10 - Push Buttons

Bulletin 800R
30.5 mm Push Button Stations Hermetically Sealed for Division 2/Zone 2
10
Type 4/13 and 4/4X/13 for Hazardous Locations
Bulletin 800R
• Hazardous Location
Push Button Stations
• Classes I and II
Division 2/Zone 2
• 30.5 mm Mounting Hole
• Types 4/13 and 4/4X/13
0
TABLE OF CONTENTS
Description
Page
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-107
800T Push Button Operators . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-6
800H Push Button Operators . . . . . . . . . . . . . . . . . . . . . . . . . . 10-60
Stations
Complete Assembled, Metallic Enclosures . . . . . . . . . . . . . 10-108
Complete Assembled, Non-Metallic Enclosures. . . . . . . . . . 10-109
10-106
Description
Page
Custom Built Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-110
Enclosures Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-110
Approximate Dimensions and Shipping Weights. . . . . . . . .10-111
Bulletin 800R
30.5 mm Push Button Stations Hermetically Sealed for Division 2/Zone 2
Type 4/13 and 4/4X/13 for Hazardous Locations
Specifications ➊
Electrical Ratings
Contact Ratings
Dielectric Strength
Electrical Design Life Cycles
Refer to the Contact Ratings tables below.
2200V for one minute, 1300V for one minute (Logic Reed)
1,000,000 at maximum rated load, 200,000 at maximum rated load (Logic Reed)
Mechanical Ratings
Vibration
Shock
Degree of Protection
Mechanical Design Life Cycles
Push Buttons
Selector Switches
10…2000 Hz 1.52mm displacement (peak-to-peak) Max./10 G Max. (except Logic Reed)
1/2 cycle sine wave for 11 milliseconds ≥ 25 G (contact fragility) and no damage at 100 G
Type 4/4X/13, 4/13; Watertight/Corrosion-Resistant IEC 529 IP66/65
(Momentary, Non-Illuminated)
(Momentary, Illuminated)
(Push-Pull/Twist-to-Release)
(Non-Illuminated)
(Illuminated)
All other devices
Contact Operation
Typical Operating Forces
10,000,000 min.
250,000 min.
250,000 min.
1,000,000 min.
200,000 min.
200,000 min.
Logic Reed and Sealed Switch Contact Blocks:
Single break magnetic
Flush, Extended, Standard Mushroom, Jumbo Plastic Mushroom: 2 lbs max.
Maintained Selector Switch: 3.6 in.-lbs maximum
3.6 in.-lbs to stop
Spring Return Selector Switches
0.2 in.-lbs to return
Illuminated Push Buttons and Push-to-Test Pilot Lights
5 lbs maximum
3-Position Push-Pull
8 lbs maximum push to in position or pull to center position (15 lbs maximum pull to out position)
9 lbs maximum push or pull
Push-Pull and Push-Pull/Twist
30 in.-oz. maximum twist, 6 in.-oz. minimum return
Logic Reed
1 lb maximum
Contact Blocks
Sealed Switch
3 lbs maximum at 0.205" plunger travel
Stackable Sealed Switch
1 lb maximum
Operators without contact blocks
Environment
Operating
Temperature Range
Storage
Note: Operating temperatures below freezing are based on the
absence of moisture and liquids. Contact your local
Allen-Bradley sales office for use in lower temperature
applications.
Humidity
–40...+131°F (–40...+55°C)
–40...+185°F (–40...+85°C)
1
50% at +104°F (+40°C)
➊ Performance Data — See page Important-2.
Control Stations
Bulletin 800R control stations are designed for Division 2/Zone 2
hazardous locations. They consist of Bulletin 800H (Type 4/4X/13) or
Bulletin 800T (Type 4/13) operators with sealed contact blocks. Bulletin
800R units are available as factory assembled stations or as
components for field assembly.
Hazardous Locations
Since the contacts are enclosed in a hermetically sealed chamber, the
contact block is suitable for use in Class I and II, Division 2/Zone 2
Groups A, B, C, D, F and G hazardous locations and is listed by
Underwriters Laboratories for this class of service. Complete stations
as shown on page 10-108 can be used for Class I and II Division 2/
Zone 2 applications. The individual components shown in the 800T and
800H sections are also suitable for Class I and II Division 2/Zone 2
locations providing they are suitably mounted by the customer in an
enclosure as required for the application and by applicable codes and
laws.
Class I Zone 2 protection method Ex nW IIc Temp. Code T3/T6, Demko
97.Y.122018 U applies to operators and contacts.
Per National Electrical Code: Zone 2. In Class I, Zone 2 locations, all
wiring methods permitted for Class I, Division 2, Class I, Division 1 or
Division 2, and Class I, Zone 0 or Zone 1 locations, including
requirements for sealing, shall be permitted.
Note: Allen-Bradley Logic Reed contact blocks are also listed by
Underwriters Laboratories for the Division 2/Zone 2 hazardous
locations listed above.
Sealed Switch Contact Ratings
Maximum continuous current Ith 5 A. Bulletin 800T and 800H units have
control circuit ratings with sealed switch contact blocks as follows:
Max. Opertnl. Utilization Category
Volts Ue
IEC
NEMA
AC 600
AC-15
B600
DC 300
DC-13
P300
Rated Operational Currents
Volts Ue
Make
Break
120…600
3600 VA
360 VA
0…120
30 A
3A
24…300
138 VA
0…24
5.0 A
Stackable Sealed Switch Contact Ratings
Maximum continuous current Ith 2.5 A. Bulletin 800T and 800H units
have control circuit ratings with sealed switch contact blocks as follows:
Max. Opertnl. Utilization Category
Volts Ue
IEC
NEMA
AC 300
AC-15
C300
DC 150
DC-13
Q150
Rated Operational Currents
Volts Ue
Make
Break
120…300
1800 VA
180 VA
0…120
15 A
1.5 A
24…150
69 VA
0…24
2.5 A
Logic Reed Contact Ratings
Maximum DC: 30V, 0.06 A Maximum AC: 150V, 0.15 A
Should only be used with resistive loads.
Approvals
UL Listed —
File: E10314
Guide: NOIV
CSA Certified: LR11924
IEC Compliance Demko 97.Y.122018 U
!
CAUTION:
The complete stations and individual components listed herein are
not suitable for use in Class I and II Division 1 hazardous
locations. For Class I and II Division 1 hazardous locations, order
Bulletin 800H Type 7 & 9 stations and units.
10-107
Bulletin 800R
30.5 mm Push Button Stations Hermetically Sealed for Division 2/Zone 2
Type 4/13 and 4/4X/13 for Hazardous Locations
Complete Assembled Stations, Metallic Enclosures
Class I, Division 2/Zone 2
Push button operators for Class I, Division 2/Zone 2 are offered in Bulletin 800T page 10-4 and Bulletin 800H page 10-58.
Surface Mount
Cat. No. 800R-1TA
Operator
0
Contact
Symbol
One
Push
Button
Two
Push
Buttons
One
Pilot Light
Two Push
Buttons
Booted Operator Station
Cat. No. 800R-1HA4T
1 N.O. 1 N.C.
Each
Button
1 N.O. 1 N.C.
Red
Each
Button
1 N.O. 1 N.C.
3-Position
Selector
Switch
1 N.O. 1 N.C.
One Push
Button
Maintained
1 N.O. 1 N.C.
Two Push
Buttons
Maintained
1 N.O. 1 N.C.
Cast Aluminum
Enclosures ➊
Stainless Steel Enclosures ➋
Button
Type/Color
Legend
Marking
Cat. No.
Cat. No.
Cat. No.
Flush/Green
START
800R-1TB
800R-1HB4T
800R-1HB4TL
Extended/Red
STOP
800R-1TA
800R-1HA4T
800R-1HA4TL
Flush/Black
No Legend
800R-1TX
800R-1HX4T
800R-1HX4TL
Flush/Green
Extended/Red
START
STOP
800R-2TA
800R-2HA4T
800R-2HA4TL
Flush/Black
Flush/Black
No Legends
800R-2TX
800R-2HX4T
800R-2HX4TL
120V AC Red
Flush/Green
Extended/Red
No Legend
START
STOP
800R-2TAR
800R-2HAR4T
800R-2HAR4TL
120V AC Red
Flush/Black
Flush/Black
No Legends
800R-2TXR
800R-2HXR4T
800R-2HXR4TL
Maintained
HAND OFF AUTO
800R-R3TA
—
800R-R3HA4TL
Maintained
No Legend
800R-R3TX
—
800R-R3HX4TL
Push-Pull/Twist
Red
EMRG. STOP
800R-1TAM
—
800R-1HAM4TL
Flush/Green
Extended/Red
START
STOP
800R-2TAM
800R-2HAM4T
800R-2HAM4TL
Flush/Black
Flush/Black
No Legends
800R-2TXM
800R-2HXM4T
800R-2HXM4TL
➊ Type 4/13
➋ Type 4/4X/13
Approximate Dimensions — Page 10-111
10-108
Bootless Operator Station
Cat. No. 800R-1HA4TL
Surface Mount
Booted
Operator Station
Bootless
Operator Station
Bulletin 800R
30.5 mm Push Button Stations Hermetically Sealed for Division 2/Zone 2
Type 4/13 and 4/4X/13 for Hazardous Locations
Complete Assembled Stations, Non-Metallic Enclosures Type 4/4X/13
Class I, Division 2/Zone 2
Push button Operators for Class I, Division 2/Zone 2 are offered in Bulletin 800T page 10-4 and Bulletin 800H page 10-58.
Booted Operator Station
Cat. No. 800R-1HA4R
Contact
Symbol
Operator
One
Push
Button
Two
Push
Buttons
One
Pilot Light
Two Push
Buttons
One Push
Button
Maintained
1 N.O. 1 N.C.
Two Push
Buttons
Maintained
1 N.O. 1 N.C.
Bootless Operator Station
Cat. No.
Cat. No.
800R-1HB4R
800R-1HB4RL
STOP
800R-1HA4R
800R-1HA4RL
Flush/Black
No Legend
800R-1HX4R
800R-1HX4RL
Flush/Green
Extended/Red
START
STOP
800R-2HA4R
800R-2HA4RL
Flush/Black
Flush/Black
No Legends
800R-2HX4R
800R-2HX4RL
120V AC Red
Flush/Green
Extended/Red
No Legend
START
STOP
800R-2HAR4R
800R-2HAR4RL
120V AC Red
Flush/Black
Flush/Black
No Legends
800R-2HXR4R
800R-2HXR4RL
Maintained
HAND OFF AUTO
—
800R-R3HA4RL
Maintained
No Legend
—
800R-R3HX4RL
Push-Pull/Twist Red
EMERG. STOP
—
800R-1HAM4RL
Flush/Green
Extended/Red
START
STOP
800R-2HAM4R
800R-2HAM4RL
Flush/Black
Flush/Black
No Legends
800R-2HXM4R
800R-2HXM4RL
1 N.O. 1 N.C.
1 N.O. 1 N.C.
Booted Operator Station
START
1 N.O. 1 N.C.
3-Position
Selector
Switch
Legend
Marking
Flush/Green
Red
Each
Button
Rosite Glass Polyester Enclosures
Button
Type/Color
Extended/Red
1 N.O. 1 N.C.
Each
Button
Bootless Operator Station
Cat. No. 800R-1HA4RL
Approximate Dimensions — Page 10-111
10-109
1
Bulletin 800R
30.5 mm Push Button Stations Hermetically Sealed for Division 2/Zone 2
Type 4/13 and 4/4X/13 for Hazardous Locations
Custom Built Stations
Description
The tables on pages 10-108 and
10-109 list the most commonly used
push button stations. Stations not listed
in the tables may be ordered as custom
built stations.
Cat. No.
The cat. no. used to identify custom built
Bulletin 800R push button stations,
which are built at the factory, will be cat.
nos. listed for the enclosure only, except
letter W will be substituted for the letter Z
and with a station serial number.
Ordering Information
The following information is required
when ordering custom built push button
stations.
1. Cat. no. of enclosure.
2. Cat. no. of control units.
3. Legend plate cat. no. and/or marking
for each unit.
4. Specify vertical or horizontal
mounting.
5. Specify desired operator mounting
sequence. Inclusion of a sketch is
recommended. If no information is
given, best judgement will be used.
Enclosures Only
0
Die Cast
Cat. No. 800R-2TZ
Stainless Steel
Cat. No. 800R-2HZ4
Rosite Glass Polyester
Cat. No. 800R-2HZ4R
Stainless Steel
(Type 4/4X/13)
Rosite Glass Polyester
(Type 4/4X/13)
Fiberglass
Cat. No. 800H-2HZ4Y
Fiberglass ➋
(Type 4/4X/12/13)
Units ➊
Die Cast
(Type 4/13)
Cat. No.
Cat. No.
Cat. No.
Cat. No.
1
800R-1TZ
800R-1HZ4
800R-1HZ4R
800H-1HZ4Y
2
800R-2TZ
800R-2HZ4
800R-2HZ4R
800H-2HZ4Y
3
800R-3TZ
800R-3HZ4
800R-3HZ4R
800H-3HZ4Y
4
800R-4TZ
800R-4HZ4
800R-4HZ4R
—
5
—
800R-5HZ4
800R-5HZ4R
—
6
800R-6TZ
800R-6HZ4
800R-6HZ4R
—
Note: Enclosure and conduit dimensions are detailed on page 10-111, except for the fiberglass enclosures which are found on
page 10-105.
➊ Number of units that can be mounted in enclosure.
➋ Extra deep. Accomodates two levels of stackable sealed switch contact blocks.
