41757
Link alarm sent due to Light
Read Only
N/A
T15
1757
41758
Read Only
N/A
T15
1758
41759
Link alarm sent due to Trip
Link alarm sent due to Trip fault tripped Upstream
Read Only
N/A
T15
TYPES:
T1:
T2:
T3:
T4:
T5:
T6:
T7:
T8:
T9:
T10:
T11:
T12:
T13:
T14:
T15:
16-bit word, 0-1023, approx 35 lux/unit; Offset at 0 Klux is dependent on software revision
and sensor type.
16-bit word, 0-1023, approx 100 mA/unit; Offset at 0 A is approximately 512.
Reading: 0=Not detected; 1=Detected; 2=Not possible, old sensor.
In mV, nominally 26 V.
In mV, range 8-48 V. May wrap on systems not capable of reading unsigned 16 bit values.
In mV, range 20-28V.
In mV, nominally 5V.
In mV, nominally 4.5V.
Reading: 0=Online mode; 1=Service mode; Writing: 0=Set online mode;
1=Set service mode, writing only allowed if explicitly enabled in configuration.
Reading: 0=AC present; 1=DC present; 2=On battery power; 3=Battery low.
Reading: 0=No errors; 1=Error.
Reading: 0=Inactive; 1=Active; 2=Cable Broken.
Reading: 0=Inactive; 1=Active; 2=Cable Broken; Writing: 1=Reset trip (self-resets), writing
only allowed if explicitly enabled in configuration.
Reading: 0=Open; 1=Closed.
Reading: 0=Inactive; 1=Active.
www.littelfuse.com
• © 2013 Littelfuse •
• 65/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
APPENDIX C COORDINATED TRIPPING OF UPSTREAM BREAKERS
The PGR-8800 is designed to detect arc faults and trip the local circuit breaker, interrupting the
energy supply to the arc and clearing the fault.
This appendix explains how to configure the PGR-8800 to detect if the local circuit breaker failed to
operate, and to send a trip signal to the upstream breaker.
This appendix generally assumes that the reader is familiar with the standard operation and
configuration of the PGR-8800.
C.1 SYSTEM OVERVIEW
Circuit breaker failure detection is possible by using either an auxiliary contact from the local circuit
breaker or by using the current sensor inputs on the PGR-8800 to detect phase currents after the
local circuit breaker has been told to trip, or both.
The operation time of the local circuit breaker must be considered before the decision is made to
trip the upstream breaker. Selecting the correct delay is described in Section C.1.3.
In the case where the PGR-8800 has detected that the local circuit breaker failed to open, the
upstream breaker must be tripped. If an upstream PGR-8800 is already installed, the Link interface
can be used to send a trip signal to this unit. The advantages are that only a TIA-485 connection is
needed between units, and that a failure in the connection will be detected. This configuration is
described in Section C.2.2.
If the unit is configured as a stand-alone device, the Service and Tripped output relays can be
programmed to trip an upstream circuit breaker. See Section C.1.4.
C.1.1 Circuit Breaker Feedback Detection
An available auxiliary contact in a circuit breaker can be used to provide feedback of the main
contact positions. The PGR-8800 trip inputs (T1 or T2) can be configured to detect the circuit
breaker status. This function is programmed using the configuration software. See Section C.2.1
for a programming and wiring example.
C.1.2 Current Sensor Detection
The PGR-8800 current sensors can also be used to detect phase currents to verify if the local
circuit breaker has operated as expected. See Section C.2.3 for a programming and wiring
example.
C.1.3 Total Clearing Time
Several parameters are needed to estimate the total clearing time of a local and upstream circuit
breaker. The total clearing time is defined as:
Total Clearing Time = Arc Detection Delay + Local Circuit Breaker Operating Time + Output Delay
+ Upstream Circuit Breaker Operating Time
C.1.3.1 Arc Detection Delay
The PGR-8800’s default arc-flash detection time is one millisecond, but can be configured between
0 and 20,000 milliseconds (see section 12.2.5). This is referred to as arc detection delay. When
configured to 0 ms, the effective trip time is less than 0.8 ms.
www.littelfuse.com
• © 2013 Littelfuse •
• 66/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
C.1.3.2 Circuit Breaker Operating Time
Circuit breakers have a predetermined operating time, dependent on the type of circuit breaker.
