DRP-240 series

240W Single Output Industrial DIN RAIL Power Supply
DRP-240
series
■
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
..
SPECIFICATION
MODEL
OUTPUT
DRP-240-24
DRP-240-48
DC VOLTAGE
24V
48V
RATED CURRENT
10A
5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
RATED POWER
240W
240W
RIPPLE & NOISE (max.) Note.2 80mVp-p
150mVp-p
VOLTAGE ADJ. RANGE
48 ~ 53V
±1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 ±1.0%
LINE REGULATION
±0.5%
LOAD REGULATION
±1.0%
SETUP, RISE TIME
800ms, 40ms/230VAC
HOLD UP TIME (Typ.)
VOLTAGE RANGE
INPUT
24ms/230VAC
Note.5 85 ~ 264VAC
±0.5%
±1.0%
800ms, 40ms/115VAC at full load
24ms/115VAC at full load
120 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
0.96/230VAC
84%
0.99/115VAC at full load
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
2.8A/115VAC
1.4A/230VAC
LEAKAGE CURRENT
OVERLOAD
PROTECTION OVER VOLTAGE
85%
COLD START 27A/115VAC
45A/230VAC
<3.5mA / 240VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
54 ~ 60V
30 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
Shut down o/p voltage, recovers automatically after temperature goes down
WORKING TEMP.
-10 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
20 ~ 90% RH non-condensing
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
UL508, UL60950-1, TUV EN60950-1 approved
OTHERS
±0.03%/℃ (0 ~ 50℃
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
Compliance to EN55011,EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
289.9Khrs min. MIL-HDBK-217F (25℃)
125.5*125.2*100mm (W*H*D)
1.2Kg; 12pcs/15.5Kg/1.29CUFT
DIMENSION
PACKING
NOTE
-20 ~ +85℃, 10 ~ 95% RH
℃





File Name:DRP-240-SPEC 2014-06-13
DRP-240
240W Single Output Industrial DIN RAIL Power Supply
Mechanical Specification
Case No. 922A
series
Unit:mm
125.5
100
125.2
TB1
LED
3 2 1
TB2
4 3 2 1
Terminal Pin Number Assignment (TB1)
+V ADJ.
Pin No.
1
2
3
35
ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15
Assignment
FG
AC/N
AC/L
Terminal Pin Number Assignment (TB2)
Pin No.
1,2
3,4
Assignment
DC OUTPUT +V
DC OUTPUT -V
Block Diagram
fosc : 100KHz
EMI FILTER
&
RECTIFIERS
I/P
PFC
CIRCUIT
RECTIFIERS
&
FILTER
POWER
SWITCHING
FG
O.L.P.
+V
-V
CONSTANT
CURRENT
LIMITING &
DETECTION
CIRCUIT
PWM & PFC
CONTROL
O.V.P.
O.T.P.
Derating Curve
Output derating VS input voltage
100
100
230VAC
90
80
80
70
110VAC
LOAD (%)
LOAD (%)
60
40
20
60
50
40
-10
0
10
20
30
40
50 55 60
AMBIENT TEMPERATURE (℃)
70 (VERTICAL)
Vin: -- 230VAC
110VAC
85
100
110
135
155
230
264
INPUT VOLTAGE (V) 60Hz
File Name:DRP-240-SPEC 2014-06-13