10-110
Bulletin 800R
30.5 mm Push Button Stations Hermetically Sealed for Division 2/Zone 2
Type 4/13 and 4/4X/13 for Hazardous Locations
Approximate Dimensions and Shipping Weights
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Type 4/4X/13
Stainless Steel
Watertight/Oiltight/
Corrosion-Resistant Enclosure
3 15/32
(88.1)
2 1/4
(57.2)
Type 4/4X/13
Rosite Glass Polyester
Watertight/Oiltight/
Corrosion-Resistant Enclosure
3 13/16
(96.9)
3
(76.2)
3 5/8
(92)
Type 4/13
Watertight/Oiltight
Cast Aluminum
Enclosure
3 13/16
(96.9)
3
(76.2)
3 31/32
(100.8)
3 7/32
(81.8)
B
C
A
B
1 27/32
(46.8)
21/
32
(16.7)
Max.
A B
23/
32
(28.6)
Max.
A
➋
➊
21/ Max.➌
32
(16.7)
Number of Units
Dimension
1
2
3
4
5
6
Mounting Instructions
(for Panel Mounting)
Stainless Steel Type 4/4X/13
A
5-5/32 (135)
7 (178)
B
6-13/32 (163)
8-1/4 (210)
Pipe Tap Size
8-27/32 (225)
10-11/16 (271) 12-17/32 (318)
10-1/8 (257)
11-31/32 (304)
14-3/8 (360)
14-1/32 (359)
3/4
Glass Polyester Type 4/4X/13
A
4-1/2 (114)
4-1/2 (114)
6-1/4 (159)
8 (203)
12-1/8 (308)
12-1/8 (308)
B
7-1/32 (181)
7-1/32 (181)
8-23/32 (221)
10-21/32 (271)
14-7/8 (378)
14-7/8 (378)
C
5-7/8 (149)
5-7/8 (149)
7-9/16 (192)
9-1/2 (241)
13-1/2 (343)
Pipe Tap Size
2 1/4
(57.2)
15-7/8 (403)
1
3/4
1/
4
(6.4)
Dia. Drill
13-1/2 (343)
1
Cast Aluminum Type 4/13
A
2-3/4 (69.8)
4-1/2 (114)
6-1/4 (159)
8 (203)
—
12-1/8 (308)
B
4-3/16 (106)
5-7/8 (149)
7-9/16 (192)
9-1/2 (241)
—
13-1/2 (343)
—
1"
11-1/2 N.P.T.
3/4"
14 N.P.T.
Conduit Opening
➊
➋
➌
➍
➍
1 27/32
(46.8)
9/
16
(14.3)
Minimum
Spacing
1 13/64 Dia.
(30.5)
Selector switch is 1-5/32 (29.4) maximum; pilot light is 1-7/32 (31).
Selector switch is 1-3/32 (27.8) maximum; pilot light is 1-5/32 (29.4) maximum.
Selector switch is 1-7/32 (30.9) maximum; pilot light is 1-9/32 (32.5).
Minimum vertical spacing dimension for jumbo legend plate is 2-15/32 (62.7).
Operator Extension in Front of Panel ➎
Type 4/4X/13
Booted
Flush and Extended
Head Push Button
Type 4/4X/13
Pilot Light
1 3/8
(34.9)
Dia.
1 19/32 Dia.
(40.5)
Type 4/13 and
Type 4/4X/13
Bootless
Flush and Extended
Head Push Button
Type 4/13
Pilot Light
1 31/64
(37.3)
Type 4/13 and
4/4X/13
Standard Knob
Selector Switches
1 31/64 Dia.
(37.7)
1 31/64
(37.3)
Extended
Head Only
3/ (4.76)
16
23/
32
(18.2)
1 7/32
(31)
15/
32
(11.9)
1 9/32
(32.5)
1 7/32
(30.9)
➎ See pages 10-52 thru 10-55 for additional Type 4/13 outlines and pages 10-100 thru 10-103 for additional Type 4/4X/13 outlines.
10-111
1
Bulletin 800H
Hazardous Location Push Buttons
10
Type 7 & 9, for Divisions 1 & 2
Bulletin 800H
• Hazardous Locations
Push Buttons and
Stations
• Classes I, II & III
Divisions 1 & 2
• 3/4" - 14 NPSM Barrel
• Type 7 & 9
• Explosion-Proof
Operators
0
TABLE OF CONTENTS
Description
Page
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-113
Complete Assembled Stations . . . . . . . . . . . . . . . . . . . . . . . 10-114
Push Buttons, Non-Illuminated
Momentary Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-116
Dual Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-116
Push Buttons, Illuminated
Momentary Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-118
Potentiometer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-118
Push-Pull, Non-Illuminated
2-Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-120
3-Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-120
Push-Pull, Illuminated
2-Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-122
3-Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-122
Selector Switches
2-Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-124
3-Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-126
4-Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-128
Pilot Lights
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-130
Push-to-Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-130
Pigtail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-130
10-112
Description
Page
Typical Pilot Light Wiring Diagrams . . . . . . . . . . . . . . . . . . .10-130
Enclosures — Description . . . . . . . . . . . . . . . . . . . . . . . . . . .10-132
Stations — Ordering Information . . . . . . . . . . . . . . . . . . . . . .10-133
Covers, Lever Type Actuator . . . . . . . . . . . . . . . . . . . . . . . . .10-134
Covers, Component Type Button. . . . . . . . . . . . . . . . . . . . . .10-134
Assembled Bases (Field Assembly or Custom Stations) . .10-135
Bases for Multi-Gang Stations . . . . . . . . . . . . . . . . . . . . . . . .10-136
Modifications and Accessories
Contact Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-137
Color Caps, Knobs and Buttons . . . . . . . . . . . . . . . . . . . . . .10-138
Boots and Booted Knobs . . . . . . . . . . . . . . . . . . . . . . . . . . .10-139
Guards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-139
Closing Plugs, Coupler, Conduit Entry Plug . . . . . . . . . . . . .10-140
Padlocking Attachments . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-140
Flange Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-141
Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-141
Legend Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-142
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Specifications ➊
Electrical Ratings
Contact Ratings
Dielectric Strength
Electrical Design Life Cycles
Refer to the Contact Ratings tables below.
2200V for one minute, 1300V for one minute (Logic Reed)
1,000,000 at max. rated load, 200,000 at max. rated load (Logic Reed)
Mechanical Ratings
Vibration
Shock
Degree of Protection
Mechanical Design Life Cycles
Push Buttons
Potentiometers
All other devices
10…2000 Hz 1.52 mm displacement (peak-to-peak) Max./10 G Max. (except Logic Reed)
1/2 cycle sine wave for 11 ms ≥ 25 G (contact fragility) and no damage at 100 G
Type 7 & 9 Explosion Proof (Type 3 and Type 4 ratings available with accessories)
250,000 minimum
100,000 minimum
200,000 minimum
Shallow and Mini Contact Blocks:
Logic Reed & Sealed Switch Contact Blocks:
Contact Operation
Slow double make and break
Snap-action
Typical Operating Forces
Operators without contact blocks:
Spring Return Selector Switches:
Illuminated Push Buttons and Push-to-Test Pilot Lights
2-Position Push-Pull
3-Position Push-Pull
800T-XA
Logic Reed
Sealed Switch
Stackable Sealed Switch
Contact Blocks:
Flush, Extended, Standard Mushroom, Jumbo Mushroom:
2.9 lbs Max.
Jumbo and Extended Aluminum Mushroom Head:
3.95 lbs maximum
Maintained Selector Switch:
4.0 in.-lbs maximum
5 in.-lbs to stop, 0.2 in.-lbs to return
5.6 lbs maximum
9 lbs maximum push or pull
12 lbs maximum push to in position or pull to center position
(15 lbs maximum pull to out position)
1 lb
1 lb maximum
3 lbs maximum at 0.205" plunger travel
1 lb maximum
Environment
Operating
Storage
Note: Operating temperatures below freezing are based on the
absence of freezing moisture and liquids.
Humidity
–4…+131°F (–20…+55°C)
–40…+185°F (–40…+85°C)
Temperature Range
50% at +104°F (+40°C)
1
➊ Performance Data — See Page Important-2.
Standard Contact Ratings
Maximum thermal continuous current Ith 10 A AC/2.5 A DC.
Bulletin 800H Type 7 & 9 units with 800T-XA contacts have
ratings as follows:
Max. Oprtnl.
Volts Ue
Utilization Category
IEC
NEMA
AC 600
AC-15
A600
DC 600
DC-13
Q600
Rated Operational Currents
Volts Ue
Make
Break
120…600
7200 VA
720 VA
72…120
60 A
720 VA
24…28 ➋
60 A
10 A
28…600
69 VA
24…28 ➋
2.5 A
➋ For applications below 24V and 24 mA, PenTUFF , Logic Reed or
stackable sealed switch contacts are recommended.
Sealed Switch Contact Ratings
Maximum continuous current Ith 2.5 A.
Max. Oprtnl.
Volts Ue
Utilization Category
IEC
NEMA
AC 600
AC-15
B600
DC 300
DC-13
P300
Rated Operational Currents
Volts Ue
Make
Break
120…600
3600 VA
360 VA
0…120
30 A
3A
24…300
138 VA
0…24
5.0 A
Stackable Sealed Switch Contact Ratings
Maximum continuous current Ith 3 A. Bulletin 800T units have
control circuit ratings with sealed switch contact blocks as
follows:
Max. Oprtnl.
Volts Ue
Utilization Category
IEC
NEMA
AC 300
AC-15
C300
DC 150
DC-13
Q150
Logic Reed Contact Ratings
Maximum: 150V AC, 0.15 A, 8 VA and 30V DC, 0.06 A, 1.8 VA.
Should only be used with resistive loads.
PenTUFF  (Low Voltage) Contact Ratings
Minimum DC: 5V, 1 mA
Maximum thermal continuous current Ith 2.5 A AC/1.0 A DC.
Bulletin 800H units with 800T-XAV contacts have ratings as
follows:
Max. Opertnl. Utilization Category
Volts Ue
IEC
NEMA
AC 300
AC-15
C300
DC 150
DC-13
R150
Approvals
Enclosures:
UL Listed —
Devices:
UL Listed —
Stations:
CSA — File:
Rated Operational Currents
Volts Ue
Make
Break
120…300
1800 VA
180 VA
0…120
15 A
1.5 A
24…150
28 VA
0…24
1.0 A
File: E71673
Guide: NNNY
File: E10314
Guide: NOIV
LR11924
Rated Operational Currents
Volts Ue
Make
Break
120…300
1800 VA
180 VA
0…120
15 A
1.5 A
24…150
69 VA
0…24
2.5 A
10-113
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Complete Assembled Stations (Supplied with 3/4" Dead End Conduit Entry)
Photo
Operator
Contact
Symbol
(1/2 Lever
Momentary)
1 N.O. 1 N.C.
One
Push
Button
Cat. No. 800H-1HA7
(Full Lever
Momentary)
Two
Push Buttons
1 N.O. 1 N.C.
Each
Button
Cat. No. 800H-2HA7P
(Full Lever
Maintained)
0
2-Position
Selector
Switch
1 N.O. 1 N.C.
Cat. No. 800H-2HAM7
3-Position
Selector
Switch
Lever Type
Actuator ➊
Component Type
Buttons ➋
Cat. No.
Cat. No.
STOP
800H-1HA7
800H-1HA7P
START
800H-1HB7
800H-1HB7P
JOG
800H-1HJ7
800H-1HJ7P
No Legend Plate
supplied.
800H-1HX7
800H-1HX7P
START-STOP
800H-2HA7
800H-2HA7P
FOR-REV
800H-2HB7
800H-2HB7P
RAISE-LOWER
800H-2HD7
800H-2HD7P
OPEN-CLOSE
800H-2HF7
800H-2HF7P
No Legend Plate
supplied.
800H-2HX7
800H-2HX7P
START-STOP
800H-2HAM 7
—
ON-OFF
800H-2HCM 7
800H-R2HC7
OPEN-CLOSE
800H-2HGM 7
800H-R2HG7
RUN-STOP
800H-2HJM7
—
HAND-AUTO
800H-2HLM7
800H-R2HA7
No Legend Plate
supplied.
800H-2HXM7
800H-R2HX7
HAND-OFF-AUTO
—
800H-R3HA7
No Legend plate
supplied.
—
800H-R3HX7
START-STOP
—
800H-2HAD10R7
Marking other than
listed — consult your
local Allen-Bradley
Sales Office.
—
800H-2HXD10R7
Legend Marking
1 N.O. 1 N.C.
Cat. No. 800H-R3HA7
Dual Push
Button
One
Pilot light
120V AC/DC
Full Volt./Red
1 N.O. 1 N.C.
Cat. No. 800H-2HAD10R7
➊ Operators have integral padlocking attachment.
➋ STOP is extended red, START is flush green, all others are flush black.
Legend Plates — Page 10-142
10-114
Approximate Dimensions — Page 10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Complete Assembled Stations — Lever Type Actuators
800H – 2H
A
a
b
7
c
d
e
f
a
b (cont’d)
c
e
No. of Operators
Legend Marking
Pilot Light Option (2-Gang)
Station Options
Code
Description
Code
Description
1H
1 Operator
Code
Description
Blank
No Pilot Light Required
Code
2H
2 Operator
D
RAISE LOWER
R
120V Full Voltage Red
Blank
No Options
3H
3 Operator
F
OPEN CLOSE
P
240V Full Voltage Red
b
G
JOG STOP
Y
480V Transformer Red
R➊
Sealing Well —
with Type 3 Flange
J
RUN STOP
V
600V Transformer Red
K➊
Sealing Well
K
JOG RUN
F
120V Full Voltage Green
S
Type 3 Flange Seal
L
HAND AUTO
H
240V Full Voltage Green
X
No Legend
J
480V Transformer Green
K
600V Transformer Green
2 Operator (1-Gang)
Legend Marking
1 Operator (1-Gang)
Code
Description
A
STOP
B
START
Code
Description
J
JOG
A
FOR REV STOP
No Legend
C
X
3 Operator (2-Gang)
2 Operator (1-Gang)
Accessories
Description
f
1-Gang Conduit Options
Note: Available with 1 or 2 operators only.
