Vizual® - Instruction Manual

VIZUAL
®
Installation and Operating Manual
For the Magnetic Level Indicator (MLI)
Magnetic
Level
Indication
7xxx
6xxx
5xxx
4xxx
3xxx
2xxx
1xxx
®
UNPACKING
Unpack the instrument carefully. Make sure all components
have been removed from the foam protection. Inspect all
components for damage. Report any concealed damage to
the carrier within 24 hours. Check the contents of the carton/crates against the packing slip and report any discrepancies to Magnetrol. Check the nameplate model number
(Model number/approvals as per inserted separate sheet) to
be sure it agrees with the packing slip and purchase order.
The Vizual® model number defines:
- The Magnetic Level Indicator.
- The Vizual® transmitter and/or switches: each of these
components have their own modelnumber that refers to
their own approvals (as per separate inserted documents).
Check and record the Vizual® serial number for future reference when ordering parts.
External mount switches/
transmitters partnumber
(for spare part / approval ref.).
Pre-installation checklist:
- Verify if the units’ center to center distance equals the
center to center distance of the vessel.
- Locate the external mounted switches/transmitters.
- Locate the float – separately packed.
Vizual® nameplate
* model number:
- Magnetic Level Indicator
- Switches and/or transmitters
* serial n°
* tag n°.
CAUTION: When handling units with longer measuring range, assure that these are supported over the entire
length to avoid bowing causing deformation / glass breakage.
MOUNTING – Magnetic Level Indicator
max 2°
max 2°
S.G.
Temp/Pressure
model ref.
Shut off valves
are recommended.
Remove bottom flange to install/remove float.
Mount always with
pointing upwards.
Note: The float is packed separately to protect against transport damage.
CAUTION: In case shut off valves are used, care must be taken when opening the valves to prevent a surge of
fluid and gases through the chamber. A surge can cause the float to be propelled to the far end of the chamber,
resulting in float damage.
2
MOUNTING – Magnetic Level Indicator
Assembly guidelines – switches/scale
Both sides can be
used to either mount
switches and or scale
Assembly guidelines – transmitter
➀
Optional springs
to protect the float
➁
Indicator rail
Reed chain
transmitter screwed
with clamps on
chamber.
Switches screwed
onto rail.
0 % marking
➀ Remove top cap to insert additional nuts.
➁ Fix switches at the desired switching point (see switching point marked on switch).
Switches/transmitter and scale can easily screwed on the
indicator rail. Simply, slide the fastening screws down on the
rail to the desired location and fasten with the locking
screws.
IMPORTANT: Floats are designed as per operating
conditions. It might occur that the float indication is
incorrect at the time of start up under ambient conditions.
WIRING – Transmitter
The Vizual® reed chain transmitter is pre-calibrated from factory
following the level indication of the MLI. The 4 mA setting is
marked on the chain and should correspond to the marking on the
MLI. Please consult factory if the measuring span needs to be
reset to other values than the default factory settings.
Cut away view
4 mA
marking
Customer supplied
local meter
0%
100 %
8-35 V DC
Ex Non Ex
Galvanic barrier for
intrinsically safe units
(not needed for GP)
Only terminals for + and - should be used for wiring up the device
in the field. Terminals 3, 4, 5 and 6 are for factory use only.
3
WIRING – Switches
Bi Stable reed switch
Hermetically sealed and vibrating resistant
micro switch
CAUTION: Power must be switched OFF before
wiring the unit.
The switch will actuate slightly above the center of the unit
and de-actuate slightly below the center of the unit.
Make sure that the switches are always properly retightened
on the indicator rail.
Switch rating @
24 V DC
CAUTION: Power must be switched OFF before
wiring the unit.
The switch will actuate slightly above the center of the unit
and de-actuate slightly below the center of the unit.
Make sure that the switches are always mounted as close
as possible to the indicator rail.
240 V AC
Switch rating @
24 V DC
240 V AC
Exi - simple apparatus 0,5 A
N/A
Exi
0,6 A
N/A
General Purpose - Exd 2 A
2A
General Purpose
0,8 A
0,8 A
Exm
0,6 A
0,6 A
Repeatability: < 2 mm (0,08")
Repeatability: < 2 mm (0,08")
NO (Brown)
NO
NC
NC (Blue)
C
C (Black)
MAINTENANCE
If the process liquid is clean (no solids or deposits), the MLI should require minimum maintenance. If the process liquid is dirty
(solids and deposits), it is recommended that the external cage be isolated from the process and flushed periodically. For complete cleaning, after draining the unit, remove the bottom flange and float, inspect cage and float for build up and clean if
required.
