RLY600 Series Features • Straight

RLY600 Series
Features
•
•
•
Straight Through Wiring
Heavy Duty
Replaceable Contacts
Definite Purpose, 3PST−DM, 40 Amp,
Magnetic Contactors
D80
3.800 (96.52)
3.250 (82.56)
.500
(12.7)
Dia
1.500
(38.1)
2.560
(64.77)
2.600
(67.31)
.210 (5.33) x .450 (11.43)
3.550 (90.17)
LINE
LOAD
3.420
(86.87)
Electrical Specifications
AC OPERATED
Coils
Input
Voltage
Nom.
Power
Contact
Arr.
Max.
Contact
Cur. @
600VAC
120 VAC
12 VA
3PST−DM
40A
NTE Type No.
RLY655
Contacts
Motor Rating in Amps
Full Load
Diag
No.
D80
Resistive
Rating
(Elect. Heat)
Locked Rotor
@ 600VAC
@ 240VAC
@ 480VAC
@ 600VAC
@ 600VAC
40A
240A
200A
160A
50A
Motor Horsepower Ratings
Motor Type
@ 240VAC
@ 240VAC
@ 440−600VAC
1∅2P
2 HP
5 HP
−
3∅3P
5 HP
10 HP
15 HP
NTE
TYPE NO.
Dual .250” Quick Connect Terminals
RLY9201
Box Lug
RLY9202
Replacement Contacts
RLY9203
NTE Electronics, Inc.
Voice (973) 748−5089
Coil
Power . . . . . . . . . . . . Inrush: 92VA
Steady State: 12VA
Duty: Continuous
Operational Characteristics
Timing Value . . . . . . Operate Time: 25 mS
Release Time: 25 mS
Insulation Characteristics
Initial Breakdown Voltage: 2200V RMS
Environmental Characteristics
Operating: −55°C to +65°C
Life
ACCESSORIES
DESCRIPTION
Tungsten Lamp Rating: 50A, 277VAC
Electric Discharge Lamp Rating: 50A, 277VAC (Wye)
Min. Load Current: 1 Amp @ 120VAC
Duty: Continuous
Mechanical: 2,000,000 Operations
Electrical:
200,000 Operations @ Full Load
Note It is not recommended to mount or operate contactors
upside−down.
FAX (973) 748−6224
http://www.nteinc.com
99