Becomes a 2-Gang station.
Code
Description
Blank
3/4" Dead End
UP DOWN STOP
d
M1
3/4" Feed Through
Station Type
D
OPEN CLOSE STOP
Code
Description
F
FAST SLOW STOP
A
START STOP
G
START JOG STOP
B
FOR REV
X
No Legend
M2
1" Dead End
M3
1" Feed Through
Code
Description
7
Type 7 & 9
Code
Description
M7
2 Button Maintained
Blank
1" Dead End
MY7
Momentary/Maintained
M3
1" Feed Through
Multi-Gang Conduit Options
Complete Assembled Stations — Push Button Type Actuators
800H – 2H
a
A
R
7P
b
c
d
e
f
a
b (cont’d)
b (cont’d)
d
No. of Push Buttons
Legend Markings
Legend Markings
Station Rating
2 Push Buttons (1-Gang)
3-Position Selector (1-Gang)
Code
Description
1H
1 Push Button
Code
Description
Code
Description
2H
2 Push Button
A
START STOP
A
HAND OFF AUTO
Code
1
Description
7P
Type 7 & 9
7
Type 7 & 9 Selector Stations or
Dual Operator Station
3H
3 Push Button
B
FOR REV
B
FORWARD OFF REVERSE
R2H
2-Position Selector
D
RAISE LOWER
G
OPEN OFF CLOSE
e
R3H
3-Position Selector
F
OPEN CLOSE
X
No Legend
2H
Dual Push Button
G
JOG STOP
Station Options
K
JOG RUN
Code
Description
X
No Legend
AD
START STOP
XD
Blank Legend
b
Legend Markings
1 Push Button (1-Gang)
3 Push Buttons (2-Gang)
Code
Description
A
FOR REV STOP
Dual Push Button (1-Gang)
Accessories
Code
Description
Blank
No Options
c
W
Padlocking Attachment on Stop
Button
Pilot Light Option
R➊
Sealing Well —
with Type 3 Flange
Dual Push Button/Pilot Light
K➊
Standard Sealing Well
S
Type 3 Flange Seal
Code
Description
A
STOP (Red)
C
UP DOWN STOP
B
START (Green)
D
OPEN CLOSE STOP
J
JOG
F
FAST SLOW STOP
Code
Description
X
No Legend
G
START JOG STOP
10R
120V Full Voltage Red
X
No Legend
20R
240V Full Voltage Red
f
Conduit Options
2 Push Button/Pilot Light ➋
2-Position Selector (1-Gang)
Code
Description
Code
Description
Code
Description
A
HAND AUTO
Blank
No Pilot Light Required
Blank
3/4" Dead End
3/4" Feed Through
B
FOR REV
R
120V Full Voltage Red
M1
C
OFF ON
P
240V Full Voltage Red
M2
1" Dead End
G
OPEN CLOSE
Y
480V Transformer Red
M3
1" Feed Through
K
JOG RUN
V
600V Transformer Red
F
120V Full Voltage Green
H
240V Full Voltage Green
G
480V Transformer Green
K
600V Transformer Green
➊ Sealing wells should only be used on stations having 1" conduit entries.
➋ 2-gang station.
10-115
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Momentary Contact Push Button Units, Non-Illuminated
Flush Head Unit
Cat. No. 800H-AP1A
0
Extended Head Unit
Cat. No. 800H-BP6B
Mushroom Head Unit
Cat. No. 800H-DP6A
Flush Head
Extended Head
Cat. No.
Cat. No.
Cat. No.
Green
Black
Red
800H-AP1
800H-AP2
—
800H-BP1
800H-BP2
800H-BP6
800H-DP1
800H-DP2
800H-DP6
1 N.O.
Green
Black
Red
800H-AP1D1
800H-AP2D1
—
800H-BP1D1
800H-BP2D1
800H-BP6D1
800H-DP1D1
800H-DP2D1
800H-DP6D1
1 N.C.
Green
Black
Red
800H-AP1D2
800H-AP2D2
—
800H-BP1D2
800H-BP2D2
800H-BP6D2
800H-DP1D2
800H-DP2D2
800H-DP6D2
1 N.O. - 1 N.C.
Green
Black
Red
800H-AP1A
800H-AP2A
—
800H-BP1A
800H-BP2A
800H-BP6A
800H-DP1A
800H-DP2A
800H-DP6A
2 N.O. - 2 N.C.
Green
Black
Red
800H-AP1B
800H-AP2B
—
800H-BP1B
800H-BP2B
800H-BP6B
800H-DP1B
800H-DP2B
800H-DP6B
Contact Type
Button Color
No Contact
Mushroom Head
Dual Push Button Units
Dual Push Button Unit
Cat. No. 800H-DPH16AAXX64
Contact Arrangement
Type
2 N.O. - 2 N.C.
Accessories — Page 10-137
Legend Plates — Page 10-142
10-116
Contacts
Legend Marking
Cat. No.
Left
Right
START
(Flush/Green)
STOP
(Extended/Red)
800H-DPH16AAXX64
ON
(Flush/Black)
OFF
(Flush/Black)
800H-DPH22AAXX50
OPEN
(Flush/Black)
CLOSE
(Flush/Black)
800H-DPH22AAXX57
UP
(Flush/Black)
DOWN
(Flush/Black)
800H-DPH22AAXX66
Blank
(Flush/Black)
Blank
(Flush/Black)
800H-DPH22AAXX
Approximate Dimensions — Page 10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Momentary Contact Push Button Units, Non-Illuminated
800 H
– AP
a
1
b
c
A
d
e
a
Barrel Type
c
e
Color Cap
Contact Block(s) ➊
Code
Description
Code
Description
H
Standard Barrel Length
Blank
Used only when ordering Operator Type DPX
Code
Description
HL
Long Barrel
1
Green
Blank
No Contacts
b
2
Black
D1
1 N.O.
3
Orange
D2
1 N.C.
4
Gray
D5
1 N.O. (Mini)
6
Red
D6
1 N.C. (Mini)
7
Blue
A2
2 N.O.
9
Yellow
A4
2 N.C.
A
1 N.O. - 1 N.C.
Operator Type
Code
Description
AP
Flush Head
BP
Extended Head
DP
Mushroom Head
DPX
Mushroom Head less Color Cap
Standard
d
Special Mushroom Head
Code
Description
Blank
No Special Head
J
Jumbo Mushroom Head — Plastic
L
Jumbo Mushroom Head — Metal
B
2 N.O. - 2 N.C.
H
3 N.O. - 3 N.C.
C
Note: Special Mushroom Head options only apply to
Mushroom Head operator Type Code DP.
4 N.O. - 4 N.C.
Pen TUFF (Low Voltage)
Code
Description
D1V
1 N.O.
D2V
1 N.C.
AV
1 N.O. - 1 N.C.
BV
2 N.O. - 2 N.C.
HV
3 N.O. - 3 N.C.
CV
4 N.O. - 4 N.C.
Dual Push Button Units
1
800 H – DP
a
b
H
16
AAXX
64
c
d
e
f
a
d
f
Barrel Type
Color of Button
Marking
Code
Description
Code
Description
H
Standard Barrel
16
Left Green Flush/Right Red Extended
HL
Long Barrel
22
Left Black Flush/Right Black Flush
Description
b
e
Operator Type
Contact Block(s)
Code
Description
DP
Dual Push Button
Contact Arrangement
Code
Description
H
Horizontal
B
Vertical
Right Button for
Horizontal
Bottom Button for
Vertical
Blank
No Mark
Specified
No Mark
Specified
STOP
64
START
Left Button for
Horizontal
Top Button for
Vertical
Right Button for
Horizontal
Bottom Button for
Vertical
50
ON
OFF
51
FORWARD
REVERSE
57
OPEN
CLOSE
AAXX
1 N.O. - 1 N.C.
1 N.O. - 1 N.C.
66
UP
DOWN
AAAA
2 N.O. - 2 N.C.
2 N.O. - 2 N.C.
99 ➋
Marking
Specified
Marking
Specified
Code
c
Mounting
Left Button for
Horizontal
Top Button for Vertical
Code
➊ For sealed switch and Logic Reed contact blocks, refer to the 800T section, page 10-10.
➋ To order with special marking, specify marking; seven characters maximum per button, single line only.
10-117
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Momentary Contact Push Button Units, Illuminated
Extended Head with Guard
Cat. No. 800H-PPB16R
Type
Lamp
Color
120 AC
Red
Green
Amber
800H-QPB10R
800H-QPB10G
800H-QPB10A
24 AC/DC
Red
Green
Amber
800H-QPB24R
800H-QPB24G
800H-QPB24A
120 AC
Red
Green
Amber
800H-PPB16R
800H-PPB16G
800H-PPB16A
120 AC
Red
Green
Amber
800H-QPBH10R
800H-QPBH10G
800H-QPBH10A
24 AC/DC
Red
Green
Amber
800H-QPBH24R
800H-QPBH24G
800H-QPBH24A
120 AC
Red
Green
Amber
800H-PPBH16R
800H-PPBH16G
800H-PPBH16A
Full Voltage
Incandescent
Transformer
Full Voltage
LED
0
Transformer
Extended Head with Guard
Volts
Cat. No.
Potentiometer Units
Potentiometer Unit
Cat. No. 800H-UP24
Resistance
Potentiometer
Cat. No.
Resistance
Potentiometer
Cat. No.
Operator Only
(without Resistive Element)
800H-NP37
2500 Ω
800H-UP19
5000 Ω
800H-UP24
1000 Ω
800H-UP13
10 kΩ
800H-UP29
Accessories — Page 10-137
Legend Plates — Page 10-142
10-118
Approximate Dimensions — Page 10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Momentary Contact Push Button Units, llluminated
800 H – PPB
a
b
H
16
R
c
d
e
f
a
c
d
e
Operator Type
Illumination Options
Voltage
Lens Color
Code
Color
Description
Blank
No Lens, No Contact Block
36
48V AC 50/60 Hz
X
16
120V AC 50/60 Hz
No Lens if ordering any Contact
Block D1-A7
LED ➌
26
240V AC 50/60 Hz
A
Amber
Full Voltage
76
277V AC 50/60 Hz
Transformer
Transformer
Code
Description
H
Standard Barrel Length
Code
Description
Code
HL
Long Barrel
Blank
Standard Pilot Light
F
Flashing Lamp ➋
b
Power Module Type
Code
Description
PPB
Transformer
(or Dual Input)
QPB
Full Voltage
(or Resistor)
RPB
Neon ➊
H
Code
Description
46
480V AC 50/60 Hz
Blank
Standard Pilot Light
56
600V AC 50/60 Hz
F
Flashing Lamp ➋
H
LED ➌
Blank
Blank
Green
R
Red
W
White
6V AC/DC
f
12V AC/DC
Contact Block(s)
No Options
24
24V AC/DC
32
32V AC/DC ➎
Code
Description
Description
48
48V AC/DC
Blank
1 N.O. - 1 N.C.
No Options
13
130V AC/DC ➎
D1
1 N.O.
10
120V AC/DC ➏
20
240V AC/DC ➎
Description
Resistor
D
Diode Type ➍
DH
Diode Type LED ➌➍
Code
Description
T
Transformer —
Relay Type
11
120V AC/DC Resistor
Transformer —
Relay Type LED ➌
Code
Description
10
120V AC/DC
20
240V AC/DC
TH
G
12
Dual Input
Code
Description
Clear
Description
Neon
Code
Code
Blue
C
06
Resistor
Code
Full Voltage
B
Neon
Dual Input
Code
Description
16
120V AC
24
24V AC/DC ➐
Standard
D2
1 N.C.
A2
2 N.O.
A4
2 N.C.
Pen TUFF (Low Voltage)
Code
Description
D1V
1 N.O.
D2V
1 N.C.
AV
1 N.O. - 1 N.C.
1
Note: For Sealed Switch and Logic Reed
contact blocks, refer to the 800T Section,
page 10-17.
➊ Neon is only available in amber or clear.
➋ Flashing lamps are only available in 6V full voltage units and all transformer units.
➌ LEDs available in red, green, amber, blue, and white. White LEDs only available in 6V and 24V full voltage and all transformer units. LED color
must match lens color, except clear lens supplied with white LED and white lens supplied with amber LED. All LEDs except 120V have an
internal shunt resistor for use with solid-state outputs.
➍ Diode type dual input provides circuit isolation via opposing diodes. Not recommended for use with solid-state outputs and neon indicators.
➎ 32V and 130V are LED only. 240V is incandescent only.
➏ 120V LED is AC only and does not contain internal shunt resistor. For AC/DC and internal shunt resistor, order 130V AC/DC LED (Code 13).
➐ Dual input diode only.
10-119
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
2-Position Push-Pull Units, Non-Illuminated
2-Position Push-Pull
Cat. No. 800H-FPX6A5
Operator Position
Contact Type
Maintained
Button
Color
Push-Pull
Out
Maintained
In
N.C.L.B
X
O
Red
800H-FPX6D4
N.O.N.C.L.B.
O
X
X
O
Red
800H-FPX6A1
N.C.L.B.N.C.L.B.
X
X
O
O
Red
800H-FPX6A5
Button
Color
Push-Pull
Cat. No.
Note: X = Closed/O = Open
3-Position Push-Pull Units, Non-Illuminated
0
3-Position Push-Pull
Cat. No. 800H-FPXM6A7
Operator Position
Contact Type
N.C.N.C.L.B.
Momentary
Maintained
Maintained
Out
Center
In
X
X
O
X
O
O
Cat. No.
Red
800H-FPXM6A7
Button
Color
Push-Pull
Operator Position
Contact Type
N.C.N.C.L.B.
Momentary
Maintained
Momentary
Out
Center
In
X
X
O
X
O
O
Cat. No.
