FP-DI-300 and cFP-DI-300 Operating Instructions

FieldPoint™ Operating Instructions
FP-DI-300 and cFP-DI-300
Eight-Channel, 24 V Digital Input Module
These operating instructions describe how to install and use the
National Instruments FP-DI-300 and cFP-DI-300 digital input
modules (referred to inclusively as the [c]FP-DI-300). For
information about configuring and accessing the [c]FP-DI-300
over a network, refer to the user manual for the FieldPoint network
module you are using.
Features
The [c]FP-DI-300 is a FieldPoint digital input module with the
following features:
•
Eight digital input channels
•
Sinking inputs compatible with 24 VDC sourcing outputs
•
On/Off LED indicators
•
250 Vrms CAT II continuous channel-to-ground isolation,
verified by 2,300 Vrms , 5 s dielectric withstand test
•
–40 to 70 °C operation
•
Hot swappable
Installing the FP-DI-300
The FP-DI-300 mounts on a FieldPoint terminal base (FP-TB-x),
which provides operating power to the module. Installing the
FP-DI-300 onto a powered terminal base does not disrupt the
operation of the FieldPoint bank.
To install the FP-DI-300, refer to Figure 1 and complete the
following steps:
1. Slide the terminal base key to either position X (used for any
module) or position 5 (used for the FP-DI-300 module).
2. Align the FP-DI-300 alignment slots with the guide rails on the
terminal base.
3. Press firmly to seat the FP-DI-300 on the terminal base. When
the module is firmly seated, the terminal base latch locks it into
place.
4
5
3
6
1
2
1 I/O Module
2 Terminal Base
3 Alignment Slot
4 Key
5 Latch
6 Guide Rails
Figure 1. Installing the FP-DI-300
Installing the cFP-DI-300
The cFP-DI-300 mounts on a Compact FieldPoint backplane
(cFP-BP-x or cFP-180x), which provides operating power to the
module. Installing the cFP-DI-300 onto a powered backplane does
not disrupt the operation of the FieldPoint bank.
To install the cFP-DI-300, refer to Figure 2 and complete the
following steps:
1. Align the captive screws on the cFP-DI-300 with the holes on
the backplane. The alignment keys on the cFP-DI-300 prevent
backward insertion.
2. Press firmly to seat the cFP-DI-300 on the backplane.
3. Using a number 2 Phillips screwdriver with a shank of at least
64 mm (2.5 in.) length, tighten the captive screws to 1.1 N ⋅ m
(10 lb ⋅ in.) of torque. The nylon coating on the screws prevents
them from loosening.
FP-DI-300 and cFP-DI-300
2
ni.com
4
3
5
2
4
2
1
1 I/O Module
2 Captive Screws
3 cFP Controller Module
4 Screw Holes
5 cFP Backplane
Figure 2. Installing the cFP-DI-300
Wiring the [c]FP-DI-300
The FP-TB-x terminal base has connections for each of the
eight input channels of the FP-DI-300 and for an external power
supply to power field devices. The cFP-CB-x connector block
provides the same connections for the cFP-DI-300. Each channel
has one input terminal, VIN . All eight inputs are referenced to the
COM terminals, which are internally connected to each other and
to the C terminals. All eight VSUP terminals are internally
connected to each other and to the V terminals.
Use a 15–30 VDC external power supply to power field devices.
Connect the external power supply to multiple V and VSUP
terminals so that the maximum current through any V terminal
is 2 A or less and the maximum current through any VSUP terminal
is 1 A or less.
© National Instruments Corp.
3
FP-DI-300 and cFP-DI-300
Install a 2 A maximum, fast-acting fuse between the external
power supply and the V terminal on each channel. The wiring
diagrams in this document show fuses where appropriate.
Table 1 lists the terminal assignments for the signals associated
with each channel. The terminal assignments are the same for the
FP-TB-x terminal bases and the cFP-CB-x connector blocks.
Table 1. Terminal Assignments
Terminal Numbers
Channel
VIN
VSUP1
COM
0
1
17
18
1
3
19
20
2
5
21
22
3
7
23
24
4
9
25
26
5
11
27
28
6
13
29
30
7
15
31
32
1
Install a 1 A maximum, fast-acting fuse on each connected VSUP
terminal. Install a 2 A maximum, fast-acting fuse on each connected
V terminal.
Cascading power between two modules defeats
isolation between those modules. Cascading power from
the network module defeats all isolation between
modules in the FieldPoint bank.