Older circuit breakers have clearing times up to eight cycles, while modern circuit breakers are
able to open in one to five cycles. Refer to the specifications of the installed circuit breaker.
TABLE C.1 CIRCUIT BREAKER OPERATING TIMES
CIRCUIT BREAKER
OPERATING TIME
50 HZ
60 HZ
8 cycles
160 ms
133 ms
5 cycles
100 ms
83 ms
3 cycles
60 ms
50 ms
2 cycles
40 ms
33 ms
1½ cycles
30 ms
25 ms
1 cycle
20 ms
17 ms
C.1.3.3 Output Delay
An additional output delay can be caused by the switching time of the Service or Tripped
mechanical relays (five milliseconds), or the reaction time of an upstream PGR-8800 trip coil
output (when connected with the Link interface).
C.1.3.4 Total Clearing Time Examples
Total Clearing Time Example 1:
Two 3-cycle breakers at 50 Hz, with the upstream breaker tripped by the Tripped relay in the local
PGR-8800:
1 + 60 + 5 + 60 ms = 126 ms
Total Clearing Time Example 2:
Two 2-cycle breakers at 50 Hz, with the upstream circuit breaker tripped by an upstream PGR8800 connected via Link interface:
1 + 40 + 1 + 40 = 82 ms
C.1.4 Relay Output
For smaller systems, one of the relay outputs can be configured to trip the upstream circuit breaker
directly. The relay outputs are rated for pilot duty B300, and will trip most circuit breakers. See
Section C.2.1 for a programming and wiring example.
C.1.5 Link Output
The Link feature can be configured to trip an upstream PGR-8800. This uses the solid state highspeed trip coil output, which eliminates the delay from the mechanical relay. See Section C.2.2 for
a programming and wiring example.
www.littelfuse.com
• © 2013 Littelfuse •
• 67/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
C.1.6 PGA-1100 Diode Logic Unit
When several PGR-8800 protected zones are used and a common upstream circuit breaker should
be tripped if any of the downstream zones experience a local clearing failure, the upstream circuit
breaker may run out of inputs. The PGA-1100 Diode Logic Unit makes it possible to combine several
trip outputs to the common circuit breaker. See Section C.2.6.
C.2 APPLICATION AND CONFIGURATION
The PGR-8800 is not configured for tripping the upstream circuit breaker in the default
configuration shown below:
The configuration software hides the extra settings associated with Coordinated Tripping, as the
feature is not yet enabled.
C.2.1 Single PGR-8800 Configuration
Figure C.1 shows an incoming feeder with a circuit breaker, a bus bar, and a zone protected with a
PGR-8800. All sensors are downstream of the circuit breaker, but the upstream circuit breaker can
be tripped if a local circuit-breaker failure occurs.
www.littelfuse.com
• © 2013 Littelfuse •
• 68/84
PGR-8800 Arc-Flash Relay
+24
Rev. 3-A-112913
Incoming
Upstream
Circuit Breaker
Upstream Trip
Busbar to Other Zones
+24
Auxiliary
Contact
C/B
Feedback
Local Circuit
Breaker
Trip
Trip Tripped Trip
Input Relay Coil
PGR-8800
Sensor
Sensor
Sensor
FIGURE C.1. Single PGR-8800 Configuration.
In this application, a circuit breaker with an auxiliary contact provides a trip input signal.
The configuration software displays two warnings to configure a digital input as a feedback signal
from the circuit breaker auxiliary contact and to configure a relay output to trip an upstream circuit
breaker.
In the Tripped Output section, select Trip Upstream CB on Clearing Failure. This will remove the
associated warning message.
www.littelfuse.com
• © 2013 Littelfuse •
• 69/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
The trip coil on the upstream circuit breaker can now be connected to the Tripped output (terminals
54, 55, and 56). It is also possible to use the Service Output to trip the upstream circuit breaker.