Red
800H-FPXN6A7
Note: X = Closed/O = Open
Accessories — Page 10-137
Legend Plates — Page 10-142
10-120
Approximate Dimensions — Page 10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
2-Position Push-Pull Units, Non-Illuminated
800 H – FPX
a
b
c
1
A1
d
e
a
d
e
Barrel Type
Color Cap
Contact Block(s)
Code
Description
Code
Color
H
Standard Barrel Length
Blank
No Cap
HL
Long Barrel
1
Green
b
2
Black
Operator Type
4
Gray (Silver)
Standard
Operator
Position
Code
Description
6
Red
Out
In
Code
Description
7
Blue
Blank
—
—
No Contacts
FPX
Push-Pull Unit
9
Yellow(Gold)
A1
O
X
X
O
1 N.O. 1 N.C.L.B. ➊
A5
X
X
O
O
2 N.C.L.B. ➊
D1
O
X
1 N.O.
D4
X
O
1 N.C.L.B. ➊
c
Head Type
Code
Description
Blank
Mushroom Head
J
Jumbo Mushroom Head ➊
Pen TUFF (Low Voltage)
Operator
Position
Code
Description
Out
In
D1V
O
X
1 N.O.
AV
O
X
X
O
1 N.O. - 1 N.C.
Note: X = Closed/O = Open.
3-Position Push-Pull Units, Non-Illuminated
1
800 H – FPX
a
b
M
1
A7
d
e
f
c
a
d
f
Barrel Type
Operator Function
Contact Block(s)
Code
Description
H
Standard Barrel Length
HL
Long Barrel
Operator Position
Standard
Operator Position
Code
Code
b
Out
Center
Operator Type
M
Momentary
Maintained
Maintained
Code
Description
N
Momentary
Maintained
Momentary
FPX
Push-Pull Unit
e
c
Head Type
Color Cap
Code
Color
Code
Description
Blank
No Cap
Blank
Mushroom Head
1
Green
J
Jumbo Mushroom Head ➋
2
Black
4
Gray(Silver)
6
Red
7
Blue
9
Yellow(Gold)
Description
In
Out
Ctr.
In
Blank
—
—
—
No Contacts
A
O
X
O
O
X
O
1 N.O. 1 N.C.
A1
O
X
O
X
X
O
1 N.O. 1 N.C.L.B.
A7
X
X
O
X
O
O
1 N.C. 1 N.C.L.B.
Pen TUFF (Low Voltage)
Operator Position
Code
AV
Description
Out
Ctr.
In
O
X
O
O
X
O
1 N.O. 1 N.C.
Note: X = Closed/O = Open.
➊ Normally closed late break contact. When button is pushed from the OUT to the IN position, the mechanical detent action of the operator occurs
before electrical contacts change state. When the button is pulled from the IN to the OUT position, the electrical contacts change state before
the mechanical detent occurs.
➋ Not valid with color cap option Blank (no cap).
10-121
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
2-Position Push-Pull Units, Illuminated
Illuminated 2-Position Push-Pull
Cat. No. 800H-FPXP16RA1
Operator Position
Type
Lamp
Volts
Push-Pull
Color
120 AC
Full Voltage
24 AC/DC
Incandescent
120 AC
Transformer
240 AC
120 AC
Full Voltage
24 AC/DC
LED
120 AC
Transformer
240 AC
Contacts
N.O. N.C.L.B.
N.O. N.C.L.B.
N.O. N.C.L.B.
N.O. N.C.L.B.
Red
Red
Red
Red
Red
Red
Red
Red
Maintained
Maintained
Out
O
X
O
X
O
X
O
X
In
X
O
X
O
X
O
X
O
Cat. No.
800H-FPXQ10RA1
800H-FPXQ24RA1
800H-FPXP16RA1
800H-FPXP26RA1
800H-FPXQH10RA1
800H-FPXQH24RA1
800H-FPXPL16RA1
800H-FPXPL26RA1
Note: X = Closed/O = Open
3-Position Push-Pull Units, Illuminated
0
Illuminated 3-Position Push-Pull
Cat. No. 800H-FPXMP16RA7
Operator Position
Momentary
Maintained
Maintained
Out
X
X
Center
O
X
In
O
O
Contacts
N.C. N.C.L.B.
Type
Full Voltage
Lamp
Incandescent
Transformer
Full Voltage
Operator Position
LED
Transformer
Volts
Color
120 AC
24 AC/DC
120 AC
120 AC
24 AC/DC
120 AC
Red
Red
Red
Red
Red
Red
Contacts
N.C. N.C.L.B.
Push-Pull
Cat. No.
800H-FPXMQ10RA7
800H-FPXMQ24RA7
800H-FPXMP16RA7
800H-FPXMQH10RA7
800H-FPXMQH24RA7
800H-FPXMPL16RA7
Momentary
Maintained
Momentary
Out
X
X
Center
O
X
In
O
O
Push-Pull
Cat. No.
800H-FPXNQ10RA7
800H-FPXNQ24RA7
800H-FPXNP16RA7
800H-FPXNQH10RA7
800H-FPXNQH24RA7
800H-FPXNPL16RA7
Note: X = Closed/O = Open
Accessories — Page 10-137
Legend Plates — Page 10-142
10-122
Approximate Dimensions — Page 10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
2- and 3-Position Push-Pull Units, Illuminated
800 H – FPX
a
b
PH
16
R
A1
d
e
f
g
c
a
d
e
f
Barrel Type
Illumination Options
Voltage
Color Cap
Code
H
HL
Description
Standard Barrel Length
Long Barrel
Transformer
Code
P
PF
PH
b
Operator Type
Code
FPX
Code
36
16
26
76
46
56
Full Voltage
Description
Push-Pull Unit
Code
Q
QF
QH
c
Operator Function
Description
Standard Incandescent
Flashing Lamp ➊
LED ➋
Code
Description
Push-Pull
Push-Pull/Twist
Description
Incandescent
Lamp
Q
Neon
3-Position
Code
R
Operator Position
Description
Neon Lamp ➌
Dual Input
Code
D
DH
Code
Out
Ctr.
In
★
★
‡
‡
‡
★
M
N
★ Momentary
DT
‡ Maintained
DTH
Description
48V AC 50/60 Hz
120V AC 50/60 Hz
240V AC 50/60 Hz
277V AC 50/60 Hz
480V AC 50/60 Hz
600V AC 50/60 Hz
Code
X
A
B
C
G
R
W
Full Voltage
Code
06
12
24
32
48
13
10
20
Resistor
2-Position
Code
Blank
T
Transformer
Description
Standard Incandescent
Flashing Lamp ➊
LED ➋
Description
Dual Input — Diode ➍
Dual Input — Diode Type LED ➍➋
Dual Input —
Transformer Relay
Dual Input Transformer —
Relay LED ➋
Description
6V AC/DC
12V AC/DC
24V AC/DC
32V AC/DC ➏
48V AC/DC
130V AC/DC ➏
120V AC/DC ➎
240V AC/DC ➏
Resistor
Code
11
Description
120V AC/DC Resistor
Neon
Code
10
20
Description
120V AC/DC
240V AC/DC
Dual Input
Code
16
24
Description
120V AC
24V AC/DC ➑
Color
No Cap
Amber
Blue
Clear
Green
Red
White
g
Contact Blocks
Standard
Code
Blank
D1
D4
A
A1
A2
A5
A7
Color
No Contacts
1 N.O.
1 N.C.L.B. ➐
1 N.O. - 1 N.C.
1 N.O. 1 N.C.L.B. ➐
2 N.O.
2 N.C.L.B.
1 N.C. 1 N.C.L.B. ➐
Pen TUFF (Low Voltage)
Code
D1V
D2V
AV
Description
1 N.O.
1 N.C.
1 N.O. - 1 N.C.
Logic Reed
Code
D1R
D2R
AR
A2R
A4R
Color
1 N.O.
1 N.C.
1 N.O. - 1 N.C.
2 N.O.
2 N.C.
Table 1. Target Selection
2-Position
g
Code
A, AV, R
A1
A2
A5
—
D1, D1V, D1R
D4
3-Position
Contact
Description
Out
In
O
X
O
X
O
O
X
X
—
—
O
X
X
O
X
O
X
X
O
O
—
—
X
O
N.O.
N.C.
N.O.
N.C.L.B.
N.O.
N.O.
N.C.L.B
N.C.L.B
N.C.
N.C.L.B.
N.O.
N.C.L.B.
Out
Ctr.
In
O
X
O
X
—
—
—
—
X
X
—
—
O
O
O
X
—
—
—
—
O
X
—
—
X
O
X
O
—
—
—
—
O
O
—
—
g
Code
A, AV, AR
A1
—
—
A7
—
—
➊ Flashing lamps are only available in 6V full voltage units and all
transformer units.
➋ LEDs available in red, green, amber, blue, and white. White LEDs
only available in 6V and 24V full voltage and all transformer units.
LED color must match lens color, except clear lens supplied with white
LED and white lens supplied with amber LED. All LEDs except 120V
have an internal shunt resistor for use with solid-state outputs.
➌ Neon is only available in amber or clear.
➍ Diode type dual input provides circuit isolation via opposing diodes.
Not recommended for use with solid-state outputs and neon
indicators.
➎ 120V LED is AC only and does not contain internal shunt resistor. For
AC/DC and internal shunt resistor, order 130V AC/DC LED (Code 13).
➏ 32V and 130V are LED only. 240V is incandescent only.
➐ Normally closed late break contact. When button is pushed from the
OUT to the IN position, the mechanical detent action of the operator
occurs before electrical contacts change state. When the button is
pulled from the IN to the OUT position, the electrical contacts change
state before the mechanical detent occurs.
➑ Dual input diode only.
10-123
1
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
2-Position Selector Switch Units, Non-Illuminated
Standard Knob Operator
Cat. No. 800H-HP2KB6AXXX
Knob Lever Operator
Cat. No. 800H-HP17KB6AXXX
Operator Position
Contact Type
No Contacts
0
—
—
1 N.O.
O
X
1 N.O.1 N.C.
O
X
X
O
2 N.O.2 N.C.
O
X
O
X
X
O
X
O
Metal Wing Lever Operator
Cat. No. 800H-HP11KBAXXX
Operator Type
Standard Knob
Knob Lever
Wing Lever
M = Maintained
S = Spring Return
Cat. No.
Cat. No.
Cat. No.
M M
S→M ➊
M M
S→M ➊
M←S
M M
S→M ➊
M←S
800H-HP2KB6
800H-HP4KL8
800H-HP2KB6DXXX
800H-HP4KB6DXXX
800H-HP5KL8DXXX
800H-HP2KB6AXXX
800H-HP4KL8AXXX
800H-HP5KL8AXXX
800H-HP17KB6
800H-HP18KL8
800H-HP17KB6DXXX
800H-HP18KB6DXXX
800H-HP19KL8DXXX
800H-HP17KB6AXXX
800H-HP18KL8AXXX
800H-HP19KL8AXXX
800H-HP11KB6
800H-HP15KL8
800H-HP11KB6DXXX
800H-HP15KB6DXXX
800H-HP16KL8DXXX
800H-HP11KB6AXXX
800H-HP15KL8AXXX
800H-HP16KL8AXXX
800H-HP2KB6AAXX
800H-HP17KB6AAXX
800H-HP11KB6AAXX
S→M ➊
800H-HP4KL8AAXX
800H-HP18KL8AAXX
800H-HP15KL8AAXX
M←S
800H-HP5KL8AAXX
800H-HP19KL8AAXX
800H-HP16KL8AAXX
M
M
Note: X = Closed/O = Open
2-Position Cylinder Lock Operator
Cat. No. 800H-HP31KB6AXXX
Contact Type
Operator
Position
—
—
1 N.O.
O
X
1 N.O.1 N.C.
O
X
X
O
2 N.O.2 N.C.
O
X
O
X
X
O
X
O
No Contacts
Operator Type
M = Maintained
S = Spring Return
Cylinder Lock
Key Removal Left ➋
Cat. No.
800H-HP31KB6
800H-HP48KL8
800H-HP31KB6DXXX
—
800H-HP48KL8DXXX
800H-HP31KB6AXXX
—
800H-HP48KL8AXXX
Key Removal Right ➋
Cat. No.
800H-HP32KB6
—
800H-HP32KB6DXXX
800H-HP42KL8DXXX
—
800H-HP32KB6AXXX
800H-HP42KL8AXXX
—
Key Removal Both ➋
Cat. No.
800H-HP33KB6
—
800H-HP33KB6DXXX
—
—
800H-HP33KB6AXXX
—
—
800H-HP31KB6AAXX
800H-HP32KB6AAXX
800H-HP33KB6AAXX
S→M ➊
—
800H-HP42KL8AAXX
—
M←S
800H-HP48KL8AAXX
—
—
M M
M←S
M M
S→M ➊
M←S
M M
S→M ➊
M←S
M
M
Note: X = Closed/O = Open
➊ Target tables are reversed from those shown.
➋ Key removable from maintained positions only.
Accessories — Page 10-137
Legend Plates — Page 10-142
10-124
Approximate Dimensions — Page 10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
2-Position Selector Switch Units, Non-Illuminated
800 H – HP
a
b
800 H – HP
a
b
A
2
KB6
c
d
e
31
c1
KB6
d1
AXXX (Knob/Wing Lever)
f
AXXX (Cylinder Lock)
e
f
a
d
e
Barrel Type
Operator Type and Function
Cam Option
Standard Knob
Code
Description
H
Standard Barrel Length
Code
HL
Long Barrel
b
Number of Positions
Code
Description
HP
2-Position
Code
Description
Operator Function
KB6
Cam for maintained operators
2
Maintained
KL8
Cam for spring return operators
4
Spring Return From Left ➌
5
Spring Return From Right
f
Contact Block(s)
Knob Lever
Code
Operator Function
17
Maintained
c
18
Spring Return From Left ➌
Knob Insert Colors ➊
19
Spring Return From Right
Standard
Description
2-Position
Code
Contact
Configuration
Metal Wing Lever
Code
Color
Blank
White
Code
Operator Function
Blank
No Contacts
—
A
Red
11
Maintained
DXXX
1 N.O.
O
X
B
Green
15
Spring Return From Left ➌
EXXX
1 N.C.
X
O
C
Blue
16
Spring Return From Right
MXXX
2 N.O.
O
X
E
Yellow
F
Orange
X
Packet of Colored Inserts ➋
d1
NXXX
Optional Keys
D Series
Key No.