Caution
You can wire each channel for use with a sourcing-output device.
A sourcing-output device provides a path to a voltage source.
FP-DI-300 and cFP-DI-300
4
ni.com
Figure 3 shows how to connect a three-wire sourcing-output device
to one channel of the [c]FP-DI-300. In this wiring configuration,
the external power supply is connected to the V and C terminals.
The output device sources power to the VIN terminal.
+
2 A max
SourcingOutput
Device
–
V
1 A max
15–30 VDC
External Power
Supply
C
VSUP
VIN
Input
Circuitry
COM
[c]FP-DI-300
Figure 3. Connection to Sourcing-Output Device
Figure 4 shows how to connect a limit switch to one channel of the
[c]FP-DI-300.
+
2 A max
–
Limit
Switch
V
1 A max
15–30 VDC
External Power
Supply
C
VSUP
VIN
Input
Circuitry
COM
[c]FP-DI-300
Figure 4. Connection to Limit Switch
© National Instruments Corp.
5
FP-DI-300 and cFP-DI-300
Alternatively, you can connect an external power supply as shown
in Figure 5.
External
Power
Supply
–
+
V
C
VSUP
SourcingOutput
Device
VIN
Input
Circuitry
COM
[c]FP-DI-300
Figure 5. Connection to Externally Powered Sourcing-Output Device
You must use the same ground for all of the
channels on the [c]FP-DI-300.
Note
Digital Input Circuit
The [c]FP-DI-300 has eight current-limited input channels. You
can connect a voltage signal to each channel. All eight input
channels share a common ground reference that is isolated from
other modules in the FieldPoint system.
When you apply a voltage above 15 V to a VIN terminal, current
flows through that terminal and turns on the optical isolator,
registering as an ON condition for the channel. When you apply
a voltage below 5 V to a VIN terminal, the channel registers an
OFF condition. When you apply a voltage between 5 and 15 V,
the channel may or may not register an ON condition.
The [c]FP-DI-300 has sinking inputs, which means that current
flows through the VIN terminal to the COM terminal. The inputs
are compatible with sourcing-output devices capable of sourcing
or driving current from a positive supply voltage to common.
A sensor is an example of a sourcing-output device.
Figure 3 shows how to connect to sourcing-output devices. These
devices should have OFF-state leakage currents of less than 1 mA
to ensure that they do not provide false ON state readings to the
[c]FP-DI-300.
FP-DI-300 and cFP-DI-300
6
ni.com
Status Indicators
The [c]FP-DI-300 has two green status LEDs, POWER and
READY. After you install the [c]FP-DI-300 onto a terminal base
or backplane and apply power to the connected network module,
the green POWER indicator lights and the [c]FP-DI-300 informs
the network module of its presence. When the network module
recognizes the [c]FP-DI-300, it sends initial configuration
information to the [c]FP-DI-300. After the [c]FP-DI-300 receives
this initial information, the green READY indicator lights and the
module is in normal operating mode.
In addition to the green POWER and READY indicators, each
channel has a numbered green status indicator that lights when the
channel is in the ON state.
Isolation and Safety Guidelines
Read the following information before
attempting to connect the [c]FP-DI-300 to any circuits
that may contain hazardous voltages.1
Caution
This section describes the isolation of the [c]FP-DI-300 and
its compliance with international safety standards. The field
wiring connections are isolated from the backplane and the
inter-module communication bus. The isolation barriers in the
module provide 250 Vrms Measurement Category II continuous
channel-to-backplane and channel-to-ground isolation, verified
by a 2,300 Vrms , 5 s dielectric withstand test.2 The [c]FP-DI-300
provides double insulation compliant with IEC 61010-1 for
working voltages of 250 Vrms.3 Safety standards (such as those
published by UL and IEC) require the use of double insulation
between hazardous voltages and any human-accessible parts or
circuits.
1
A hazardous voltage is a voltage greater than 42.4 Vpeak or 60 VDC. When a
hazardous voltage is present on any channel, all of the channels must be considered
to be carrying hazardous voltages. Ensure that all circuits connected to the module
are inaccessible to human touch.
2
Refer to the Isolation Voltage section for more information about isolation on the
[c]FP-DI-300.
3
Working voltage is defined as the signal voltage plus the common-mode voltage.
Common-mode voltage is the voltage of the module with respect to ground.
© National Instruments Corp.
7
FP-DI-300 and cFP-DI-300
Never try to use any isolation product between human-accessible
parts (such as DIN rails or monitoring stations) and circuits that
can be at hazardous potentials under normal conditions, unless the
product is specifically designed for such an application, as is the
[c]FP-DI-300.