REPLACEMENT PARTS
➃
➁
Item
Part number
1
Float – provide S.G, model code on float and serial n° of MLI
–
2
Indicator rail
Consult factory
➂
Micro switches
Switches
➀
Transmitter
Last 3 digits specify measuring
range in 1 cm increments
➃
4
4
Reed switches
3
Body gasket
General Purpose
048-8510-003
Exi simple apparatus
048-8510-001
Exd
048-8508-001
General Purpose
048-8509-002
Exi
048-8509-001
Exm
048-8507-001
General Purpose
039-4052-xxx
Ex i
039-4053-xxx
Exd
039-4054-xxx
150 lbs
012-1301-027
300/
600 lbs
012-1301-028
TROUBLESHOOTING
Problem
Solution
Flags do not rotate with level change.
Test flags with a magnet from bottom to top (magnet not included). If
flags test O.K, check if float is present or for float obstruction (see
maintenance).
Switch does not actuate with level change.
Check switch for continuity. Replace if damaged, if O.K, remove switch
from piping column and test switch magnet assembly with re-alignment
magnet, by moving magnet over the housing face. If the switch magnet
assembly fails to respond, replace the switch. If the switch checks O.K,
check float travel.
Reed transmitter does not track level.
Remove transmitter assembly from piping column and test with realignment magnet. Run magnet from bottom to top of reed chain.
Check zero and span calibration. If no change in output, replace.
Flags rotate at different height than actual
level.
Float selected for different specific gravity. Replace float with a float
with correct specific gravity rating. Confirm correctness of float orientation. Top is up.
Float inside the level gauge is moving slowly
or not at all.
Make sure the MLI is levelled vertically.
The process fluid being measured may be too viscous and heat tracing
may be required to make the material more fluid.
The specific gravity of the process fluid and the float weight may need
to be reverified.
The liquid being measured may contain magnetic particles collecting on
the magnetic section of the float causing drag.
Visual inspection of the float may be required to see if the float has collapsed.
Scale is at zero to the center of the bottom
process connection, but the indicator is
above or below zero.
The scale assembly is mounted to the chamber using stainless steel
gear clamps. It can be easily adjusted in the field using a screwdriver.
Make sure the scale zero is in line with the center of the process connection.
PHYSICAL SPECIFICATIONS
Description
Measured value
Density range
Measuring range
Indicator
Resolution
Scale (Optional)
Materials
Process connections
Design standards
Hydro test
Specification
Liquid level and liquid-liquid interface
Standard models: min S.G. 0,56 - max S.G. 1,5 - Consult factory for different S.G.’s
Interface units: min. S.G. difference between upper and lower liquid > 0,1 (consult factory
for smaller differences)
From 30 cm (12") up to 570 cm (224"). Consult factory for longer lengths
≤ +250 °C (+480 °F): Polycarbonate window / aluminium rail / SST flags
> +250 °C (+480 °F): Glass window / aluminium rail / SST flags
Red-white flags (optional float failure warning: blue-white)
10 mm (0.4") - height of flapper
In cm or tailor made (at request) in 304 stainless steel
Cage/Flanges: 316/316L stainless steel
Float: 316 Ti SST (1.4571) standard. Titanium for custom made floats
Threaded, socket welded or flanged (ANSI - EN/DIN)
In compliance to PED regulations and essential safety requirements
1,5 x operating pressure (without float)
5
ELECTRICAL SPECIFICATIONS
Description
Specification
Micro switch
Switch ratings
Reed switch
Switches
Transmitter
Approvals
Micro switch
Temperature ranges
Reed switch
Reed chain
transmitter
Micro switch
Reed switch
Housing
0,5 A / 30 V A / 20 W
240 V AC
2 A / 100 V A / 40 W
– Exi (simple apparatus)
– General Purpose / Exd
24 ... 240 V AC / V DC
0,8 A / 60 V A / 40 W
0,6 A / 45 V A / 45 W
– General Purpose
– Exm/Exi
< 2 mm (0.08")
Switch Repeatability
Signal output
24 ... 240 V AC / V DC
Reed chain
transmitter
SPDT micro-switches (optional DPDT), bi-stable SPDT reed switches
8-30 V DC Loop powered transmitter: reed chain type: 4-20 mA output (opt. HART®)
Accuracy: < 5 mm.
