XMC0 Series

XMC0 Series
Definite Purpose Contactors
Description
Hongfa’s Definite Purpose
Contactor XMC0 meets the
rigorous demands of the HVAC,
refrigeration, heating, data
processing, welding, elevators,
hoist & cranes, pool, commercial
spa, and food service equipment industries. The contactor series meet and exceed the
requirements for IEC 60947-4-1, GB 14048.4, UL 508, UL 60947-4-1, and UL 1995.
Features
1. Tools-free accessories for quick & easy snap on assembly.
2. Various terminal options for specific application.
3. Universal mounting plate.
4. Heavy duty Silver Metal Oxide contacts to provide long electrical endurance.
5. Class F (155°C) Coil insulation systems with a broad range of 50/60Hz voltage offerings.
6. Protective coil cover option available for the 1 & 2 pole contactors.
7. UL(USR/CNR) and CCC approved, some models SEMKO, KETI or TÜV plus.
Environmental characteristics
Protective treatment
Total climate tropical use “TH”
Vertical or Horizontal
(Metal/Plastic base mounting)
Operating position
Ambient temperature
Relative humidity
Pollution degree
Operation
-40°C~+70°C/ -40°F~+158°F
Storage
-40°C~+70°C / -40°F~+158°F
90-95%RH at 40°C
3
Type model nomenclature - Ordering Information
XMC 0 - 50 J33 . E B B C 0
0 F G Z X
Option
Product Type
XMC = Contactor Series
Design Sequence Number
0 = Design Sequence Number
Customer assigned suffix "X"
where "X" may be any alphanumeric
character or any combined
alphanumeric character.
Full Load Amperes (FLA)
20 = 20A (Same as 25A)
25 = 25A
32 = 32A
40 = 40A
50 = 50A
63 = 63A
75 = 75A
90 = 90A
Contact construction style
(For 50/63 FLA only)
Blank = Flat construction in shape
Z = Bend construction in shape(No
"Break All Lines" restriction)
Number of Poles
Power Quick Terminals
1 = 1-pole+shunt
2 = 2-pole
7 = 1-pole
3 = 3-pole
3A = 2-pole (3P frame)
Jmn = Matching mechanically interlocked block
(3P frame). "m" = 2 or 3, number of poles of the
contactor A(on the left) and "n" = 2 or 3, number
of poles of the contactor B(on the right).
Blank = Quad Terminals in 1- and 2- pole
models and Dual Terminals in 3-pole models
G = None QC Terminals
Q = Quad Terminals in 3-pole models (Only
the side no coil terminals)
Notes:
1.Quantum series only available for 3, 3A or Jmn.
2.Please contact us if you have any other request.
Coil Voltage
E = 24VAC 50/60Hz
F = 110-120VAC 50/60Hz
I = 208-220VAC 50Hz
208-240VAC 60Hz
L = 277VAC 60Hz
N = 380-415VAC 50Hz
440-480VAC 60Hz
U = 550-600VAC 50/60Hz
Note: Please contact us if you have any other request.
Mounting plate
B = Metal plate
Blank = Quantum series - Serviceable /metal plate
Top Cover
B = Short cover
Blank = Quantum series - Serviceable /short cover
Power Terminals
C = Slotted & Hex head washer w/ quick connect
D = Box Lug w/ quick connect
E = Box lug w/ quick connect (Line side)
Slotted & Hex head washer w/ quick connect (Load side)
F = Slotted & Hex head washer w/ quick connect (Line side)
Box lug w/ quick connect (Load side)
Note: Please contact us if you have any other request.