On the Digital Inputs tab, set the Trip Input Main function to Circuit breaker feedback.
Select CB is closed when low (switch closed). When Trip Input T1 or T2 (terminal 41 and 42
respectively) is connected to Common (terminal 45), the monitored circuit breaker is determined to
be closed.
This will remove the warning message and the configuration can be saved.
www.littelfuse.com
• © 2013 Littelfuse •
• 70/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
Ensure the delay time for the local circuit breaker is set correctly for the circuit breaker type. The
default is a 2-cycle circuit breaker delay. See Section C.1.3.2 for instructions on how to determine
the circuit breaker operating time.
www.littelfuse.com
• © 2013 Littelfuse •
• 71/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
C.2.2 Dual PGR-8800 Configuration using Link Interface
The single line diagram shows an incoming feeder with a circuit breaker, a bus bar, and a zone
protected with a PGR-8800. The upstream circuit breaker can be tripped by the local PGR-8800
via the Link interface if the local circuit breaker fails to operate.
Incoming
+24
Upstream
Circuit Breaker
Trip
Busbar to Other Zones
Link
Sensor
Trip
Coil
Upstream
PGR-8800
+24
Link
Bus
Clearing
Failure
Sent through Link
Auxiliary
Contact
Local Circuit
Breaker
C/B
Feedback
Trip
Link
Trip
Input
Trip
Coil
Local
PGR-8800
Sensor
Sensor
FIGURE C.2. Dual PGR-8800 Configuration using Link Interface.
The local circuit breaker auxiliary contact feedback is configured as in Section C.2.1.
Configure the local PGR-8800 to use the Link Interface. The unit address must be unique, and the
number of linked units in the system must be configured.
Select Clearing Failure to allow the PGR-8800 to send the Link alarm signal to the upstream
PGR-8800.
The Received Link alarm signal trips this unit is not selected. This makes it possible to have
several downstream units trip a common upstream unit without tripping each other.
www.littelfuse.com
• © 2013 Littelfuse •
• 72/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
The unit controlling the upstream circuit breaker is configured to receive a link alarm. The
upstream PGR-8800 is configured to send a Link alarm signal, but in the current configuration, this
has no effect as the local PGR-8800 is not configured to receive the Link alarm.
The LINK cable wires must be connected to both units using terminals 37 and 38. The maximum
length and cable type is described in Section 11.
C.2.3 Single PGR-8800 Configuration with Current Sensor Input
The single line diagram in Fig. C.3 shows a local circuit breaker that does not have an available
feedback auxiliary contact. The current-sensor inputs can be configured to verify that the local
breaker successfully operated.
www.littelfuse.com
• © 2013 Littelfuse •
• 73/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
+24
Upstream
Circuit Breaker
Upstream Trip
Busbar to Other Zones
+24
Local Circuit
Breaker
Trip
Tripped Trip
Relay Coil
PGR-8800
5A Secondary Current Sensors
Sensor
Sensor
Sensor
FIGURE C.3. Single PGR-8800 Configuration with Current Sensor Input.
NOTE: In this application, it is important that the current sensors are placed so that they only
monitor current flowing through the local circuit breaker section. Otherwise, the upstream circuit
breaker could trip even though the local circuit breaker cleared the fault.
NOTE: It is critical for the correct function of this application that three current sensors are
connected.
In this case the current sensors are used as circuit feedback. This function is configured by
selecting the Detect clearing failure by current check box.
www.littelfuse.com
• © 2013 Littelfuse •
• 74/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
The warning message refers to the output method, which has not yet been configured.
Select the Detect clearing failure by current checkbox.
Rated nominal load current and CT transformation ratio should be set correctly. The rest of the
setup does not influence the clearing failure function.
The relay output is configured as described in Section C.2.1. The warning message will disappear
after selecting an output.
www.littelfuse.com
• © 2013 Littelfuse •
• 75/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
C.2.4 Dual PGR-8800 Configuration using Link Interface and Current Sensor Input
The single line diagram in Fig. C.4 shows an incoming feeder with a circuit breaker, a bus bar, and
a zone protected with an upstream PGR-8800. The upstream circuit breaker can be tripped in the
event of a local circuit breaker failure.