Code
Blank
D018
(Std. Key)
15
T112
03
D020
16
T115
04
D025
17
T324
05
D335
18
T382
Key Removal Position
06
D429
19
T404
Maintained
07
D461
20
T171
Metal Wing Lever Colors
Code
Color
A
Red
Blank
Gray
c1
Code
T Series
Key No.
Code
Operator Function
08
D111
21
T484
31
Key Removal — Left
09
D587
22
T547
32
Key Removal — Right
10
D682
23
T569
33
Key Removal — Both
11
D713
24
Spring Return From Left
12
D900
25
2 N.C.
AXXX
1 N.O. - 1 N.C.
AAXX
2 N.O. 2 N.C.
X
O
O
X
X
O
O
X
X
O
O
X
X
O
Pen TUFF (Low Voltage)
Description
2-Position
HXXX
1 N.O.
O
X
T752
UXXX
1 N.C.
X
O
FXXX
1 N.O. - 1 N.C.
FFXX
2 N.O. 2 N.C.
Operator Function
13
D992
26
T178
14
D118
—
—
Spring Return From Right
Key Removal — Left
O
T692
Key Removal — Right ➌
48
X
X
Contact
Configuration
42
Operator Function
O
Code
Code
Code
—
O
X
X
O
O
X
X
O
O
X
X
O
Note: X = Closed/O = Open.
➊ Each standard and knob lever operator is factory assembled with a white insert. Other colors are available, factory assembled, if ordered in
quantities of 10 or more.
➋ Packet of colored inserts, one of each color except orange.
➌ Target tables are reversed from those shown.
10-125
1
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
3-Position Selector Switch Units, Non-Illuminated
Standard Knob Operator
Cat. No. 800H-JP2KB7AXXX
Knob Lever Operator
Cat. No. 800H-JP17KB7AXXX
Operator Position
Contact
Type
Operator Type
M = Maintained
S = Spring Return
M
No
Contacts
—
—
—
11N.O.
N.O.1 N.C.
0
2 N.O. 2 N.C.
O
X
O
X
O
O
O
O
X
O
X
O
X
O
Knob Lever
Metal Wing Lever
Cat. No.
Cat. No.
Cat. No.
M
M
800H-JP2KB7
800H-JP17KB7
800H-JP11KB7
M
800H-JP4KB7
800H-JP18KB7
800H-JP15KB7
M←S
800H-JP5KB7
800H-JP19KB7
800H-JP16KB7
800H-JP91KB7
800H-JP20KB7
800H-JP141KB7
M
M
M
800H-JP2KB7AXXX
800H-JP17KB7AXXX
800H-JP11KB7AXXX
S→M
M
800H-JP4KB7AXXX
800H-JP18KB7AXXX
800H-JP15KB7AXXX
M←S
800H-JP5KB7AXXX
800H-JP19KB7AXXX
800H-JP16KB7AXXX
S→M←S
800H-JP91KB7AXXX
800H-JP20KB7AXXX
800H-JP141KB7AXXX
M
M
O
O
Standard Knob
S→M
S→M←S
O
X
Metal Wing Lever Operator
Cat. No. 800H-JP11KB7AXXX
M
M
M
800H-JP2KB7AAXX
800H-JP17KB7AAXX
800H-JP11KB7AAXX
S→M
M
800H-JP4KB7AAXX
800H-JP18KB7AAXX
800H-JP15KB7AAXX
M←S
800H-JP5KB7AAXX
800H-JP19KB7AAXX
800H-JP16KB7AAXX
S→M←S
800H-JP91KB7AAXX
800H-JP20KB7AAXX
800H-JP141KB7AAXX
M
Note: X = Closed/O = Open
3-Position Cylinder Lock Operator
Cat. No. 800H-JP42KB7AXXX
Operator Position
Contact
Type
Operator Type
M = Maintained
S = Spring Return
M
No
Contacts
—
—
—
M
M
S→M
M
M
M←S
S→M←S
M
1 N.O. 1 N.C.
O
X
O
O
X
O
M
M
S→M
M
M
M←S
S→M←S
Cylinder Lock
Key Removal All ➊
Key Removal Left
Key Removal Center
Cat. No.
Cat. No.
Cat. No.
800H-JP41KB7
800H-JP42KB7
800H-JP44KB7
—
800H-JP50KB7
800H-JP51KB7
800H-JP69KB7
800H-JP38KB7
800H-JP73KB7
—
800H-JP631KB7
—
800H-JP41KB7AXXX
800H-JP42KB7AXXX
800H-JP44KB7AXXX
—
800H-JP50KB7AXXX
800H-JP51KB7AXXX
800H-JP69KB7AXXX
800H-JP38KB7AXXX
800H-JP73KB7AXXX
—
800H-JP631KB7AXXX
—
Note: X = Closed/O = Open
➊ Key removable in maintained positions only.
Accessories — Page 10-137
Legend Plates — Page 10-142
10-126
Approximate Dimensions — Page 10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
3-Position Selector Switch Units, Non-Illuminated
800 H – JP
a
b
c
800 H – JP
a
2
KB7
d
e
f
KB7
AAXX
e
f
41
b
d1
c1
a
c1
Cylinder Lock Operators
Barrel Type
Code
Description
H
Standard Barrel Length
Code
HL
Long Barrel
b
Description
JP
3-Position
(Cylinder Lock)
d
e
Knob/Lever Type Operators
Cam Option
Maintained Position
Number of Positions
Code
AAXX (Knob/Wing Lever)
c
Standard Knob
Locking Position
Code
41
Left
2
Maintained
42
Center
4
Spring Return from Left
43
Right
5
Spring Return from Right
44
All
91
Spring Return from Both
45
Left and Center
46
Right and Left
Code
Operator Function
47
Right and Center
17
Maintained
f
Contact Block Option
Spring Return from Left
Code
Blank
No Contacts
20
Spring Return from Both
AXXX
2 contact targets for a given cam
as shown in the W (white side)
column of Table 1.
Blank
50
Center
52
Right
A
Red
51
B
Green
Metal Wing Lever ➌
Right and Center
Spring Return from Right
Code
Operator Function
11
Maintained
Spring Return from Left
C
Blue
Code
Locking Position
15
E
Yellow
69
Left
16
Spring Return from Left
F
Orange
38
Center
141
Spring Return from Both
X
Packet of
Colored Inserts ➋
73
Red
Blank
Gray
Cam KA7 (See Table 1)
Note: For additional Cam descriptions, see
Table 1.
Spring Return from Right
Color
Color
Cam KA1 (See Table 1)
KA7
19
White knob insert or Cylinder Lock
Operator
A
KA1
18
Code
Code
Standard Cam KB7
(See Table 1)
Locking Position
Code
Left and Center
Code
Locking Position
631
Center
4 contact targets for a given cam
as shown in the W (white side)
column of Table 1 and
4 contact targets for the same cam
AAAA
as shown in the B (black side)
column of Table 1.
(2-800T-XA Contact Blocks per
side.
4 Contact Blocks total.)
Standard Knob
Code
Key No.
Blank
D018 (Standard Key)
Description
2 contact targets for a given cam
as shown in the W (white side)
column of Table 1 and
2 contact targets for the same cam
AAXX
as shown in the B (black side)
column of Table 1. (1-800T-XA
Contact Block per side.
2 Contact Blocks total.)
d1
Operator Type/Function ➌
Spring Return from Both
Metal Wing Lever Colors
Description
KB7
Knob Lever
Spring Return from Left
Knob Insert Colors ➊
Code
Operator Function
Note: Refer to page 10-125 for additional
key option codes.
Table 1. Selector Switch Cam Targets
Cam Description
KB7
(std.)
Target
W
KA1
KA7
KC1
B
W
B
W
B
W
KE7 ➍
KC7
B
W
B
W
KQ1
KQ7
KR1
B
W
B
W
B
W
KR7
KT1
B
W
B
W
KT7
B
KU7
W
B
W
B
O
O
X
1
1
—
—
1
1
1
1
—
1
—
1
—
1
—
—
—
1
—
—
1
1
1
—
—
1
O
X
O
—
—
1
1
1
1
1
—
1
—
—
—
1
1
1
1
1
—
1
—
—
—
—
—
1
—
O
X
X
—
—
—
—
—
—
—
—
—
—
1
—
—
—
—
—
—
—
—
1
—
—
—
1
—
—
X
O
O
1
1
1
1
—
—
—
1
1
1
1
—
—
—
—
1
—
—
—
1
1
—
1
1
1
—
X
O
X
—
—
—
—
—
—
—
—
—
—
—
—
1
—
1
—
1
—
1
—
—
—
—
—
—
—
X
X
O
—
—
—
—
—
—
—
—
—
—
—
1
—
—
—
—
—
1
—
—
—
1
—
—
—
1
Note: W = White B = Black. X = Closed/O = Open. For additional targets and overlapping cams, see Publication 800T-2.8.
➊ Each standard and knob lever operator is factory assembled with a white insert. Other colors available, factory assembled, if ordered in quantities
of 10 or more.
➋ Packet of colored inserts, one of each color except orange.
➌ For additional keys, see page 10-125.
➍ Wing levers are not suitable with KE7 cam code.
10-127
1
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
4-Position Selector Switch Units, Non-Illuminated
Standard Knob Operator
Cat. No. 800H-NP2KF4AAXX
Knob Lever Operator
Cat. No. 800H-NP17KF4AAXX
Operator Position
Operator Type
M = Maintained
S = Spring Return
Contact
Type
No
Contacts
2 N.O. 2 N.C.
X
O
O
O
—
O
X
O
O
—
O
O
X
O
—
O
O
O
X
Standard Knob
Knob Lever
Metal Wing Lever
Cat. No.
Cat. No.
Cat. No.
M
M
M
800H-NP2KF4
800H-NP17KF4
800H-NP11KF4
S→M
M
M
800H-NP3KF4
800H-NP29KF4
800H-NP13KF4
M
M
M←S
800H-NP9KF4
800H-NP30KF4
800H-NP14KF4
M
M
M
M
800H-NP2KF4AAXX
800H-NP17KF4AAXX
800H-NP11KF4AAXX
S→M
M
M
800H-NP3KF4AAXX
800H-NP29KF4AAXX
800H-NP13KF4AAXX
M
M←S
800H-NP9KF4AAXX
800H-NP30KF4AAXX
800H-NP14KF4AAXX
M
—
Metal Wing Lever Operator
Cat. No. 800H-NP11KF4AAXX
M
Note: X = Closed/O = Open
0
Cylinder Lock Operator
Cat. No. 800H-NP32KF4AAXX
Operator Position
Operator Type
M = Maintained
S = Spring Return
Contact
Type
No
Contacts
2 N.O. 2 N.C.
X
O
O
O
—
O
X
O
O
—
O
O
X
O
—
O
O
O
X
Cat. No.
Cat. No.
Key Removal All ➊
Cat. No.
M
M
M
800H-NP32KF4
800H-NP33KF4
800H-NP61KF4
S→M
M
M
800H-NP132KF4
800H-NP133KF4
800H-NP154KF4
M
M
M←S
800H-NP232KF4
800H-NP233KF4
800H-NP251KF4
M
M
M
M
800H-NP32KF4AAXX
800H-NP33KF4AAXX
800H-NP61KF4AAXX
S→M
M
M
800H-NP132KF4AAXX
800H-NP133KF4AAXX
800H-NP154KF4AAXX
M
M←S
800H-NP232KF4AAXX
800H-NP233KF4AAXX
800H-NP251KF4AAXX
M
—
Cylinder Lock
Key Removal Position 2 Key Removal Position 3
M
Note: X = Closed/O = Open
➊ Key removable in maintained positions only.
Accessories — Page 10-137
Legend Plates — Page 10-142
10-128
Approximate Dimensions — Page 10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
4-Position Selector Switch Units, Non-Illuminated
800 H – NP
a
b
800 H – NP
a
c
2
KF4
d
e
f
KF4
AAXX
e
f
31
b
d1
c1
a
c1 (cont’d)
Key Removal Position and
Operator Function
Barrel Type
Code
Description
H
Standard Barrel Length
HL
Long Barrel
Spring Return From Position 1 to
Position 2
b
Code
Number of Positions
132
Code
Description
NP
4-Position
134
Knob Insert Colors ➊
154
Color
Blank
White
A
Red
B
Green
C
Blue
Yellow
X
Packet of Color Inserts ➋
233
Color
A
Red
Blank
Gray
Maintained
33
34
61
Description
Key Removal
Position 1
Key Removal
Position 2
e
Code
Description
KF4
KG4
F Cam (Standard)
G Cam
KK4
K Cam
KM4
M Cam
KP4
P Cam
KH4
Overlapping Cam
f
Code
Description
Blank
No Contacts
AAXX
2 contact targets for a given cam
as shown in the W (white side)
column of Table 1
and
2 contact targets for the same cam
as shown in the B (black side)
column of Table 1. (1-800T-XA
Contact Block per side. 2 Contact
Blocks total)
Knob Lever
Key Removal
Position 3
Key Removal
Position 4
Key Removal All Positions
Code
Operator Function
17
Maintained
Spring Return from Position 1 to
Position 2
Spring Return from Position 4 to
Position 3
29
30
FFFF
Description
2 contact targets for a given cam
as shown in the W (white side)
column of Table 1
and
2 contact targets for the same cam
as shown in the B (black side)
column of Table 1. (1-800T-XAV
Contact Block per side. 2 Contact
Blocks total)
4 contact targets for a given cam
as shown in the W (white side)
column of Table 1
and
4 contact targets for the same cam
as shown in the B (black side)
column of Table 1. (2-800T-XAV
Contact Blocks per side. 4 Contact
Blocks total.)