LRS (marine applications)
ATEX II 1G EEx ia II C T6, intrinsically safe (for reed chain transmitters)
ATEX II 2G EEx d II C T6, explosion proof (for micro switches)
ATEX II 2G EEx ia II C T6, intrinsically safe (for reed switches)
ATEX II 2G EEx m II C T6 (for reed switches)
-50 °C to +380 °C (-55 °F to +715 °F) – General Purpose / Exi (simple apparatus)
-50 °C to +300 °C (-55 °F to +570 °F) – Exd
-25 °C to +75 °C (-10 °F to +165 °F) – General Purpose
-25 °C to +85 °C (-10 °F to +185 °F) – Exm/Exi
-40 °C to +150 °C (-40 °F to +300 °F) – General Purpose
-40 °C to +120 °C (-40 °F to +250 °F) – Exi/Exd (higher temp. at request)
IP 65, Aluminium with M20 x 1.5 cable entry (cable gland incl.) – GP/Exi (simple apparatus)
IP 65, Cast aluminium with dual 3/4" NPT cable entries – Exd
IP 67, Polyamide with flying leads (5 m of cable included) – General Purpose
IP 67, Cast aluminium with flying leads (5 m of cable included) – Exm/Exi
IP 67, ABS with M16 x 1.5 cable entry (cable gland included) – General Purpose / Exi
IP 65, Cast aluminium with 1/2" NPT cable entry – Exd
MOUNTING CONFIGURATIONS AND DIMENSIONS in mm (inches)
120
(4.72)
100
(3.94)
measuring
range
measuring
range
120
(4.72)
measuring
range
±250➀
(9.84)
GU Type
Top-Bottom
6
±250➀
(9.84)
GR Type
Side-side
GS Type
Side-side
Depending float size.
measuring
range
±250➀
(9.84)
±250➀
(9.84)
➀
100
(3.94)
GT Type
Top-Bottom
100
(3.94)
measuring
range
±250➀
(9.84)
GA Type
Side-Bottom
120
(4.72)
measuring
range
±250➀
(9.84)
GB Type
Side-Bottom
MODEL IDENTIFICATION
A complete measuring system consists of:
1
Code for Vizual® MLI cage (for modified models or adders, put an “X” in front of the closest matching order code and
X = with material certification EN 10204-3.1
specify the modifications separately. E.g. XGSD-H23F-120
2. Always specify operating temperature/ pressure/ S.G. and viscosity if > 80 cP
3. Code for options:
- Reed chain transmitter / Micro-switches / Bi-stable (reed type) switches: consult factory
- Scale: standard 304 stainless steel
Code: 032-3930-xxx: scale in cm. Consult factory for tailor made scales
3-last digits represent the measuring range in cm increments (e.g. 120 = 120 cm)
BASIC MODEL NUMBER - ANSI CLASS CAGES IN 316/316L (1.4401/1.4404) - FLANGES AND CAGE
G
G
G
G
G
G
A
B
S
R
T
U
Side/bottom process connection with sealed top cap
Side/bottom process connection with flanged top
Side/Side process connection with sealed top cap
Side/Side process connection with flanged top
Top/bottom process connection with sealed top cap
Top/bottom process connection with flanged top
SPECIFIC GRAVITY RANGE AND FLOAT HYDROTEST PRESSURE➀
ALWAYS SPECIFY EXACT OPERATING S.G, max temp & pressure when ordering Vizual
Hydrotest 36 bar @ +40 °C
Hydrotest 52 bar @ +40 °C
Hydrotest 85 bar @ +40 °C
A
0,56 to 0,60
F
0,58 to 0,61
M
0,62 to 0,70
B
0,61 to 0,70
G
0,62 to 0,70
N
0,71 to 0,80
C
0,71 to 0,80
H
0,71 to 0,80
O
0,81 to 0,90
D
0,81 to 0,90
J
0,81 to 0,90
P
0,91 to 1,50
E
0,91 to 1,50
K
0,91 to 1,50
➀
Consult factory for low S.G, interface applications or high pressure floats
MATERIALS OF CONSTRUCTION
CAGE & FLANGES: 316/316L (1.4401/1.4404) – FLOAT: 316 Ti (1.4571) except code A: Titanium
Indication rail without scale ➀
Aluminium rail / SST flappers / Polycarbonate window
Aluminium rail / SST flappers / Polycarbonate window
Aluminium rail / SST flappers / Polycarbonate window
Aluminium rail / SST flappers / Polycarbonate window
Aluminium rail / SST flappers / Glass window
Aluminium rail / SST flappers / Glass window
Aluminium rail / SST flappers / Glass window
H
J
K
L
M
N
P
➀