Incoming
+24
Upstream
Circuit Breaker
Trip
Busbar to Other Zones
Link
Sensor
Trip
Coil
Upstream
PGR-8800
+24
Link
Bus
Local Circuit
Breaker
Clearing
Failure
Sent through Link
Trip
Link
Trip
Coil
Local
PGR-8800
5A Secondary Current Sensors
Sensor
Sensor
FIGURE C.4. Dual PGR-8800 Configuration using Link Interface and Current Sensor Input.
Configure clearing failure as in Section C.2.3, and output as in Section C.2.2.
In this case the current sensors are used as circuit feedback. This function is configured by
selecting the Detect clearing failure by current check box.
www.littelfuse.com
• © 2013 Littelfuse •
• 76/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
The warning message refers to the output method, which has not yet been configured.
Select the Detect clearing failure by current checkbox.
The Rated Nominal load current and CT transformation ratio should be set correctly. The rest of
the setup does not influence the clearing failure function.
Configure the local PGR-8800 to use the Link Interface. The unit address must be unique, and the
number of linked units in the system must be configured.
Select Clearing Failure to allow the PGR-8800 to send the Link alarm signal to the upstream
PGR-8800.
The Received Link alarm signal trips this unit is not selected. This makes it possible to have
several downstream units trip a common upstream unit without tripping each other.
www.littelfuse.com
• © 2013 Littelfuse •
• 77/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
The unit controlling the upstream circuit breaker is configured to Receive Link alarm signal trips
this unit. The upstream PGR-8800 is configured to send a Link alarm signal, but in the current
configuration, this has no effect as the other downstream units are not configured to receive the
Link alarm.
The link cable must be connected to both units, using terminals 37 and 38. The maximum length
and cable type is described in the Section 14.
C.2.5 Configuration of Multiple Inputs and Outputs
It is possible to combine both input and output methods. For example, it is possible to use both the
current sensor inputs and a circuit breaker auxiliary signal to detect a clearing failure. The relay will
send the upstream trip signal if any of the criteria is met.
Likewise, it is possible to configure several outputs to react on a circuit breaker failure. The relay
will simultaneously energize the two possible output relays and the Link Alarm signal, if so
configured.
www.littelfuse.com
• © 2013 Littelfuse •
• 78/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
C.2.6 Tripping Common Upstream Circuit Breaker from Several Zones using
PGA-1100
+24
Incoming
Incoming
Circuit
Breaker
+24
Circuit
Breaker
PGA-1100
PGA-1100
Manual Trip
Manual Trip
Tie Circuit
Breaker
Busbar to Other Zones
+24
Circuit
Breaker
Trip
Trip
PGA-1100
Trip
Coil
Trip
Coil
PGR-8800
PGR-8800
Manual Trip
Sensor
Sensor
Fig. C.5. Tripping Common Upstream Circuit Breaker from Several Zones using PGA-1100.
Fig C.5 shows two incoming feeders and a tie breaker. Each incoming circuit breaker trip coil is
connected to an independent PGR-8800 through a PGA-1100 Diode Logic Unit. The tie breaker
trip coil is also connected to the trip coil of each PGR-8800 through a separate PGA-1100.
If a trip occurs at either PGR-8800, both the tie circuit breaker and the corresponding circuit
breaker will trip.