Contact Block Option
Maintained
9
FFXX
Cam Option
Spring Return from Position 1 to
Position 2
Spring Return from Position 4 to
Position 3
3
PenTUFF (Low Voltage)
Code
Blank
D018 (Standard Key)
Note: Refer to page 10-125 for additional
key option codes.
Operator Function
2
Operator Function
32
Code
Standard Knob
Code
AAAA
D Series
Operator Function and Knob
Type
Key Removal Position and
Operator Function
31
d1
Optional Keys
d
c1
Code
14
Key Removal
Positions 1,2, and 3
251
Description
4 contact targets for a given cam
as shown in the W (white side)
column of Table 1
and
4 contact targets for the same cam
as shown in the B (black side)
column of Table 1. (2-800T-XA
Contact Blocks per side. 4 Contact
Blocks total.)
Maintained
Spring Return from Position 1 to
Position 2
Spring Return from Position 4 to
Position 3
13
Key Removal
Position 1
Key Removal
Position 2
Key Removal
Position 3
232
Code
Operator Function
11
Operator Function
Metal Wing Lever Colors
Code
Code
Key Removal
Positions 2,3, and 4
231
Orange
f (cont’d)
Contact Block Option
Key Removal
Position 2
Key Removal
Position 3
Key Removal
Position 4
Code
F
d (cont’d)
Operator Function and Knob
Type
Metal Wing Lever
Spring Return From Position 4 to
Position 3
E
(Cylinder Lock)
Operator Function
133
c
Code
AAXX (Knob/Wing Lever)
Table 1. Selector Switch Cam Targets
Cam Description
Target
KF4
KG4
KK4
KM4
KH4 ➌
KP4
Contact Block Side
W
B
W
B
W
B
W
B
W
B
W
B
—
1
—
1
—
—
—
1
1
—
1
—
1
—
—
—
—
—
—
—
—
1
—
—
1
—
—
—
—
1
—
—
—
—
—
—
1
1
—
1
—
—
—
1
1
—
—
—
—
—
1
—
—
1
—
—
1
—
1
—
—
1
—
—
—
—
—
—
1
—
—
—
—
—
—
—
O
O
O
X
O
O
X
O
—
1
O
O
X
X
—
—
O
X
O
O
1
—
—
O
X
X
O
—
—
—
X
O
O
O
1
—
—
X
O
O
X
—
—
—
X
X
O
O
—
—
1
—
Note: W = White B = Black. X = Closed/O = Open. For additional targets and overlapping cams, see Publication 800T-2.8.
➊ Each standard and knob lever operator is factory assembled with a
white insert. Other colors available, factory assembled, if ordered in
quantities of 10 or more.
➋ Packet of colored inserts, one of each color except orange.
➌ Overlapping cam.
10-129
1
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Pilot Light Units
Transformer Type Pilot Light
Cat. No. 800H-PP16R
Lamp
Push-to-Test Pilot Light
Cat. No. 800H-PPT16R
Type
Volts
Color
Red
Green
Amber
Red
Green
Amber
Red
Green
Amber
Red
Green
Amber
Red
Green
Amber
Red
Green
Amber
120 AC
Full Voltage
Incandescent
24 AC/DC
Transformer
120 AC
120 AC
Full Voltage
24 AC/DC
LED
Transformer
120 AC
Pigtail Pilot Light
Cat. No. 800H-LP24R
Pilot Light
Cat. No.
800H-QP10R
800H-QP10G
800H-QP10A
800H-QP24R
800H-QP24G
800H-QP24A
800H-PP16R
800H-PP16G
800H-PP16A
800H-QPH10R
800H-QPH10G
800H-QPH10A
800H-QPH24R
800H-QPH24G
800H-QPH24A
800H-PPH16R
800H-PPH16G
800H-PPH16A
Push-to-Test➊
Cat. No.
800H-QPT10R
800H-QPT10G
800H-QPT10A
800H-QPT24R
800H-QPT24G
800H-QPT24A
800H-PPT16R
800H-PPT16G
800H-PPT16A
800H-QPTH10R
800H-QPTH10G
800H-QPTH10A
800H-QPTH24R
800H-QPTH24G
800H-QPTH24A
800H-PPTH16R
800H-PPTH16G
800H-PPTH16A
Pigtail
Cat. No.
800H-LP10R
800H-LP10G
800H-LP10A
800H-LP24R
800H-LP24G
800H-LP24A
—
—
—
—
—
—
—
—
—
—
—
—
➊ Includes one standard 800T-XA (1 N.O. - 1 N.C.) contact block.
0
Typical Pilot Light Wiring Diagrams
See applicable Codes and Laws.
Push-to-Test Pilot Light Device Schematic
Dual Input Diode Pilot Device Schematic
NORMAL
B2
B1
NORMAL
(3)
R1
TEST
L1
A4
A3
TEST
(1)
R2
D1
L2 (2)
D2
Dual Input Pilot Light
Typical Application Wiring Diagram
TEST
L1
1CR
1LS
L2
Dual Input Pilot Light
Transformer Type Device Schematic
(3)
(2)
(1)
3CR
PS
NORMAL
(3)
(3)
(2)
(1)
TEST
(1)
SOL
2LS
C
(3)
(2)
(1)
Accessories — Page 10-137
Legend Plates — Page 10-142
10-130
L2 (2)
Approximate Dimensions — Page 10-144
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Pilot Light Units
800 H – PP
a
b
T
c
d
16
R
e
f
a
d
e
f
Barrel Type
Transformer
Voltage
Lens Color
Transformer
Code
Description
Code
Description
H
Standard Barrel Length
Blank
Standard Pilot Light
Code
HL
Long Barrel
F
Flashing Lamp ➍
b
H
LED ➎
Full Voltage
Power Module Type
Code
Description
PP
Transformer
(or Dual Input)
QP
Full Voltage
(or Resistor)
RP
Neon ➊
LP
Pigtail — Full Voltage ➋
LPK
Pigtail — Full Voltage ➋
(for Dual Push Buttons)
c
Color
Blank
No Lens
36
48V AC 50/60 Hz
A
Amber
16
120V AC 50/60 Hz
B
Blue
26
240V AC 50/60 Hz
C
Clear
Green
Code
Description
76
277V AC 50/60 Hz
G
Blank
Standard Pilot Light
46
480V AC 50/60 Hz
R
Red
F
Flashing Lamp ➍
56
600V AC 50/60 Hz
W
White
H
Full Voltage
LED ➎
Resistor
Code
Description
Code
Description
06
6V AC/DC
Blank
No Options
12
12V AC/DC
Neon
Code
Blank
Lamp Test Options
Description
No Options ➊
Dual Input
Code
Description
Code
Description
Blank
No Test Option
Blank
No Options
T
Push-to-Test
D
Dual Input — Diode ➌
Code
Description
DT
Dual Input —
Transformer Relay ➌
Blank
Standard Pilot Light
F
Flashing Lamp ➍
H
LED ➎
Note: Push-to-Test Pilot Light is supplied
with a factory jumpered 800T-XA,
1 N.O - 1 N.C Contact Block.
Code
Description
24
24V AC/DC
32
32V AC/DC ➏
48
48V AC/DC
13
130V AC/DC ➏
10
120V AC/DC ➐
20
240V AC/DC ➏
Resistor
Pigtail
Code
Description
11
120V AC/DC Resistor
1
Neon
Code
Description
10
120V AC/DC
20
240V AC/DC
Dual Input
Code
Description
16
120V AC
24
24V AC/DC ➑
Pigtail
Code
Description
06
6V AC/DC
12
12V AC/DC
24
24V AC/DC
10
120V AC/DC
20
240V AC/DC
➊
➋
➌
➍
➎
Neon is only available in amber or clear.
Lamp test options not available with pigtail.
Only available with power module type code PP.
Flashing lamps are only available in 6V full voltage units and all transformer units.
LEDs available in red, green, amber, blue, and white. White LEDs only available in 6V and 24V full voltage and all transformer units. LED color
must match lens color, except clear lens supplied with white LED and white lens supplied with amber LED. All LEDs except 120V have an internal
shunt resistor for use with solid-state outputs.
➏ 32V and 130V are LED only. 240V is incandescent only.
➐ 120V LED is AC only and does not contain internal shunt resistor. For AC/DC and internal shunt resistor, order 130V AC/DC LED (Code 13).
➑ Dual input diode only.
10-131
Bulletin 800H
Hazardous Location Push Buttons
10n/
Type 7 & 9, for Divisions 1 & 2
Description
Application
When properly mounted in a Type 7 & 9
enclosure, Bulletin 800H Type 7 & 9
operators are designed to meet the
requirements of the National Electrical
Code for Class I, Divisions 1 & 2, Groups
B, C & D Hazardous Gas; Class II,
Divisions 1 & 2, Groups E, F and G
Hazardous Dust; and, Class III Hazardous
Fiber Locations. In addition, the single
gang shallow base, Cat. No. 800H-IHZX7,
meets Class I, Group B requirements.
This Type 7 & 9 equipment is listed by
Underwriters Laboratories, Inc.
Per National Electrical Code:
Zone 1. In Class I, Zone 1 locations, all
wiring methods permitted for Class I,
Division 1 locations and Class I, Zone 0
or Zone 1 locations, including
requirements for sealing, shall be
permitted.
Zone 2. In Class I, Zone 2 locations, all
wiring methods permitted for Class I,
Division 2, Class I, Division 1 or Division 2,
and Class I, Zone 0 or Zone 1 locations,
including requirements for sealing, shall
be permitted.
0
Operator Construction
The Allen-Bradley line of hazardous
location devices feature copper free (less
than 0.4 of 1% copper content) die cast
aluminum bushings and mounting rings,
Type #316 stainless steel operating shafts
and an O-ring seal for added corrosion
resistance. These components mount into
a threaded hole (3/4"-14 NPSM) in a
suitable enclosure.
Type 3 Flange Seal
10-132
Bulletin 800H Type 7 & 9 components are
available in two basic formats: standard
barrel (Bulletin 800H) and long barrel
(Bulletin 800HL). Standard barrel devices
are suitable for mounting in panel
thickness up to 1"; Long barrel devices are
suitable for mounting in panel thickness
greater than 1" and no thicker than 2-1/2".
Both style operators offer a unique locking
bracket which provides an anti-turn
feature to guard against loosening. The
mounting rings in front of the panel are
knurled to provide a second means of
tightening each unit into the panel.
Outdoor Use
Bulletin 800H Type 7 & 9 stations and
enclosures are not configured for outdoor
use as standard. A Type 3 rating is
available, while maintaining Type 7 & 9
integrity of the enclosure, by the addition
of a Type 3 sealing flange and an
approved drain. The sealing flange shown
below may be purchased as an option
(see page 10-115) or as an accessory
(see page 10-141). A Type 4 rating can be
achieved by using sealing nuts to seal the
push button operators in addition to using
the sealing flange. Sealing nuts are
available as accessories (see page
10-141.)
Sealing Wells
Elimination of Conduit Seal Off
Requirement
Bulletin 800H Type 7 & 9 units may be
installed with a variety of sealing options.
By utilizing either a sealing well or flanged
sealing well, these stations may be
installed without a conduit seal off in most
applications (subject to applicable codes
and laws). The sealing wells shown below
may be purchased as an option (see
page 10-115) or as an accessory (see
page 10-141). Sealing wells are also
available with an integral Type 3 flange
seal for outdoor applications.
Sealed switch contact blocks are another
way to eliminate the need for conduit seal
fittings in most applications (subject to
applicable codes and laws). Sealed switch
contact blocks may be purchased as an
option on assembled stations by changing
the Bulletin No. from 800H to 800R.
Sealed switch contact blocks can be
ordered as an accessory (see
page 10-141). A push button station with
a sealed switch contact block is shown
below.
Sealed Switch Contact Blocks
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Ordering Information for Stations
Stations
Bulletin 800H Type 7 & 9 stations are
available as factory assembled or as
components for field assembly.
Factory Assembled Stations
Bulletin 800H Type 7 & 9 control stations
are designed to meet the requirements of
the National Electrical Code. These
stations are listed by Underwriters
Laboratories, Inc. for Class I,
Divisions 1 & 2, Groups C & D Hazardous
Gases or Vapors, Class II, Divisions 1 & 2,
Groups E, F & G Hazardous Dust and
Class III Hazardous Fiber Locations. In
addition the single gang shallow base,
Cat. No. 800H-IHZX7, meets Class I,
Group B requirements as defined in the
National Electrical Code.
Factory assembled stations may be
ordered in three ways:
• Standard, factory assembled stations
listed on page 10-114.
• Modified Standard, factory
assembled stations can be selected
from the configurator on page 10-115.
• Custom, factory assembled stations
can be ordered by following the
instructions listed on this page.
1. Push-to-test pilot lights, illuminated
push buttons, push-pull units,
4-position selector switches, all
operators with two contact blocks
fastened along side one another or
with a power module and contact
block along side one another must
be installed in a single hole cover.
2. Dual push button units may only be
installed in a single hole cover or the
specially designed two hole cover
(Cat. No. 800H-NP33), which can
accommodate the dual push button
and the special pigtail pilot light (Cat.
No. 800H-LPK10R).
Components for Field Assembled
Stations
Eight-gang maximum ➊. These 2- and
3-gang modules may be assembled into
the multi-gang stations by installing a
coupler kit between the enclosures.
