72a-115buien-00

A. Input Characteristics:
1) Voltage: (100-127) / (200-250)VAC
2) Frequency: 50/60 Hz.
3) Line Current: 15A / 12A Maximum
4) Load Capacity: 2.40 / 3.68 KVA
5) Overload Protection: (1) 2P/15 AMP CB
6) Power Cord: NO
7) Connector: IEC 60320 C20
B. Output Characteristics:
1) Voltage: (100-127) / (200-250)VAC
2) Current: 15A / 12A, Total Combined Load
3) Outlets: 9X IEC 60320 C13
2) RoHS: Compliant to Directive 2002/95/EC
C. Mechanical Characteristics:
1) Material: CRS
.750 in / 19.1 mm
3) Lettering: Silk-Screen, White/Epoxy
4) Storage Temp.: -(13) - 149F (-25 - 65C)
D. Operating Environment:
1) Temperature: 32 - 122F (0 - 50C)
.500 in / 12.7 mm
2) Finish: Powder Coat, Black, Fine Texture
15.500 in / 393.7 mm
14.750 in / 374.7 mm
2) Relative Humidity: 0 - 95% (Non-Condensing)
3) Elevation: 0 - 10,000FT (0 - 3000 m)
E. Regulatory Conformance:
1) Safety Agency: UL/cUL, UL60950-1, CE
14.000 in / 355.6 mm
2.500 in / 63.5 mm
1.500 in / 38.1 mm
0
REV
2.700 in / 68.6 mm
1.811 in / 46 mm
CHANGE NOTICE
1472-ENG
1.730 in / 43.9 mm
DRAWINGS IN ACCORDANCE WITH
STANDARD ANSI Y14.5M-1994
.
THIS DOCUMENT CONTAINS
PROPRIETARY INFORMATION AND IS
COPYRIGHTED. EXCEPT WITH THE
WRITTEN PERMISSION OF SPECTRUM
CONTROL, INC. OR ITS SUBSIDIARIES,
SUCH INFORMATION SHALL NOT BE
PUBLISHED OR DISCLOSED TO OTHERS,
OR USED FOR ANY PURPOSE AND THIS
DOCUMENT SHALL NOT BE DUPLICATED
IN WHOLE OR IN PART.
DRAWN:
CarrS
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
FRACTIONS ±1/64
DECIMAL .XX ± .020
DECIMAL .XXX ±.010
DATE
11/3/2009
ANGLES ± 030'
Spectrum
Management Systems
PDU,0U-SAT,9/C13,15A,CB
THIRD
ANGLE
PROJECTION
SHEET:
1 OF 1
72A-115BUIEN-00
CODE IDENT
NO:
STATE COLLEGE,