www.littelfuse.com
• © 2013 Littelfuse •
• 79/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
APPENDIX D SYSTEM PARAMETERS AND SETUP RECORD1
GENERAL INSTALLATION
SETTINGS
MIN
DEFAULT
MAX
1
9
9
MIN
DEFAULT
MAX
UNIT
COMMENTS
UNIT
PROGRAM SELECTION
Date installed
Operator
Front panel trip level (1-9)
Comment 1
Comment 2
PARAMETER AND
SETTINGS
GENERAL
System Name
Description of this unit
PGR-8800 Arc-Flash Relay
Date and Time
Synchronize to PC clock
Disabled
 Enabled
Disabled
OPTICAL SENSORS
Common Settings
Arc Detection time before tripping
LED flashes green when above
0 (effective
0.8)
50
1
20,000
ms
75
90
% Trip Level
Sensor 1
Sensor description
Sensor 1
Ignore sensor check errors
Disabled
Change configuration
No change
 Enabled
Disabled
 No change
 No sensor expected
 Sensor expected
Sensor 2
Sensor description
Sensor 2
Ignore sensor check errors
Disabled
Change configuration
No change
 Enabled
Disabled
 No change
 No sensor expected
 Sensor expected
Sensor 3
Sensor description
Sensor 3
Ignore sensor check errors
Disabled
Change configuration
No change
 Enabled
Disabled
 No change
 No sensor expected
 Sensor expected
Sensor 4
Sensor description
Sensor 4
Ignore sensor check errors
Disabled
Change configuration
No change
 Enabled
Disabled
 No change
 No sensor expected
 Sensor expected
Sensor 5
Sensor description
Sensor 5
Ignore sensor check errors
Disabled
Change configuration
No change
 Enabled
Disabled
 No change
 No sensor expected
 Sensor expected
Sensor 6
Sensor description
Sensor 6
Ignore sensor check errors
Disabled
Change configuration
No change
www.littelfuse.com
• © 2013 Littelfuse •
 Enabled
Disabled
 No change
 No sensor expected
 Sensor expected
• 80/84
PGR-8800 Arc-Flash Relay
PARAMETER AND
SETTINGS
MIN
DEFAULT
MAX
Rev. 3-A-112913
UNIT
PROGRAM SELECTION
Local Sensor
Sensor Description
Local Sensor
Local sensor causes trip
Disabled
 Enabled
Disabled
CURRENT SENSORS
Setup
Rated nominal load current
5
100
CT transformation ratio
5
100
Amperes
100,000 RMS on CT
Primary
Ratio x: 5 A
100,000
RMS
Current sensor mode
AC
 AC
DC
Enable current inhibit
Disabled
 Enabled
Disabled
Trip on Overcurrent 1
Disabled
 Enabled
Disabled
Trip on Overcurrent 2
Disabled
 Enabled
Disabled
Trip Inhibit (if enabled)
Inhibit function disables trips below
Overcurrent 1 Protection (if
enabled)
10
50
1,000
Trip on current above
150
150
1,000
1
500
20,000
150
150
1,000
1
500
20,000
Time delay
Overcurrent 2 Protection (if
enabled)
Trip on current above
Time delay
%
% of rated
current
ms
% of rated
current
ms
DIGITAL INPUTS
Inhibit Inputs
Function
Inhibit when low (switch
closed)
 Inhibit when low (switch
closed)
 Inhibit when low with circuit
check
 Inhibit when not low (switch
open)
 Disabled
Trip Inputs
Main function
Trip input
Function (with Trip Input main
function)
Trip the output when low
(switch closed)
Function (with circuit breaker
feedback)
CB is closed when low (switch
closed)
Trip on this input can be inhibited
Disabled
 Trip input
 Circuit breaker feedback
 Disabled
 Trip the output when low
(switch closed)
 Trip the output when low with
circuit check
 Trip the output when not low
(switch open)
 CB is closed when low (switch
closed)
 CB is closed when low with
circuit check
 CB is closed when not low
(switch open)
 Enabled
Disabled
Reset Inputs
Function
www.littelfuse.com
Reset when low (switch
closed)
• © 2013 Littelfuse •
 Reset when low (switch
closed)
 Reset when low with circuit
check
 Reset when not low (switch
open)
 Disabled
• 81/84
PGR-8800 Arc-Flash Relay
