1318 Connection Guide

Bulletin 1318 Connection Guide
Terminal Block Connections
Terminals 1, 2 & 3
"Power Supply" Common for 24V logic (O Volts).
Terminals 4, 5, & 6
+ 24V DC unregulated power supply. Maximum combined load: 150mA.
Terminal 7
- 24V DC unregulated power supply. Maximum load: 50mA.
Terminal 8
+ 15V DC regulated power supply.
Terminal 9
- 15V DC regulated power supply.
Terminals 10 & 11
+ 10V DC regulated power supply. Maximum load: 20mA.
Terminals 12 & 13
- 10V DC regulated power supply. Maximum load: 20mA.
Terminals 14,15, & 16 "Signal" Common.
Terminal 17
Inverse Time Current Limit Output (10V DC @ 2ma = 200% current).
Terminal 18
Stop under Ramp control (via contact).
Terminal 19
Zero to + 10V Speed reference input to Ramp circuit.
Terminal 20
+ 24V DC, causes Ramp to reset to zero (regenerate to Zero Speed at current limit) DC Loop contactor
does not drop out at Zero Speed.
Terminal 21
0 to + 10V DC current command (5V DC = 100% Controller current).
Terminal 22
Jog Disable, connecting to signal common disables Jog reference input
Terminal 23
Non-Buffered Speed amplifier output (0 to +- 5V DC) through resistor.
Terminal 24
Reverse current limit program input (5V DC = 100% rated line current).
Terminal 25
Jog (Crawl) input reference ( + 10V DC = 25% Speed).
Terminal 26
Speed reference (0 to + 10V DC reference) ramp bypassed.
Terminal 27
Forward current limit program input (5V DC = 100% rated Drive current).
Terminal 28
Tachometer feedback input (7.5 to 245V DC maximum) Negative input for forward operation. See
following note.
Note: Verify that resistors are selected correctly in slots R16 and R17 (Applications Board) for tachometer output.
Terminal 29
Buffered Tachometer output, (O to + 10V DC = 100% Speed @ 2mA maximum) for speed metering.
Terminal 30
Current Limit solid state relay output ( + 24V DC = "in Current Limit") maximum load: 45mA.
Terminal 31
Drive Healthy (Internal Fault Detector Circuit Output) (0VA DC = Fault) maximum load: 45mA.
Terminal 32
Zero Speed Detector Output ( + 24V DC = Zero speed) maximum load: 45mA.
Terminal 33
Make Ready (Enable) input ( + 24V DC allows the Drive DC Loop contactor to close and activate Drive
circuitry when + 24V DC RUN signal is present at terminal 36).
Terminal 34
DC Loop contactor closed input via auxiliary contact ( + 24V DC = Contactor closed).
Terminal 35
DC Loop contactor output ( + 24V DC = Contactor closed).
Terminal 36
Run enable input ( + 24V DC = Run).
Terminal 37
Trip input ( + 24V DC allows Drive to run. Removing + 24V DC causes Drive to Coast-to-Stop.).
Terminal 38
Ramp (Accel/Decel) output (O to + 10V DC). Max Load = 2 mA. Not for Reference follower applications.
Terminal 39
Stop 3 input (Regenerative Stop) contactor remains closed + 24V DC = OK to run, removing + 24V DC
causes Regenerative Stop.
Terminal 40
Not Used. Do not use as a tie point.
Terminal 41
Buffered Current Amplifier output ( + 1mA = 200% rated Controller current). For current metering
(bi-directional).
Terminal 42
Buffered Current Amplifier output ( + 1mA = 200% rated controller current). For current metering
(unidirectional).
Terminal 51/53 RL1 Normally Open 115V AC/0.5A Contact.
Terminal 53/52 RL1 Normally Closed 115V AC/0.5A Contact.
Terminal 54
RL1 Normally Open 115V AC/0.5A Contact.
100V Wound Field Motors
Permanent Magnetic Motors
200V Wound Field Motors
Control Logic Interconnections
Coast to Stop Control Logic
Required Current Limit Stop Control Logic
Required Ramp Controlled Stop Control Logic