Coil Terminals
Blank = Dual QC without screw in 1- and 2- pole
models and Single QC with screw in 3-pole models
F = Dual QC in 3-pole models
Auxiliary Contacts or
Microswitch on Left Side
(For 3-pole only)
Auxiliary Contacts or
Microswitch on Right Side
(For 3-pole only)
0 = None (Standard Type)
1 = 1NC + 1NO, 0.250" quick
connect terminal
3 = 1NC, 0.250" quick connect
terminal
4 = 1NO, 0.250" quick connect
terminal
5 = 2NC, 0.250" quick connect
terminal
6 = 2NO, 0.250" quick connect
terminal
1P = 1NC + 1NO, pressure plate
screw
3P = 1NC, pressure plate screw
4P = 1NO, pressure plate screw
5P = 2NC, pressure plate screw
6P = 2NO, pressure plate screw
L = 2 SPDT
L1 = 1 SPDT, left side(position 1)
of microswitch block
L2 = 1 SPDT, right side(position
2) of microswitch block
0 = None (Standard Type)
1 = 1NC + 1NO, 0.250" quick
connect terminal
3 = 1NC, 0.250" quick connect
terminal
4 = 1NO, 0.250" quick connect
terminal
5 = 2NC, 0.250" quick connect
terminal
6 = 2NO, 0.250" quick connect
terminal
1P = 1NC + 1NO, pressure plate
screw
3P = 1NC, pressure plate screw
4P = 1NO, pressure plate screw
5P = 2NC, pressure plate screw
6P = 2NO, pressure plate screw
R = 2 SPDT
R1 = 1 SPDT, left side(position
1) of microswitch block
R2 = 1 SPDT, right side(position
2) of microswitch block
For example:
34P = 1NC 0.250" quick connect terminal on left side
1NO pressure plate screw on right side
LR1 = 2 SPDT on left side
1 SPDT(position 1 of microswitch block) on right side
3R2 = 1NC 0.250" quick connect terminal on left side
1 SPDT(position 2 of microswitch block) on right side
Note: If "00" will be the final digits in selection, omit from model
nomenclature.
Type model nomenclature - Ordering Information
Auxiliary Contact Blocks:
C03 A 11 P Q X
Basic Designation
C03 = For XMC0 3P Series Definite Purpose Contactors.
Accessory Category
A = Auxiliary Contacts Block
01 = 1NC
10 = 1NO
Contact Type
11 = 1NC + 1NO
02 = 2NC
20 = 2NO
Note: NC = Normally Closed, NO = Normally Opened.
Quick Connect Terminals
Blank = 0.250" quick connect terminals
P = Pressure plate screw(None QC terminals)
Used Function
Blank = Match with 3P Contactor
Q = Match with Quantum series
Option
Customer assigned suffix "X" where "X" may be any alphanumeric character or any
combined alphanumeric character.
Microswitch Blocks:
C03 M 10 Q X
Basic Designation
C03 = For XMC0 3P Series Definite Purpose Contactors.
Accessory Category
M = Microswitch Block
Contact Type
Microswitch at Left side(position 1) for Microswitch at Right side(position
Microswitch Assembly
2) for Microswitch Assembly
0 = None
1 = 1 SPDT
3 = 1 SPST-NC
4 = 1 SPST-NO
0 = None
1 = 1 SPDT
3 = 1 SPST-NC
4 = 1 SPST-NO
Note: SPDT = Single Pole Double Throw, SPST = Single Pole Single Throw,
NC = Normally Closed, NO = Normally Opened.
Used Function
Blank = Match with 3P Contactor
Q = Match with Quantum series
Position 1
Option
Customer assigned suffix "X" where "X" may be any alphanumeric character or
any combined alphanumeric character.
Interlock Blocks:
C03 J 1Q X
Basic Designation
C03 = For XMC0 3P Series Definite Purpose Contactors.
Accessory Category
J = Mechanically Interlocked Block
0 = Match with 25-40A
1 = Match with 50-63A
Interlock Type
2 = Match with 75-90A
1Q = Match with 25-63A(Quantum series)
Option
Customer assigned suffix "X" where "X" may be any alphanumeric character
or any combined alphanumeric character.
Position 2
Pole Characteristics
Full Load
Amps(FLA)
Poles
25
1
32
1
40
1
25
2
32
2
40
2
25
2
3
32
2
3
40
2
3
50
2
3
63
2
3
50
2
3
63
2
3
75
2
3
90
2
3
Voltage
Locked Rotor
Amps (LRA)
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
150
180
150
120
240
150
125
100
180
150
120
240
200
160
150
125
100
180
150
120
240
200
160
300
250
200+
360
300
240+
300
250
200
360
300
240
450
375
300
540
450
360
Maximum Horsepower(HP)
Resistive amps
rating (RES)
Voltage
Single
Phase
Three
Phase
35
240/277
2
-
XMC0-257*
XMC0-251*
40
240/277
2
-
XMC0-327*
XMC0-321*
50
240/277
3
-
XMC0-407*
XMC0-401
35
240/277
3
-
XMC0-252*
40
240/277
3
-
XMC0-322*
50
240/277
3
-
XMC0-402*
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
3
3
5
5
7.5
5
7.5
15
15
-
5
7.5
10
7.5
10
15
10
15
20
15
20
25
20
25
30
15
20
25
20
25
30
25
40
40
30
50
50
35
40
50
63
75
63
75
94
120
Catalog
Number
XMC0-253A*
XMC0-253*
XMC0-323A*
XMC0-323*
XMC0-403A*
XMC0-403*
XMC0-503A*
XMC0-503*
XMC0-633A*
XMC0-633*
XMC0-503A*Z
XMC0-503*Z
XMC0-633A*Z
XMC0-633*Z
XMC0-753A*
XMC0-753*
XMC0-903A*
XMC0-903*
Notes:
1. All the models also could be marked or used for the actual applications which have less contact ratings than the certificated
ratings. The rating can be Voltage, FLA, LRA or RES.
