Powerbox Battery Backup Charger Brochure

PBB2S SERIES
DC UPS / BATTERY CHARGERS
Features
•
•
•
•
•
•
•
•
•
•
•
•
13.8Vdc 3.5A and 7A power supplies with battery backup
High reliability and high efficiency industrial-grade switching
power converter
Universal AC input range from 100VAC to 240VAC nominal
without power derating
Light weight corrosion resistant aluminium enclosure
Output overcurrent and short circuit protection
Separate current-limited battery charging output
Output overvoltage protection
Self-resetting battery fuse
Overtemperature protection
Green Mains/DC OK LED and 7A form-C alarm contact
Green Battery OK LED and 7A form-C alarm contact
Red Battery Fuse Fail LED
Specifications
MECHANICAL
INPUT
Dimensions (LxWxH)
219 x 114 x 62mm
Nominal Voltage
100-240VAC
Weight
Current
PBB2S-13-3.5: 1.3A
PBB2S-13-7: 2.8A
PBB2S-13-3.5: 600g
PBB2S-13-7: 900g
ENVIRONMENTAL
Nominal Frequency
50–60Hz
Operating Temp
-10°C to +70°C
Power Factor
Conforms to EN61000-3-2
Power De-rating
-2.5%/°C above 40°C
OUTPUT AC MAINS OPERATION
Cooling
Natural Convection
Voltage
13.8VDC
Automatic self-resetting
Current *
See table * Sum of load + battery charging
current.
Overtemperature
Protection
Battery Charging Current
See table
Ripple & Noise **
< 100mVpp ** BW=20MHz
Short Circuit Protection
Hiccup, non-latching
Load+Battery Charging
Hiccup overcurrent protection, >120% of
rated current
Battery Charging
Current limited taper charging
Overvoltage
16V +10%/-5% Hiccup
DISPLAYS & ALARMS
Mains/ DC OK
Green LED: ON=OK
Voltage-free changeover contact, 30VDC, 7A rating
Battery OK
Green LED: ON=Vbatt >11.5V
OFF=Vbatt <10.5V
Voltage-free changeover contact, 30VDC, 7A rating
Battery Fuse Fail
Red LED: ON=FAIL
STANDARDS & APPROVALS
OUTPUT BATTERY OPERATION
Voltage Drop Battery to
Output
PBBS-13-3.5: 0.47V typ.
PBBS-13-7: 0.55V typ.
Short Circuit Protection
Self-resetting battery fuse
Battery Reverse Polarity
Protection
Indefinite
Safety
AS/NZS60950.1, Class I Certificate NSW26927
Isolation
I/P to Output 3.0 kVac, 1 min.
I/P to Ground 1.9 kVac, 1 min.
O/P to Ground 500 Vac, 1 min.
EMC
AS/NZS CISPR22 Class B
Selection Table
MODEL NUMBER
OUTPUT VOLTAGE
RATED TOTAL OUTPUT
CURRENT
MAXIMUM LOAD CURRENT
BATTERY CHARGING
CURRENT
PBB2S-13-3.5
13.8VDC
3.5A
3.25A
0.25A typ.
PBB2S-13-7
13.8VDC
7.0A
6.0A
1.0A typ.
Continued next page
PBB2S SERIES: DC UPS / BATTERY CHARGERS
EXTERNAL VIEW
External View
TERMINATIONS
Note: Alarm terminations show state in normal non-alarm conditions.
POWERBOX AUSTRALIA PTY LTD
Sydney Head Office:
4 Beaumont Road, Mt Kuring-Gai, NSW 2080
POWERBOX PACIFIC LTD
New Zealand
1a Henry Rose Place, Albany Auckland New Zealand 0632
www.powerbox.com.au
www.powerbox.co.nz
347-0602 Issue X3 23/10/14
Powerbox Australia Pty Ltd
Toll Free: 0800 104 480 Email: [email protected]
4 Beaumont Road, Mount Kuring-Gai NSW 2080. Tel: (02) 9457-2200. www.powerbox.com.au
Toll Free: 1800 251 380 Email: [email protected]
14PB066 PBB2S Spec Sheet