These separate bases, covers, or bases
with covers are Underwriters
Laboratories, Inc. listed when properly
assembled. These enclosures meet the
requirements of Class I, Division 1 & 2,
Groups C & D, Class II, Divisions 1 & 2,
Groups E, F & G, and Class III hazardous
locations as defined in the National
Electrical Code. Bulletin 800H Type 7 & 9
components are designed for these
modular enclosures and are Underwriters
Laboratories, Inc. listed for this purpose.
Note: Components may be assembled as
multi-gang units up to an eight-gang
maximum ➊.
To select components for field assembly,
follow the instructions for ordering a
custom built station.
Also, in Step 3 you may choose to select
the base as components to provide
additional design flexibility, see
page 10-115.
Instructions for Ordering Custom
Built Stations
1. Select operators required from
pages 10-116 through 10-131. (If
lever type, select covers from
page 10-134 and go to Step 3).
2. Select covers based on mounting
requirements from page 10-134.
3. Select an assembled base from
pages 10-135 through 10-136 in
accordance with the number of covers
selected in Step 2.
4. Select legend plates from
pages 10-142 through 10-143 (and
accessories, if required, from
pages 10-137 through 10-141).
5. If a particular sequence of operators
or mounting orientation (vertical
versus horizontal) is required, include
a rough sketch.
1
Station Design Guidelines
(Also see Applicable Codes and Standards)
3. When two components are installed
in one cover, contact blocks are
restricted to one side of the operator.
Contact blocks of each operator
must face each other.
4. One level of contact blocks is
maximum in a shallow base or deep
base when used with a sealing well.
Contact blocks, except sealed switch
type, may be mounted two deep in
other bases.
5. If sealed switch contact blocks or a
sealing well are used, a deep
enclosure is required.
6. a. START push buttons should be
green or black flush, installed to the
left or above STOP push buttons.
b. EMERGENCY STOP push
buttons should be a red mushroom.
c. STOP push buttons should be red
extended, installed to the right or
below START push button.
d. STOP push buttons should be
installed in the last position (bottom
or right) of each unit when required.
e. Pilot lights should be installed in
the first position (top or left side) of
each unit when required.
➊ Flange width is designed to comply with Underwriters Laboratories standards to enclosures with an internal free volume of up to 300 cubic inches
(a maximum 8-gang assembly).
10-133
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Covers, Lever Type Actuator
Note:Lever type covers are furnished without contact blocks. Legend plate for half lever is STOP; full lever momentary and maintained
it is a START-STOP.
START
STOP
STOP
Half Lever
Half Lever
Cat. No.
800H-NP14
Double Lever Momentary
Double Lever Momentary
Cat. No.
800H-NP15
Double Lever Maintained
Cat. No.
800H-NP16
Double Lever Momentary/Maintained ➊
Cat. No.
800H-NP34
Covers, Component Type Button
0
Blank
Cat. No.
800H-NP32
Design Guideline #4
One level of contact blocks is
maximum in a shallow base
or deep base when used with
a sealing well. Contact
blocks, except sealed switch
type, may be mounted two
deep in other bases.
One Hole ➋
Cat. No.
800H-NP30
Design Guideline #1
Push-to-test pilot lights,
illuminated push buttons,
push-pull units, 4-position
selector switches, all
operators with two contact
blocks fastened along side
one another or with a power
module and contact block
along side one another must
be installed in a single hole
cover.
➊ A normally open circuit configuration is recommended for use behind
this momentary lever and a late break normally closed circuit
configuration is required for use behind the maintained lever to
achieve proper functioning of the device.
➋ One hole covers use a jumbo legend plate only.
➌ Two hole covers use a standard legend plate only.
10-134
Two Hole ➌
Cat. No.
800H-NP31
Design Guideline #3
When two components are
installed in one cover, contact
blocks are restricted to one
side of the operator. Contact
blocks of each operator must
face each other.
Two Hole Special ➍
Cat. No.
800H-NP33
Design Guideline #2
Dual push button units may
only be installed in a single
hole cover or the specially
designed two hole cover (Cat.
No. 800H-NP33), which can
accommodate the dual Push
Button and the special pigtail
pilot light (Cat.
No. 800H-LPK10R).
➍ This special two hole cover can accommodate the pigtail pilot light
(Bulletin 800H-LPK10 series), the dual push button or any
non-illuminated unit. Legend plates (Cat. No. 800H-Y140J green and
red split-field) and (Cat. No. 800H-Y141J gray full field), are the only
legend plates suitable for use with this cover.
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Assembled Bases (for Field Assembly and Custom Stations)
Enclosure Covers — See table on page 10-134 for a complete listing of covers for these bases.
Special Conduit Entries — For conduit entries not listed, consult your local Allen-Bradley Sales Office.
1-Gang Shallow ➊
Conduit Entry
3/4" Dead End
3/4" Feed Through
1" Dead End
1" Feed Through
1-Gang Deep ➋
Cat. No.
800H-1HZX7
—
—
—
2-Gang Horizontal ➋
Cat. No.
800H-1HVX7
800H-1HVX7M1
800H-1HVX7M2
800H-1HVX7M3
Cat. No.
—
—
800H-2HHX7
—
1
2-Gang Vertical ➋
Conduit Entry
1" Feed Through
3-Gang Vertical ➋
Cat. No.
800H-2HYX7
6-Gang ➋
Conduit Entry
1" Feed Through
4-Gang ➋
Cat. No.
800H-3HYX7
Cat. No.
800H-4HVX7
8-Gang ➋
Cat. No.
800H-6HVX7
Cat. No.
800H-8HVX7
➊ Shallow base cannot accommodate sealing well, sealed switched contact blocks or stacked contact blocks. Shallow base rated for Group B.
➋ Deep base can accommodate sealing well, sealed switch contact blocks or up to 2 deep standard contact blocks.
10-135
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Bases for Multi-Gang Stations
➊
➊
➊
➊
Conduit Sizes
3/4" Feed Through
1" Feed Through
Cat. No.
800H-NP40C
800H-NP40D
Cat. No.
800H-NP41C
800H-NP41D
Cat. No.
800H-NP42A
800H-NP42B
➊
➊
➊
➊
Conduit Sizes
3/4" Feed Through
1" Feed Through
0
➊
➊
➊
Cat. No.
800H-NP43A
800H-NP43B
➊
Cat. No.
800H-NP44A
800H-NP44B
➊
Cat. No.
800H-NP45
—
Cat. No.
800H-NP46A
800H-NP46B
Example:
7-Gang Base with 1-inch through-feed conduit consists of:
3-Cat. No. 800H-NP42B
1-Cat. No. 800H-NP43B
1-Cat. No. 800H-NP44B
1-Cat. No. 800H-NP45
1-Cat. No. 800H-NP46B
6-Cat. No. 800H-NP7
Plus up to 4-1" plugs (Cat. No. 800H-NP11) to close unused conduit openings.
Caution: Do not assemble more than 8 enclosure gangs together, to avoid exceeding the internal volume for which the flame path
of these enclosures is designed.
➋
➋
➋
800H-NP43B
800H-NP44B
800H-NP46B
800H-NP45
800H-NP42B
800H-NP42B
➋
➋
800H-NP42B
➋
➊ When coupling modular enclosures together, a coupler kit (Cat. No. 800H-NP7) is required between enclosures.
➋ 1" conduit through-feed (all gangs).
10-136
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Modifications and Accessories
Contact Blocks
Packaged in kit form for field installation. All necessary mounting hardware is provided with each contact block kit. Contact ratings
are listed on page 10-113. Note: It is not recommended to mount more than four contact blocks on any one unit (maximum two
blocks deep). Sealed switch contact blocks are limited to two blocks per unit maximum.
Shallow Block
Mini Block
PenTUFF (Low Voltage)
Contact Block
Shallow Block ➊➋➌
Mini Block ➊➌
Cat. No.
Cat. No.
Cat. No.
1 N.O.
800T-XD1
800T-XD5
800T-XD1V
Number of Contacts
PenTUFF (Low Voltage) Block ➊➋➌
1 N.C.
800T-XD2
800T-XD6
800T-XD2V
1 N.O.E.M.
800T-XD3
—
800T-XD3V
1 N.C.L.B.
800T-XD4
—
800T-XD4V
1 N.O. - 1 N.C.
800T-XA
—
800T-XAV
2 N.O.
800T-XA2
—
—
2 N.C.
800T-XA4
—
—
1 N.C.L.B. - 1 N.O.
800T-XA1
—
—
1 N.C.L.B. - 1 N.C.
800T-XA7
—
—
1
Logic Reed Block
Sealed Switch Block
Stackable Sealed Switch Block
Logic Reed Block ➊
Sealed Switch Block ➊
Cat. No.
Cat. No.
Cat. No.
1 N.O.
800T-XD1R
800T-XD1P
800T-XD1Y
800T-XD2Y
Number of Contacts
Stackable Sealed Switch Block ➊
1 N.C.
800T-XD2R
800T-XD2P
1 N.O. - 1 N.C.
800T-XAR
800T-XAP
800T-XAY
2 N.O.
800T-XA2R
—
800T-XA2Y
2 N.C.
800T-XA4R
—
800T-XA4Y
➊ To determine if a conduit seal-off is necessary, see page 10-141 for sealing well information.
➋ Specify Bulletin 800TC for finger-safe contact blocks. Example: 800TC-XA.
➌
Contact blocks with normally closed contacts meet direct drive positive opening standard requirements.
10-137
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Modifications and Accessories, Continued
Replacement Color Caps (Illuminated)
Pilot Light
Cat. No. 800H-N104R
Color
Red
Green
Amber
Blue
White
Clear
Push-to-Test Pilot Light
Cat. No. 800H-N105R
Pilot Light
Cat. No.
800H-N104R
800H-N104G
800H-N104A
800H-N104B
800H-N104W
800H-N104C
Illuminated Push Button
Cat. No. 800H-N106R
Push-to-Test Pilot Light
Cat. No.
800H-N105R
800H-N105G
800H-N105A
800H-N105B
800H-N105W
800H-N105C
Illuminated Push-Pull
Cat. No. 800H-NP50A
Illuminated Push Button
Cat. No.
800H-N106R
800H-N106G
800H-N106A
800H-N106B
800H-N106W
800H-N106C
Illuminated Push-Pull
Cat. No.
800H-NP50R
800H-NP50G
800H-NP50A
800H-NP50B
800H-NP50W
800H-NP50C
Replacement Color Caps (Non-Illuminated)
Momentary Mushroom —
Standard (Plastic)
Cat. No. 800T-N246R
0
Color
Red
Green
Blue
Yellow
Black
Gray
Natural
Momentary Mushroom —
Jumbo (Metal)
Cat. No. 800T-N248R
Momentary Mushroom —
Standard (Plastic)
Cat. No.
800T-N246R
800T-N246G
800T-N246BL
800T-N246Y
800T-N246B
800T-N246GR
—
Push-Pull — Standard (Metal)
Cat. No. 800H-NP51C
Momentary Mushroom —
Jumbo (Metal) ➊
Cat. No.
800T-N248R
800T-N248G
800T-N248BL
800T-N248Y
800T-N248B
800T-N248GR
800T-N248
Push-Pull —
Standard (Metal)
Cat. No.
800H-NP51A
800H-NP51B
800H-NP51C
800H-NP51E
800H-NP51H
800H-NP51G
—
Push-Pull — Jumbo (Metal)
Cat. No. 800H-NP52A
Push-Pull —
Jumbo (Metal)
Cat. No.
800H-NP52A
800H-NP52B
800H-NP52C
800H-NP52E
800H-NP52H
—
—
Replacement Knobs and Dual Push Button Assembly
Standard Knob
Cat. No. 800H-N130F
Color
White
Kit (Complete) ➌
Gray
Red
Green/Red
Knob Lever
Cat. No. 800H-131F
Standard Knob
Cat. No.
800H-N130F
800H-N130
—
—
—
Wing Lever
Cat. No. 800H-N138
Knob Lever
Cat. No.
800H-N131F
800H-N131
—
—
—
➊ To order Plastic Jumbo Color Caps, contact your local Allen-Bradley
Sales Office.
➋ Standard finish is gray.
10-138
Wing Lever ➋
Cat. No.
—
—
800H-N138
800H-N138A
—
Dual Push Button
Cat. No. 800H-NP39
Dual Push Button
Cat. No.
—
—
—
—
800H-NP39
➌ Kit includes knob and packet of inserts (Cat. No. 800T-N123). Refer
to color insert kits on page 10-141.
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Modifications and Accessories, Continued
Boots and Booted Knobs
Flush Push Button Boot
Cat. No. 800H-NP5B
Material
Color
Red
Green
Black
Yellow
Blue
Red
Green
Black
Yellow
Blue
Red
Green
Black
Yellow
Blue
Red
Green
Black
Yellow
Blue
Hypalon
Silicone
●
Urethane
●●
Ethylene
Propylene
●
●●
Extended Push Button
Cat. No. 800H-NPE5A
Flush
Push Button Boot
Cat. No.
➊
800H-NP5B
800H-NP5H
800H-NP5E
800H-NP5C
➊
800H-NP101G
800H-NP101B
800H-NP101Y
800H-NP101BL
➊
800H-NP100G
800H-NP100B
800H-NP100Y
800H-NP100BL
➊
800H-NP103G
800H-NP103B
—
—
Booted Standard Knob
Booted Knob Lever
Selector Switch
Selector Switch
Cat. No. 800H-NP5
Cat. No. 800H-NPE5
Extended
Booted Standard Knob
Booted Knob Lever
Push Button Boot
Selector Switch ➋
Selector Switch ➋
Cat. No.
Cat. No.
Cat. No.