Temperature range
-20 °C upto +160 °C (-5 °F upto +320 °F)
-50 °C upto +125 °C (-60 °F upto +260 °F)
-20 °C upto +200 °C (-5 °F upto +390 °F)
-20 °C upto +250 °C (-5 °F upto +480 °F)
-20 °C upto +300 °C (-5 °F upto +570 °F)
-20 °C upto +350 °C (-5 °F upto +660 °F)
-20 °C upto +400 °C (-5 °F upto +750 °F)
See options for scales
PROCESS CONNECTION: SIZE
0
1
2
3
4
1/2"
3/4"
1"
1 1/2"
2" ➀
➀
Z
A
B
C
D
DN
DN
DN
DN
DN
15
20
25
40
50
➀
2"/DN 50 process flanges are machined to 1" size
PRESSURE RATING - FLANGE TYPE (if applicable)
EN/DIN
ANSI
3
150 lbs - RF flange
PN
A
4
300 lbs - RF flange
PN
B
5
600 lbs - RF flange
PN
D
E
PN
16
25/40
63
100
EN
EN
EN
EN
1092-1
1092-1
1092-1
1092-1
B1
B1
B2
B2
flange
flange
flange
flange
PROCESS CONNECTION: STYLE
N
S
F
NPT-F coupling (size: max 1")
Socket weld coupling (size: max 1")
Flanged (all sizes)
MEASURING RANGE (as per drawings at left page) – per 1 cm (0.39") increments
minimum 30 cm (12")
0 3 0
5 7 0
maximum 570 cm (224")
Note: segmented cage for lengths > 570 cm (224"), consult factory
G
complete code for Vizual® Magnetic Level Indicator
7
IMPORTANT
SERVICE POLICY
Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or
replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to
the purchaser, (or owner) other than transportation cost if:
a. Returned within the warranty period; and,
b. The factory inspection finds the cause of the malfunction to be defective material or workmanship.
If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be charges for labour
and the parts required to rebuild or replace the equipment.
In some cases, it may be expedient to ship replacement parts; or, in extreme cases a complete new control, to replace the
original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the
control to be replaced. In such cases, credit for the materials returned, will be determined on the basis of the applicability of
our warranty.
No claims for misapplication, labour, direct or consequential damage will be allowed.
RETURNED MATERIAL PROCEDURE
So that we may efficiently process any materials that are returned, it is essential that a “Return Material Authorisation” (RMA)
form will be obtained from the factory. It is mandatory that this form will be attached to each material returned. This form is
available through Magnetrol’s local representative or by contacting the factory. Please supply the following information:
1.
2.
3.
4.
5.
6.
Purchaser Name
Description of Material
Serial Number and Ref Number
Desired Action
Reason for Return
Process details
All shipments returned to the factory must be by prepaid transportation. Magnetrol will not accept collect shipments.
All replacements will be shipped FOB factory.
BULLETIN N°:
EFFECTIVE:
SUPERSEDES:
UNDER RESERVE OF MODIFICATIONS
www.magnetrol.com
®
BE 46-637.2
APRIL 2007
March 2004
BENELUX
Heikensstraat 6, 9240 Zele, België
Tel. +32 (0)52.45.11.11 • Fax. +32 (0)52.45.09.93 • E-Mail: [email protected]
DEUTSCHLAND
Alte Ziegelei 2-4, D-51491 Overath
Tel. 02204 / 9536-0 • Fax. 02204 / 9536-53 • E-Mail: [email protected]
FRANCE
40 - 42, rue Gabriel Péri, 95130 Le Plessis Bouchard
Tél. 01.34.44.26.10 • Fax. 01.34.44.26.06 • E-Mail: [email protected]
ITALIA
Via Arese 12, I-20159 Milano
Tel. (02) 607.22.98 (R.A.) • Fax. (02) 668.66.52 • E-Mail: [email protected]
UNITED
KINGDOM
Unit 1 Regent Business Centre, Jubilee Road Burgess Hill West Sussex RH 15 9TL
Tel. (01444) 871313 • Fax (01444) 871317 • E-Mail: [email protected]
INDIA
E-22, Anand Niketan, New Delhi - 110 021
Tel. 91 (11) 41661840 • Fax 91 (11) 41661843 • E-Mail: [email protected]