FP-1601 FieldPoint Quick Start Guide

322978c.qxd
4/4/2003
FieldPoint
4:08 PM
Page 1
TM
FP-1601 FieldPoint Quick Start Guide
What You Need • FP-1601 network module
to Get Set Up • 35 mm DIN rail
• Two DIN rail locks (included)
• Terminal base(s)
• I/O module(s)
• 11–30 VDC power supply
1
• Accessories: Ethernet cable,
flathead screwdriver
• PC running Windows
• National Instruments FieldPoint
Software CD
Install the Network Module
Mount the module on a DIN rail.
A. Unlock rail clip.
© National Instruments Corporation
1
FP-1601 Quick Start Guide
322978c.qxd
4/4/2003
4:08 PM
Page 2
NOTE Do not use spliced DIN rails. Use only a single DIN rail.
B. Hook lip on back of module
onto top of DIN rail, press
down, and snap into place.
C. Slide module into position
and lock rail clip.
FP-1601 Quick Start Guide
2
ni.com
322978c.qxd
2
4/4/2003
4:08 PM
Page 3
Install the Terminal Base(s)
CAUTION Connect the terminal bases to the network module before applying
power to the module. Do not connect or disconnect terminal bases while
power is applied to the network module.
A. Unlock rail clip.
B. Press base onto rail.
© National Instruments Corporation
3
FP-1601 Quick Start Guide
322978c.qxd
4/4/2003
4:08 PM
Page 4
C. Slide base into position and
lock rail clip. Be careful not
to bend any pins.
D. Repeat for each terminal base, up to nine for each network module in most cases.
You can use one or two extender cables (which you can order separately) if the
FieldPoint bank is too long for the available space. Make sure there are no gaps
between terminal bases.
E. You must install DIN rail locks at each end of the bank to ensure reliable
connections between terminal bases and network module. Two rail locks are
included with each network module. Place protective cover on last base.
FP-1601 Quick Start Guide
4
ni.com
322978c.qxd
3
4/4/2003
4:08 PM
Page 5
Install the I/O Module(s)
It does not matter where you install each I/O module, except in the following cases:
• If you plan to cascade power between any I/O modules using the V and C terminals,
those modules should be grouped together.
CAUTION Cascading power defeats isolation.
• For more accurate measurements, place thermocouple modules away from heat
sources, including network modules and relay modules.
A. Align slots on module with guide rails
on base, and press module onto base
until terminal base latch locks module
in place.
B. Repeat for each I/O module.
4
Connect the FP-1601 to the Network
Connect the FP-1601 to an
Ethernet network by
connecting the RJ-45
Ethernet port of the
FP-1601 to an Ethernet
hub using a standard
Category 5 Ethernet cable.
© National Instruments Corporation
Straight-Through
UTP Cable
Straight-Through
UTP Cable
5
FP-1601 Quick Start Guide
322978c.qxd
4/4/2003
4:08 PM
Page 6
Optionally, you can connect an
FP-1601 directly to a computer using
an Ethernet crossover cable.
Crossover Cable
Do not use a cable longer than 100 m.
If you are using a 100 Mbps Ethernet,
National Instruments recommends using a Category 5 shielded twisted-pair cable.
If you need to build your own cable, refer to the FP-1601 User Manual specifications
section for cabling details.
5
Wire Power to the FieldPoint System
A. Connect power supply leads to the V and C terminals of the network module. Use an
11–30 VDC, 15 W minimum power supply such as the NI FP-PS-4. Refer to the I/O
module operating instructions for the power requirements of each module. Refer to
the Specifications section of this document for instructions on calculating the
power requirement of the FieldPoint bank.
B Connect power to the I/O modules that require external power for outputs (examples
include output, counter, relay, PWM, PG, and QUAD modules). It is generally best to
power each such module by connecting an external power supply to the VSUP and
COM terminals. Refer to the I/O module operating instructions for power
requirements, detailed wiring diagrams, and safe wiring practices.
FP-1601 Quick Start Guide
6
ni.com
322978c.qxd
4/4/2003
4:08 PM
Page 7
CAUTION Cascading power from neighboring bases or network modules
defeats isolation between cascaded modules.
