RLY400 Series - NTE Electronics

RLY400 Series
Features
•
•
•
Straight Through Wiring
Heavy Duty
Universal Mounting Plate
Definite Purpose, 3PST−DM, 25 Amp,
Magnetic Contactors
D79
3.750 (95.3)
3.250 (82.55)
.500
(12.7)
Dia
1.500
(38.1)
2.050
(52.1)
2.500
(63.5)
2.150
(54.61)
.210 (5.33) x .450 (11.43)
2.750 (69.85)
3.140
(79.76)
LINE
LOAD
.832
(21.13)
1.610 (40.89)
Electrical Specifications
AC OPERATED
Coils
Input
Voltage
Nom.
Power
Contact
Arr.
Max.
Contact
Cur. @
600VAC
120 VAC
10 VA
3PST−DM
25A
NTE Type No.
RLY455
Contacts
Motor Rating in Amps
Full Load
Diag
No.
D79
Resistive
Rating
(Elect. Heat)
Locked Rotor
@ 600VAC
@ 240VAC
@ 480VAC
@ 600VAC
@ 600VAC
25A
150A
125A
100A
30A
Motor Type
@ 240VAC
@ 240VAC
@ 440−600VAC
1∅2P
1.5 HP
3.0 HP
−
3∅3P
3.0 HP
7.5 HP
10 HP
Power . . . . . . . . . . . . Inrush: 40VA
Steady State: 10VA
Duty: Continuous
Operational Characteristics
Insulation Characteristics
Initial Breakdown Voltage: 2200V RMS
Environmental Characteristics
Operating: −55°C to +65°C
ACCESSORIES
NTE
TYPE NO.
Dual .250” Quick Connect Terminals
RLY9201
Box Lug
RLY9204
Replacement Contacts
RLY9205
Auxiliary Switch
RLY9206
94
Coil
Timing Value . . . . . . Operate Time: 25 mS
Release Time: 25 mS
Motor Horsepower Ratings
DESCRIPTION
Tungsten Lamp Rating: 30A, 277VAC
Electric Discharge Lamp Rating: 30A, 277VAC
Heavy Duty Pilot Rating: 720VA, 120−600VAC
(Box lug nut accessory limits voltage to 277VAC)
Min. Load Current: 1 Amp @ 120VAC
Duty: Continuous
NTE Electronics, Inc.
Life
Mechanical: 2,000,000 Operations
Electrical:
500,000 Operations @ Full Load
Note It is not recommended to mount or operate contactors
upside−down.
Voice (973) 748−5089
FAX (973) 748−6224
http://www.nteinc.com