Even though the [c]FP-DI-300 is designed to handle applications
with hazardous potentials, follow these guidelines to ensure a safe
total system:
•
There is no isolation between channels on the [c]FP-DI-300. If
a hazardous voltage is present on any channel, all channels are
considered hazardous. Make sure that all other devices and
circuits connected to the module are properly insulated from
human contact.
•
Do not share the external supply voltages (the V and
C terminals) with other devices, including other FieldPoint
devices, unless those devices are isolated from human contact.
•
For Compact FieldPoint, you must connect the protective earth
(PE) ground terminal on the cFP-BP-x backplane to the system
safety ground. The backplane PE ground terminal has the
following symbol stamped beside it: . Connect the
backplane PE ground terminal to the system safety ground
using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in.
panhead screw shipped with the backplane to secure the ring
lug to the backplane PE ground terminal.
•
As with any hazardous voltage wiring, make sure that all
wiring and connections meet applicable electrical codes and
commonsense practices. Mount terminal bases and backplanes
in an area, position, or cabinet that prevents accidental or
unauthorized access to wiring that carries hazardous voltages.
•
Do not use the [c]FP-DI-300 as the only isolating barrier
between human contact and working voltages higher than
250 Vrms .
•
Operate the [c]FP-DI-300 only at or below Pollution Degree 2.
Pollution Degree 2 means that only nonconductive pollution
occurs in most cases. Occasionally, however, temporary
conductivity caused by condensation must be expected.
•
Operate the [c]FP-DI-300 at or below Measurement
Category II. Measurement Category II is for measurements
performed on circuits directly connected to the low-voltage
installation. This category refers to local-level distribution,
such as that provided by a standard wall outlet.
FP-DI-300 and cFP-DI-300
8
ni.com
Safety Guidelines for Hazardous Locations
The cFP-DI-300 is suitable for use in Class I, Division 2, Groups
A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nC IIC
T4 and Ex nC IIC T4 hazardous locations; and nonhazardous
locations only. Follow these guidelines if you are installing the
cFP-DI-300 in a potentially explosive environment. Not following
these guidelines may result in serious injury or death.
Caution Do not disconnect I/O-side wires or connectors
unless power has been switched off or the area is known
to be nonhazardous.
Caution Do not remove modules unless power has been
switched off or the area is known to be nonhazardous.
Substitution of components may impair
suitability for Class I, Division 2.
Caution
For Zone 2 applications, install the Compact
FieldPoint system in an enclosure rated to at least IP 54
as defined by IEC 60529 and EN 60529.
Caution
For Zone 2 applications, install a protection
device across the external power supply and the COM
terminal. The device must prevent the external power
supply voltage from exceeding 42 V if there is a transient
overvoltage condition.
Caution
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as EEx nC IIC T4 equipment
under DEMKO Certificate No. 03 ATEX 0251502X. Each module
is marked
II 3G and is suitable for use in Zone 2 hazardous
locations.
For Zone 2 applications, connected signals must
be within the following limits:
Caution
Capacitance .......................... 0.2 μF max
Specifications
These specifications are typical for the range –40 to 70 °C unless
otherwise noted. Specifications are subject to change without
notice.
© National Instruments Corp.
9
FP-DI-300 and cFP-DI-300
Input Characteristics
Number of channels.......................... 8
Input type .......................................... 24 VDC sinking inputs
Reverse voltage protection................ –30 VDC
Input OFF range................................ <5 VDC
Input ON range ................................. 15 to 30 VDC
Input impedance................................ 5 kΩ
Current sink per channel
Logic Level
Minimum
Maximum
ON state
3 mA
6 mA
OFF state
–6 mA
1 mA
Physical Characteristics
Indicators .......................................... Green POWER and
READY indicators,
8 green input state indicators
Weight
FP-DI-300................................... 140 g (4.93 oz)
cFP-DI-300................................. 110 g (3.88 oz)
Power Requirements
Power from network module ............ 225 mW
Isolation Voltage
Isolation voltage is verified by a dielectric withstand test.
Channel-to-ground isolation
Continuous ................................. 250 Vrms, Measurement
Category II
Dielectric withstand.................... 2,300 Vrms, 5 s max
Channel-to-channel isolation ............ None
Environmental
FieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature ...................... –40 to 70 °C
Storage temperature .......................... –55 to 85 °C
FP-DI-300 and cFP-DI-300
10
ni.com
Humidity ........................................... 10 to 90% RH,
noncondensing
Maximum altitude............................. 2,000 m
Pollution Degree ............................... 2
Shock and Vibration
These specifications apply only to the cFP-DI-300. NI
recommends Compact FieldPoint if your application is
subject to shock and vibration.
