A. Input Characteristics: 1) Voltage: 200/250 VAC 2) Frequency: 50/60 Hz. 3) Current: 30A Maximum (24A Derated, N.A.) 4) Load Capacity: 6.90 KVA 5) Overload Protection: (2) 2P/15A UL489 Circuit Breaker 6) Power Cord: 10' (3m) 7) Connector: L6-30P B. Output Characteristics: 1) Voltage: 200/250 VAC X 2) Current: 24A (Total Combined Load) 3) Outlets: 18X IEC320 C13, 6x IEC320 C19 G C. Mechanical Characteristics: Y 1) Material: CRS/G40 Galv. Coating L6-30P 2) Finish: Powder Coat, Black, Fine Texture 3) Silk-Screen: White/Epoxy 4) Storage Temp.: -(13) - 149F (-25 - 65C) D. Operating Environment: 1) Temperature: 32 - 122F (0 - 50C) 2) Relative Humidity: 0 - 95% (Non-Condensing) 3) Elevation: 0 - 10,000FT (0 - 3000 m) E. Regulatory Conformance: 1) Safety Agency: UL/cUL, FCC 15 Class A, UL60950-1 2) RoHS: Compliant to Directive 2002/95/EC 3.25 in / 82.6 mm 66 in / 1676.4 mm 1.73 in / 43.9 mm CHANGE NOTICE 1 00772-SPMS REV INFORMATIONAL LABEL DRAWINGS IN ACCORDANCE WITH STANDARD ANSI Y14.5M-1994 . THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION AND IS COPYRIGHTED. EXCEPT WITH THE WRITTEN PERMISSION OF SPECTRUM CONTROL, INC. OR ITS SUBSIDIARIES, SUCH INFORMATION SHALL NOT BE PUBLISHED OR DISCLOSED TO OTHERS, OR USED FOR ANY PURPOSE AND THIS DOCUMENT SHALL NOT BE DUPLICATED IN WHOLE OR IN PART. DRAWN: CarrS TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONS ±1/64 DECIMAL .XX ± .020 DECIMAL .XXX ±.010 ANGLES ± 030' DATE 4/30/2008 Spectrum Management Systems 18X C13, 6X C19, 0U PDU THIRD ANGLE PROJECTION SHEET: 1 OF 1 72A-130BMXGN-10 CODE IDENT NO: STATE COLLEGE, PENNSYLVANIA