2. All the ratings have not “Break All Lines” restriction, except the rating “600VAC 50FLA/200LRA” for “XMC0-50 without Z” and
“600VAC 63FLA/240LRA” for “XMC0-63 without Z”.
3. Contact factory representative for Cd free option.
-4-
Auxiliary contacts block characteristics
Contact Rating - Single
Circuit NO or NC and
Two Circuit NO/NC
Voltage Rating
120VAC
240VAC 480VAC
600VAC
Amperes - Break
3.0
1.5
0.75
0.6
Amperes - Make
30
15
7.5
6
Amperes - Thermal
continuous
10
10
10
10
Microswitch Blocks characteristics
10A or 11A, 1/3 HP, 125 or 250 VAC
1/2A, 125 VDC; 1/4A, 250 VDC
4A 120 VAC on Lamp Load
Contact Rating - SPDT
Note: Please contact us if you have any other request.
Coil characteristics @ 25℃(Cold state)
Part number
Max. Inrushed VA
60Hz
50Hz
Max. Sealed VA
60Hz
50Hz
Sealed Watts
60Hz
XMC0-□1/7
40
55
7.5
10
3
XMC0-□2
45
55
8
10.5
3.5
XMC0-□3/3A
XMC0-503/633
XMC0-753/903
80
145
300
90
160
325
12
17.6
35
16
23
46
5
7
12
Voltage
Pick-up Drop-out
≤0.8Us
≥0.2Us
Notes:
1. Us=24VAC 50/60Hz(“E“coil) or 120VAC 50/60Hz(“F“coil) or 220VAC/50Hz, 240VAC/60Hz(“I“coil) or
277VAC/60Hz(“L“ coil) or 415VAC/50Hz, 480VAC/60Hz(“N“coil).
2. Inrushed VA and Sealed VA test at Us.
-5-
Outline Dimensions
1 pole (metal plate, 25-40FLA, w/o coil cover)
1 pole (metal base, 25-40FLA, with coil cover)
-6-
1 pole+shunt (metal base, 25-40FLA, w/o coil cover)
1 pole+shunt (metal base, 25-40FLA, with coil cover)
-7-
2 pole (metal base, 25-40FLA, w/o coil cover)
2 pole (metal base, 25-40FLA, with coil cover)
-8-
3 pole (metal base, 25-40FLA) - Quantum series
3 pole (metal base, 25-40FLA)

-9-
3 pole (metal base, 50-63FLA) - Quantum series
3 pole (metal base, 50-63FLA)

- 10 -

3 pole (metal base, 75-90FLA)
Auxiliary Contact Blocks - Used for Quantum series
Auxiliary Contact Blocks
Microswitch Blocks - Used for Quantum series
Microswitch Blocks
Interlock Blocks - Used for Quantum series
Interlock Blocks
- 11 -
Wiring diagram
Contactors:
XMC0-□7
XMC0-□1
XMC0-□2
XMC0-□3
Auxiliary Contact Blocks:
1NC
1NC + 1NO
1NO
2NC
2NO
Remarks:
1) Torque for Screws 25 lb-in /Lugs 25 lb-in for 25-40FLA types;
Torque for Screws 45 lb-in /Lugs 50 lb-in for 50-63FLA types;
Torque for Screws 50 lb-in /Lugs 60 lb-in for 75-90FLA types;
Torque for Screws 8 lb-in for Auxiliary Contact Blocks;
Torque for Coil Screws 8 lb-in for 3-pole 25-40FLA types and 12 lb-in for 50-90FLA types.
2) For QC wiring, the female connector should meet IEC 60760, necessary to ensure the reliability of connection between
female connectors and QC terminals.
3) If the actual condition differs from this specification, please contact us for further discussion.
- 12 -