Separate Power Supply
(Recommended)
No External
Power Required
Cascaded Power
(Reduces Isolation)
FP-1601
FP-AI-100
FP-AO-200
15 16 V
Shades of gray indicate
different voltage potentials.
31 32 C
FP-RLY-420
V 1 2 3
FP-TC-120
Power supply connected to
VSUP and COM terminals
C 17 18
CAUTION Cascading
power defeats isolation.
© National Instruments Corporation
7
FP-1601 Quick Start Guide
322978c.qxd
6
4/4/2003
4:08 PM
Page 8
Connect to Field Devices
Use the operating instructions for each I/O module to help you connect field devices.
7
Power Up the FieldPoint System
FP-1601 Quick Start Guide
8
RESET
7
6
5
4
3
O
F
F
/
O
N
2
Make sure the RESET DIP switch is
not on. Plug in each power supply to
the FieldPoint bank. You should see
the POWER and STATUS LEDs come
on. After about 5 seconds, the
STATUS LED begins flashing, one
flash at a time. This indicates that the
FP-1601 is ready to be configured. If
the LEDs do not follow this sequence,
refer to the FP-1601 User Manual
troubleshooting appendix.
1
CAUTION Connect terminal bases to the FP-1601 before applying power.
ni.com
322978c.qxd
8
4/4/2003
4:08 PM
Page 9
Install Software on the Host PC
A. Install the software packages you plan to use, such as LabVIEW, LabVIEW RT,
Measurement Studio, VI Logger, or LabWindows™/CVI™, before you install the
FieldPoint software. The FieldPoint software installation installs the LabVIEW VIs
and examples and the LabWindows/CVI instrument driver only if it finds the
corresponding development software installed.
B. Close all other applications.
C. Insert the National Instruments FieldPoint
Software CD into the CD-ROM drive of
your computer.
D. Follow the onscreen instructions to
complete the installation.
NOTE If the setup does not launch automatically, select Start»Run from
Windows, enter d:\setup, where d is the letter of the CD-ROM drive, and
select OK.
© National Instruments Corporation
9
FP-1601 Quick Start Guide
322978c.qxd
9
4/4/2003
4:08 PM
Page 10
Configure the FP-1601
Launch NI Measurement & Automation Explorer (MAX) to configure the FP-1601. For
information about configuring the FP-1601 in software, refer to the Measurement &
Automation Explorer Help for FieldPoint (Start»Programs»National Instruments»
FieldPoint»FieldPoint Help).
FP-1601 Quick Start Guide
10
ni.com
322978c.qxd
4/4/2003
4:08 PM
Page 11
Specifications
Network
Network interface . . . . . . . . . . . . . . . 10BaseT and 100BaseTX Ethernet
Compatibility. . . . . . . . . . . . . . . . . . . . IEEE 802.3
Communications rate . . . . . . . . . . . . 10 Mbps, 100 Mbps, autonegotiated
Maximum cabling distance . . . . . . . 100 m/segment
Maximum power supplied
to terminal bases . . . . . . . . . . . . . . . . 9 W
Maximum number of banks . . . . . . . Determined by network topology
Power Requirements
Power supply range . . . . . . . . . . . . . 11–30 VDC
Recommended power supply
FP-1601 with
up to 5 modules . . . . . . . . . . . . 15 W (FP-PS-4 or equivalent)
FP-1601 with
6 to 9 modules . . . . . . . . . . . . . 20 W
Power consumption . . . . . . . . . . . . . 4.5 W + 1.1(I/O module power requirements)
Physical Characteristics
Screw-terminal wiring . . . . . . . . . . . 16–26 AWG copper conductor wire with 7 mm
(0.28 in.) of insulation stripped from the end
Torque for screw terminals . . . . . . . 0.5–0.6 N · m (4.4–5.3 lb · in.)
Weight. . . . . . . . . . . . . . . . . . . . . . . . . 235 g (8.3 oz)
© National Instruments Corporation
11
FP-1601 Quick Start Guide
322978c.qxd
4/4/2003
4:08 PM
Page 12
Environmental
FieldPoint modules are intended for indoor use only. For outdoor use, they must be
installed in a suitable sealed enclosure.
