ALLEN-BRADLEY BULLETIN 1336 PLUS OUTPUT CONTACTOR

ALLEN-BRADLEY
ALLEN-BRADLEY
BULLETIN 1336 PLUS
OUTPUT CONTACTOR
APPLICATION NOTE #1336S - 10
May 19, 1997
PURPOSE
The purpose of this document is to provide guidelines for wiring and control
schemes for the Bulletin 1336S AC Drive. This document is to be used as a
suggestion only. Users must ensure that installations meet applicable codes and
are suitable for the existing conditions.
The Bulletin 1336S User Manual should be used as a reference to ensure that
proper wire selection, routing and fusing guidelines are followed.
WHAT THIS NOTE
CONTAINS
Suggested guidelines for applying an Output Contactor to a Bulletin 1336S. The
Output Contactor may also be utilized as part of an ALL-STOP circuit. Refer to
application note #1336S-4, 1336S ALL-STOP CIRCUITRY for additional
information.
INTENDED
AUDIENCE
This application note is intended to be used by personnel familiar with the
hardware components and programming procedure necessary to operate the
Bulletin 1336S.
WHERE IT
IS USED
The diagrams, parameter settings and auxiliary hardware used in this application
note are designed to address specific issues in many different applications. Some
changes by the User may be necessary to apply the concepts of this document to
a specific application.
TERMS AND
DEFINITIONS
The Output Contactor (2K) is an electromechanical device wired between the
adjustable frequency drive and the AC motor.
Faxback Document #3030 Web location Http://WWW.AB.COM
Page 1 of 5
ALLEN-BRADLEY
DESCRIPTION
The Output Contactor is used where it is desired to electrically isolate the drive
from the motor. An ALLEN-BRADLEY Bulletin 100 (IEC) or Bulletin 500 (NEMA)
contactor is recommended.
Figure 1 illustrates the coordination of the Output Contactor with the drive fault
contact. Drive start/stop operation must ensure that 2K is energized prior to
initiating a start command. The drive fault contact ensures that the drive output is
off before opening the Output Contactor.
Figure 2 utilizes a timer circuit to interrupt power to the Output Contactor. This is
useful for applications that have RAMP-TO-STOP or DC INJECTION BRAKING.
The time delay should be set to a value greater than the DECEL TIME or the
INJECTION BRAKE TIME. This will ensure that the drive output is off prior to
opening the contactor.
Figure 3 uses the start command to energize the Output Contactor and the RUN
contact to hold-in the contactor until the drive output is off. This scheme is useful
for the controlled stop modes of operation.
APPLICATION
CONSIDERATIONS
The output contactor should be closed before the drive begins to run and should
open after the drive has been stopped. If not operated this way voltage transients
sent back to the drive can do one or all of the following......
1. Cause the drive to fault on overcurrent.
2. Cause the drive to fault on overvoltage.
3. Degrade the life of the drive.
The schematics on the following pages show suggested wiring schemes for the
output contactor. Notice that the contactor is never closing or opening while the
drive is running.
Faxback Document #3030 Web location Http://WWW.AB.COM
Page 2 of 5
ALLEN-BRADLEY
FIGURE 1 OUTPUT CONTACTOR WITH FAULT CONTACT CONTROL
R
115V AC
S
T
GND
TB1
1
POT HIGH
2
POT WIPER
3
POT COMMON
4
SIGNAL COMMON
5
0-10V INPUT
6
4-20ma INPUT
7
PULSE INPUT (-)
8
PULSE INPUT (+)
9
METER OUTPUT
JUMPER J5
1-2 (4-20ma)
3-4 (0-10vdc)
10
CR1
11
CR2
12
13
CR3 (FAULT)
14
CR3 (NOT FAULT)
15
2K
16
CR4
17
CR4
18
TB3
START
2K
L6E
115VAC INTERFACE
TB3
19
START
ENCODER B
31
20
STOP
ENCODER A
32
21
COMMON
ENCODER B
33
22
REVERSE
ENCODER A
34
23
JOG
+12VDC
35
24
AUXILIARY
ENC COM
36
25
COMMON
26
SPD SEL 3
27
SPD SEL 2
28
SPD SEL 1
29
COMMON
30
ENABLE
STOP
EXT FAULT
INTERLOCK
CUSTOMER
INTERLOCK
INPUT MODE 2
TB1
U
V
W
GND
2K
Faxback Document #3030 Web location Http://WWW.AB.COM
Page 3 of 5
ALLEN-BRADLEY
FIGURE 1 OUTPUT CONTACTOR WITH TIMER CONTROL
R
115V AC
S
T
GND
TB1
1
POT HIGH
2
POT WIPER
3
POT COMMON
4
SIGNAL COMMON
5
0-10V INPUT
6
4-20ma INPUT
7
PULSE INPUT (-)
8
PULSE INPUT (+)
9
METER OUTPUT
JUMPER J5
1-2 (4-20ma)
3-4 (0-10vdc)
10
CR1
11
CR2
12
13
CR3 (FAULT)
14
CR3 (NOT FAULT)
15
1TD
2K
16
CR4
17
RUN
1TD
CR4
18
TB3
1TD
2K
L6E
115VAC INTERFACE
TB3
19
START
ENCODER B
31
20
STOP
ENCODER A
32
21
COMMON
ENCODER B
33
22
REVERSE
ENCODER A
34
23
JOG
+12VDC
35
24
AUXILIARY
ENC COM
36
25
COMMON
26
SPD SEL 3
27
SPD SEL 2
28
SPD SEL 1
29
COMMON
30
ENABLE
STOP
EXT FAULT
INTERLOCK
CUSTOMER
INTERLOCK
INPUT MODE 2
TB1
U
V
W
GND
2K
Faxback Document #3030 Web location Http://WWW.AB.COM
Page 4 of 5
ALLEN-BRADLEY
FIGURE 1 OUTPUT CONTACTOR WITH RUN CONTACT CONTROL
R
115V AC
S
T
GND
TB1
1
POT HIGH
2
POT WIPER
3
POT COMMON
4
SIGNAL COMMON
5
0-10V INPUT
6
4-20ma INPUT
7
PULSE INPUT (-)
8
PULSE INPUT (+)
9
METER OUTPUT
JUMPER J5
1-2 (4-20ma)
3-4 (0-10vdc)
10
CR1
11
CR2 (RUN)
12
4K
13
CR3 (FAULT)
14
CR3 (NOT FAULT)
15
RUN
2K
16
CR4
17
4K
CR4
18
TB3
2K
L6E
115VAC INTERFACE
TB3
19
START
ENCODER B
31
20
STOP
ENCODER A
32
21
COMMON
ENCODER B
33
22
REVERSE
ENCODER A
34
23
JOG
+12VDC
35
24
AUXILIARY
ENC COM
36
25
COMMON
26
SPD SEL 3
27
SPD SEL 2
28
SPD SEL 1
29
COMMON
30
ENABLE
STOP
EXT FAULT
INTERLOCK
CUSTOMER
INTERLOCK
INPUT MODE 2
TB1
U
V
W
GND
2K
Faxback Document #3030 Web location Http://WWW.AB.COM
Page 5 of 5