Operating vibration, random
(IEC 60068-2-64).............................. 10–500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6)................................ 10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27).............................. 50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations
Safety
This product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement,
control, and laboratory use:
• IEC 61010-1, EN-61010-1
• UL 61010-1, CSA 61010-1
Note For UL and other safety certifications, refer to the
product label or visit ni.com/certification, search
by model number or product line, and click the
appropriate link in the Certification column.
Electromagnetic Compatibility
This product is designed to meet the requirements of the following
standards of EMC for electrical equipment for measurement,
control, and laboratory use:
• EN 61326 EMC requirements; Industrial Immunity
• EN 55011 Emissions; Group 1, Class A
• CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A
For EMC compliance, operate this product with
shielded cabling.
Note
© National Instruments Corp.
11
FP-DI-300 and cFP-DI-300
CE Compliance
This product meets the essential requirements of applicable
European Directives, as amended for CE marking, as follows:
•
73/23/EEC; Low-Voltage Directive (safety)
•
89/336/EEC; Electromagnetic Compatibility Directive (EMC)
Note Refer to the Declaration of Conformity (DoC) for
this product for any additional regulatory compliance
information. To obtain the DoC for this product, visit
ni.com/certification, search by model number or
product line, and click the appropriate link in the
Certification column.
Waste Electrical and Electronic Equipment
(WEEE)
At the end of their life cycle, all products
must be sent to a WEEE recycling center. For more
information about WEEE recycling centers and National
Instruments WEEE initiatives, visit ni.com/
environment/weee.htm.
EU Customers
Mechanical Dimensions
Figure 6 shows the mechanical dimensions of the FP-DI-300
installed on a terminal base. If you are using the cFP-DI-300,
refer to the Compact FieldPoint controller user manual for the
dimensions and cabling clearance requirements of the Compact
FieldPoint system.
107.19 mm
(4.22 in.)
109.5 mm
(4.31 in.)
91.44 mm
(3.60 in.)
Figure 6. FP-DI-300 Mechanical Dimensions
FP-DI-300 and cFP-DI-300
12
ni.com
Where to Go for Support
For more information about setting up the FieldPoint system, refer
to these National Instruments documents:
•
FieldPoint network module user manual
•
Other FieldPoint I/O module operating instructions
•
FieldPoint terminal base and connector block operating
instructions
Go to ni.com/support for the most current manuals, examples,
and troubleshooting information.
National Instruments corporate headquarters is located at 11500
North Mopac Expressway, Austin, Texas, 78759-3504. National
Instruments also has offices located around the world to help
address your support needs. For telephone support in the United
States, create your service request at ni.com/support and follow
the calling instructions or dial 512 795 8248. For telephone
support outside the United States, contact your local branch office:
Australia 1800 300 800, Austria 43 0 662 45 79 90 0,
Belgium 32 0 2 757 00 20, Brazil 55 11 3262 3599,
Canada 800 433 3488, China 86 21 6555 7838,
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,
Finland 385 0 9 725 725 11, France 33 0 1 48 14 24 24,
Germany 49 0 89 741 31 30, India 91 80 41190000,
Israel 972 0 3 6393737, Italy 39 02 413091,
Japan 81 3 5472 2970, Korea 82 02 3451 3400,
Lebanon 961 0 1 33 28 28, Malaysia 1800 887710,
Mexico 01 800 010 0793, Netherlands 31 0 348 433 466,
New Zealand 0800 553 322, Norway 47 0 66 90 76 60,
Poland 48 22 3390150, Portugal 351 210 311 210,
Russia 7 095 783 68 51, Singapore 1800 226 5886,
Slovenia 386 3 425 4200, South Africa 27 0 11 805 8197,
Spain 34 91 640 0085, Sweden 46 0 8 587 895 00,
Switzerland 41 56 200 51 51, Taiwan 886 02 2377 2222,
Thailand 662 278 6777, United Kingdom 44 0 1635 523545
© National Instruments Corp.
13
FP-DI-300 and cFP-DI-300
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the
Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other
product and company names mentioned herein are trademarks or trade names of their respective companies.
For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software,
the patents.txt file on your CD, or ni.com/patents.