Operating temperature . . . . . . . . . . . –25 to 55 °C
Storage temperature . . . . . . . . . . . . . –55 to 85 °C
Humidity . . . . . . . . . . . . . . . . . . . . . . . 10 to 90% RH, noncondensing
Maximum altitude . . . . . . . . . . . . . . . 2,000 m
Pollution Degree . . . . . . . . . . . . . . . . 2
Safety
The FP-1601 is designed to meet the requirements of the following standards for safety
and electrical equipment for measurement, control, and laboratory use:
• EN 61010-1, IEC 61010-1
• UL 3121-1, UL 61010C-1
• CAN/CSA C22.2 No. 1010.1
For UL and other safety certifications, refer to the product label or to ni.com.
Electromagnetic Compatibility
CE, C-Tick and FCC Part 15 (Class A) Compliant
Emissions . . . . . . . . . . . . . . . . . . . . . . EN 55011 Class A at 10 m FCC Part 15A
above 1 GHz
Immunity . . . . . . . . . . . . . . . . . . . . . . . EN 61326: 1997+A2:2001, Table 1
NOTE For EMC compliance, operate this device with shielded cabling.
FP-1601 Quick Start Guide
12
ni.com
322978c.qxd
4/4/2003
4:08 PM
Page 13
CE Compliance
This product meets the essential requirements of applicable European Directives,
as amended for CE Marking, as follows:
Low-Voltage Directive (safety). . . . . 73/23/EEC
Electromagnetic Compatibility
Directive (EMC) . . . . . . . . . . . . . . . . . 89/336/EEC
NOTE Refer to the Declaration of Conformity (DoC) for this product for any
additional regulatory compliance information. To obtain the DoC for this
product, click Declarations of Conformity Information at
ni.com/hardref.nsf/.
Mechanical Dimensions
107.19 mm
(4.22 in.)
109.5 mm
(4.31 in.)
91.44 mm
(3.60 in.)
© National Instruments Corporation
13
FP-1601 Quick Start Guide
322978c.qxd
4/4/2003
4:08 PM
Page 16
Go to ni.com/support for the most current manuals, examples, and troubleshooting information.
For telephone support in the United States, create your service request at ni.com/ask and follow the
calling instructions or dial 512 795 8248. For telephone support outside the United States, contact your
local branch office:
Australia 02 612 9672 8846, Austria 43 0 662 45 79 90 0, Belgium 32 0 2 757 00 20, Brazil 55 11 3262 3599,
Canada (Calgary) 403 274 9391, Canada (Montreal) 514 288 5722, Canada (Ottawa) 613 233 5949,
Canada (Québec) 514 694 8521, Canada (Toronto) 905 785 0085, Canada (Vancouver) 514 685 7530,
China 86 21 6555 7838, Czech Republic 420 2 2423 5774, Denmark 45 45 76 26 00, Finland 385 0 9 725 725 11,
France 33 0 1 48 14 24 24, Germany 49 0 89 741 31 30, Greece 30 2 10 42 96 427, India 91 80 51190000,
Israel 972 0 3 6393737, Italy 39 02 413091, Japan 81 3 5472 2970, Korea 82 02 3451 3400,
Malaysia 603 9131 0918, Mexico 001 800 010 0793, Netherlands 31 0 348 433 466,
New Zealand 64 09 914 0488, Norway 47 0 32 27 73 00, Poland 48 0 22 3390 150, Portugal 351 210 311 210,
Russia 7 095 238 7139, Singapore 65 6226 5886, Slovenia 386 3 425 4200, South Africa 27 0 11 805 8197,
Spain 34 91 640 0085, Sweden 46 0 8 587 895 00, Switzerland 41 56 200 51 51, Taiwan 886 2 2528 7227,
Thailand 662 992 7519, United Kingdom 44 0 1635 523545
CVI™, FieldPoint™, LabVIEW™, Measurement Studio™, National Instruments™, NI™, and ni.com™ are
trademarks of National Instruments Corporation. Product and company names mentioned herein are
trademarks or trade names of their respective companies.
For patents covering National Instruments products, refer to the appropriate location:
Help»Patents in your software, the patents.txt file on your CD, or ni.com/patents.
© 2001–2003 National Instruments Corporation. All rights reserved.
*322978C-01*
322978C-01
Apr03