PARAMETER AND
SETTINGS
MIN
DEFAULT
MAX
Rev. 3-A-112913
UNIT
PROGRAM SELECTION
OUTPUTS
Trip Coil Output
Circuit breaker pulse time
 Shunt Coil (opens when
powered)
 Undervoltage coil (closed
when powered)
Shunt Coil (opens when
powered)
Circuit breaker type
1
1
5
seconds
Trip in service mode
Report an error if trip coil is not
detected
Coordinated Tripping
Disabled
 Enabled
Disabled
Enabled
 Enabled
Disabled
Detect clearing failure by trip input
Disabled
 Enabled
Disabled
Detect clearing failure by current
Maximum local circuit breaker
clearing time (if Coordinated
Tripping is enabled)
Service Output
Disabled
 Enabled
Disabled
0
Service output function
40
500
ms
Indicate service mode
 Indicate service mode
 Follow trip coil output
 Trip upstream circuit breaker
on clearing failure
Indicate that the unit tripped
 Indicate that the unit tripped
 Follow trip coil output
 Trip upstream circuit breaker
on clearing failure
Tripped Output
Tripped output function
COMMUNICATIONS
Link Interface
Is used for
 Nothing
 Linking multiple units
 MODBUS
Nothing
Link Configuration (if enabled)
Unit address
Number of linked units in the
system
1
1
4
1
1
4
Send Link alarm signal on
Received Link alarm signal trips
this unit
Link sends and receives the user
interface
Link sends and receives errors
MODBUS Configuration (if
enabled)
Unit address
Unit address
 Never
 Light above threshold
 Trip
 Clearing failure
Trip
Enabled
 Enabled
Disabled
Enabled
 Enabled
Disabled
Enabled
 Enabled
Disabled
2400
9600
Disabled
 1200
 4800
 19200
 None
 Even
 Enabled
Enable data logging
Disabled
 Enabled
Disabled
Enabled waveform capture (beta)
Disabled
 Enabled
Disabled
www.littelfuse.com
• © 2013 Littelfuse •
Baud rate
Parity
Allows writes via MODBUS
1
1
247
1,200
19,200
19,200
Even
Unit address
Odd
Disabled
ADVANCED
Logging
• 82/84
PGR-8800 Arc-Flash Relay
PARAMETER AND
SETTINGS
MIN
Internal Drives
Reset configuration drive to factory
default
Reset log drive to factory default
Configuration
Reset configuration to factory
defaults
DEFAULT
MAX
Rev. 3-A-112913
UNIT
PROGRAM SELECTION
Disabled
 Enabled
Disabled
Disabled
 Enabled
Disabled
Disabled
 Enabled
Disabled
NOTES:
1
Firmware reference 1.03.09.
www.littelfuse.com
• © 2013 Littelfuse •
• 83/84
PGR-8800 Arc-Flash Relay
Rev. 3-A-112913
APPENDIX E
PGR-8800 REVISION HISTORY
MANUAL RELEASE
DATE
MANUAL REVISION
November 29, 2013
3-A-112913
HARDWARE REVISION
(REVISION NUMBER ON
PRODUCT LABEL)
2.1
December 14, 2012
2
2
FIRMWARE REVISION
1.03.11
1.03.10
1.03.09
MANUAL REVISION HISTORY
Revision 3-A-112913
Section 3
Updated power supply information.
Section 4
Updated Figs. 6 and 8.
Section 14
Added EMC test specifications.
Section 15
Updated ordering information.
Appendix B
Updated Modbus database table.
Appendix E
Added revision history.
Revision 2
Significant manual update for most sections. Added UL certification.
HARDWARE REVISION HISTORY
Hardware Revision 2.1
Combines CE and UL conformance in the same PCB revision.
No changes in functionality, performance, or components.
Hardware Revision 2
Changed protection components for UL conformance.
Added screw fasteners to current sensor inputs.
FIRMWARE REVISION HISTORY
Firmware Revision 1.03.11
Added feature to keep circuit check running and visible when tripping in service mode is
selected and USB is inserted.
Firmware Revision 1.03.10
Added Internet Explorer support in event viewer.
Firmware Revision 1.03.09
Removed trip terminal from Link Sharing.
www.littelfuse.com
• © 2013 Littelfuse •
• 84/84