800H-NPE5A
—
—
800H-NPE5B
—
—
800H-NPE5H
800H-NP5
800H-NPE5
800H-NPE5E
—
—
800H-NPE5C
—
—
800H-NPE101R
—
—
800H-NPE101G
—
—
800H-NPE101B
800H-NP101
800H-NPE101
800H-NPE101Y
—
—
800H-NPE101BL
—
—
800H-NPE100R
—
—
800H-NPE100G
—
—
800H-NPE100B
800H-NP100
800H-NPE100
800H-NPE100Y
—
—
800H-NPE100BL
—
—
800H-NPE103R
—
—
800H-NPE103G
—
—
800H-NPE103B
800H-NP103
800H-NPE103
—
—
—
—
—
—
➊ Red flush head push buttons are not suitable for applications requiring extended head, mushroom head or other unguarded buttons capable of
being operated quickly in emergencies, and they may not comply with applicable codes or standards. To order a protective boot for a red flush
head push button, use the following cat. nos.: Hypalon — Cat. No. 800H-NP5A; Silicone — Cat. No. 800H-NP101R; Urethane — Cat.
No. 800H-NP100R; Ethylene Propylene — Cat. No. 800H-NP103R.
➋ Includes color insert kit.
Push Button Guards and Mushroom Push Button Guards
Cat. No.
800H-NP19
Cat. No.
800H-NP13
Push Buttons, Pilot Lights and
Push-to-Test
Cat. No.
800H-NP19
Extra Long Guard (1") for
Push Button
Cat. No.
800H-NP13
Cat. No.
800H-NP9
Cat. No.
800H-NP12
Jumbo
Mushroom
Cat. No.
800H-NP12
Mushroom
Cat. No.
800H-NP9
Protective Rings
Protective Ring for 2-Position Push-Pull
Cat. No. 800H-NP40
Jumbo Protective Ring for 2-Position Push-Pull
Cat. No. 800H-NP40J
Protective Ring for Illuminated Push Buttons
Description
Type
Protective ring for 800H 2-position push-pull operators. Illuminated or non-illuminated.
For standard size button
Often used to avoid unintentional tripping of E-stop operators. Available for standard size
For jumbo size button
button (40 mm) or for jumbo button (60 mm).
Cat. No.
800H-NP40
800H-NP40J
10-139
1
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
General Accessories
Plugs
Description
Cat. No.
Coupler
Used for both horizontal and vertical assembly.
800H-NP7
Coupler
Cat. No. 800H-NP7
Description
Type
Cat. No.
Cover Hole
800H-NP1
Base Coupling
800H-NP3
Size
Cat. No.
3/4"
800H-NP10
1"
800H-NP11
Closing Plug
Whenever an enclosure with more than the required number of
cover openings is used, this plug can be used to close the
unused openings. Includes synthetic O-ring washer.
Closing Plug
Cat. No. 800H-NP1
(Operators not included)
Description
Conduit Entry Plug
This plug can be used to plug unused conduit openings in
Type 7 & 9 bases.
0
Conduit Entry Plug
Cat. No. 800H-NP10
(Operators not included)
Locking Attachments
Description
Cat. No.
Push Button Padlocking Attachments
This device permits locking in the depressed position on
Extended head push button units only.
800H-NP2
Dual Push Button Extended Head Padlocking
Attachments
This device permits locking for dual push button — extended
head units only.
800H-NP17
Push Button Padlocking Attachment
Cat. No. 800H-NP2
(Padlock not included)
Dual Push Button Extended Head
Padlocking Attachment
Cat. No. 800T-N10
(Padlock not included)
10-140
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
General Accessories, Continued
Locking Attachments, Continued
Padlocking Cover
Cat. No. 800H-NP4
(Padlock not included)
Description
Cat. No.
Padlocking Cover
Padlocking cover is used for Type 7 & 9 selector switches,
non-illuminated push buttons (except mushrooms) and non-illuminated
2-position push-pull units, but not for potentiometer units.
Note: Push-pull units will only lock in the depressed position. Padlocking
cover includes blank legend plate for customer marking. A pre-marked
legend plate entitled OPEN COVER TO OPERATE (Front View) and
PULL-TO-START-PUSH-TO-STOP (Rear View) is available. To order
legend plate only, specify Cat. No. 800H-W174L.
800H-NP4
Miscellaneous
Description
Sealing Well with
Flange Seal
Cat. No. 800H-NPRD91
Sealing Well without
Flange Seal
Cat. No. 800H-NPD93
Sealing Well with or without Integral
Type 3 Flange Seal
These sealing wells should only be
used with bases having 1" conduit
entries. They reduce costs usually
necessary with other conduit seal fittings
for most installations (subject to applicable
codes and laws) while maintaining Type 7
& 9 integrity. When using a sealing well
with integral flange seal for Type 3 outdoor
applications, an approved drain fitting must
be provided. (Refer to National Electrical
Code.)
Description
Flange Seal
Cat. No. 800H-NP20
With Integral
Flange Seal,
Type 3, 7 & 9
Without Integral
Flange Seal,
Type 7 & 9
Description
Color Insert Kit
These color insert kits are used with
illuminated push buttons, pilot lights,
push-pull, and push-to-test push buttons
(order quantity of 1 to receive kit of
5 inserts).
No. of
Wires
Cat. No.
2
800H-NPRD90
4
800H-NPRD91
6
800H-NPRD92
8
800H-NPRD93
2
800H-NPD90
4
800H-NPD91
6
800H-NPD92
8
800H-NPD93
Style
Cat. No.
Flange Seal
800H-NP20
Type 3 Flange Seal
This seal provides a Type 3 rating while
Drain for 3/4"
maintaining Type 7 & 9 integrity. They are
Conduit Opening
used with the Allen-Bradley enclosures
listed on page 10-132 for outdoor
applications. An approved drain (see
Drain for 1" Conduit
listing) is required for condensation when
Opening
using this option (refer to National
Electrical Code). For a Type 4 rating, use
sealing nuts to seal the push button
Type 4
operators in addition to using the flange
Sealing
Nut
seal. Sealing kit is comprised of flange seal
and sealing nut.
Drain Plug
Cat. No. 800H-NP21
Color Insert Kit
Cat. No. 800H-NP23R
Style
800H-NP21
800H-NP22
800H-N479
Type 4
Sealing Kit
800H-N479F
Color
Cat. No.
Red
800H-NP23R
Green
800H-NP23G
Amber
800H-NP23A
Blue
800H-NP23B
White
800H-NP23W
One of each color
800H-NP23
10-141
1
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Legend Plates
Blank Legend Plates
Lever Style
Use 1 lever style legend
with each lever
Color
type cover
(Cat. Nos. 800H-NP14,
-NP15, -NP16 or -NP34)
Cat. No.
Gray
—
Red
—
Green
—
Top Gray — Bottom Gray
800H-Y222
Top Gray — Bottom Red
800H-Y223
Left Green — Right Red
—
Gray with Potentiometer
—
Graduations
Standard Size
Jumbo Size
Use 2 standard size
legends with each
standard 2 hole cover
(Cat. No. 800H-NP31)
Use 1 jumbo size
legend with each
standard 1 hole cover
(Cat. No. 800H-NP30)
Cat. No.
800H-Y59
800H-Y121
800H-Y136
—
—
—
Cat. No.
800H-Y59J
800H-Y121J
800H-Y136J
—
—
—
Special Jumbo Size
Use 1 special jumbo legend with
each special 2 hole cover
(Cat. No. 800H-NP33)
Ex: Dual Push Button/
Pigtail Pilot Light
Cat. No.
800H-Y141J
—
—
—
—
800H-Y140J
800H-Y109
800H-Y109J
—
Custom Legend Plates
Lever Style
Use 1 lever style legend
with each lever
type cover
(Cat. Nos. 800H-NP14,
-NP15, -NP16 or -NP34)
Color
0
Standard Size
Jumbo Size
Special Jumbo Size
Use 2 standard size
Use 1 jumbo size
Use 1 special jumbo legend with
legends with each
legend with each
each special 2 hole cover
standard 2 hole cover
standard 1 hole cover
(Cat. No. 800H-NP33)
(Cat. No. 800H-NP31)
(Cat. No. 800H-NP30)
Ex: Dual Push Button/
2 lines of 15 characters 5 lines of 15 characters
Pigtail Pilot Light
maximum per line.
maximum per line
Cat. No.
Cat. No.
Cat. No.
800H-Y59E ➊
800H-Y59JE ➊
800H-Y141JE ➊
800H-Y121E ➊
800H-Y121JE ➊
—
800H-Y136E ➊
800H-Y136JE ➊
—
—
—
—
—
—
—
—
—
800H-Y140JE ➊
Cat. No.
Gray
—
—
Red
Green
—
Top Gray — Bottom Gray
800H-Y222E ➊
Top Gray — Bottom Red
800H-Y223E ➊
Left Green — Right Red
—
Gray with Potentiometer
—
800H-Y109E ➊
800H-Y109JE ➊
—
Graduations
➊ Horizontally mounted engraved legend plates (with standard or custom marking) are available. Add the letter H after the Y in the cat. no. Example:
Cat. No. 800H-Y222E would become 800H-YH222E.
Lever Style Legend Plates with Standard Markings
START
STOP
Marking
Upper
HAND
Lower
AUTO
JOG
RUN
JOG
ON
10-142
Cat. No.
Marking
Cat. No.
800H-Y228
Upper
OPEN
Lower
CLOSE
800H-Y205
800H-Y227
RUN
STOP (Red)
800H-Y226
STOP (Red)
800H-Y206
START
STOP (Red)
800H-Y200
OFF
800H-Y225
—
—
—
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Legend Plates, Continued
Legend Plates with Standard Markings
Standard Size
Jumbo Size
Cat. No.
Cat. No.
AUTO-OFF-HAND
800H-Y1
800H-Y1J
AUTO-MAN-HAND
800H-Y125
CLOSE
800H-Y2
CYCLE START
Marking
Marking
Standard Size
Jumbo Size
Cat. No.
Cat. No.
ON
800H-Y30
800H-Y30J
800H-Y125J
OPEN
800H-Y31
800H-Y31J
800H-Y2J
OPEN-CLOSE
800H-Y32
800H-Y32J
800H-Y62
800H-Y62J
OPEN-OFF-CLOSE
800H-Y33
800H-Y33J
DOWN
800H-Y3
800H-Y3J
OUT
800H-Y34
—
EMERGENCY STOP (Red)
800H-Y4
800H-Y4J
FAST
800H-Y5
800H-Y5J
PUSH TO STOPPULL TO START
800H-Y118
800H-Y118J
FEED START
800H-Y66
800H-Y66J
POWER ON
800H-Y139
800H-Y139J
FEED STOP
800H-Y67
800H-Y67J
RAISE
800H-Y35
800H-Y35J
FOR.-REV.
800H-Y6
800H-Y6J
RAISE-LOWER
800H-Y36
800H-Y36J
FOR.-OFF-REV.
800H-Y7
800H-Y7J
RAISE-OFF-LOWER
800H-Y37
800H-Y37J
FORWARD
800H-Y8
800H-Y8J
RESET
800H-Y38
800H-Y38J
FOURTH SPEED
800H-Y124
800H-Y124J
REVERSE
800H-Y39
800H-Y39J
FULL SPEED
800H-Y9
800H-Y9J
RUN
800H-Y40
800H-Y40J
HAND-AUTO
800H-Y10
800H-Y10J
RUN-INCH
800H-Y134
800H-Y134J
HAND-OFF-AUTO
800H-Y11
800H-Y11J
RUN-JOG
800H-Y41
800H-Y41J
HIGH
800H-Y12
800H-Y12J
SAFE-RUN
800H-Y42
800H-Y42J
HIGH-LOW
800H-Y13
800H-Y13J
SECOND SPEED
800H-Y43
800H-Y43J
HIGH-OFF-LOW
800H-Y14
800H-Y14J
SLOW
800H-Y44
800H-Y44J
IN
800H-Y15
800H-Y15J
SLOW-FAST
800H-Y45
800H-Y45J
INCH
800H-Y16
800H-Y16J
SLOW-OFF-FAST
800H-Y46
800H-Y46J
JOG
800H-Y17
800H-Y17J
SPEED ➊
800H-Y108
800H-Y108J
JOG FORWARD
800H-Y18
800H-Y18J
START (Green)
800H-Y47
800H-Y47J
JOG REVERSE
800H-Y19
800H-Y19J
START-JOG
800H-Y48
800H-Y48J
JOG-RUN
800H-Y20
800H-Y20J
START-STOP
800H-Y49
800H-Y49J
JOG-SAFE-RUN
800H-Y22
800H-Y22J
STOP (Red)
800H-Y50
800H-Y50J
JOG-STOP-RUN
800H-Y21
800H-Y21J
STOP-START
800H-Y51
800H-Y51J
LEFT-RIGHT
800H-Y23
800H-Y23J
SUMMER-OFF-WINTER
800H-Y53
800H-Y53J
LOW
800H-Y24
800H-Y24J
SUMMER-WINTER
800H-Y52
800H-Y52J
LOW SPEED
800H-Y25
—
TEST
800H-Y54
800H-Y54J
LOWER
800H-Y26
800H-Y26J
THIRD SPEED
800H-Y55
—
OFF
800H-Y27
800H-Y27J
UP
800H-Y56
800H-Y56J
OFF-COOLANT-ON
800H-Y28
800H-Y28J
UP-DOWN
800H-Y57
800H-Y57J
OFF-ON
800H-Y29
800H-Y29J
UP-OFF-DOWN
800H-Y58
800H-Y58J
➊ Graduated potentiometer type.
10-143
1
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Approximate Dimensions and Shipping Weights
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Jumbo Legend Plate
(used with one hole cover)
2 1/16
(52.4) ➊
1 1/16 Dia.
(27.4)
Standard Legend Plate
(used with two hole cover)
2 1/16
(52.4) ➊
4 31/64
(114)
1 1/16 Dia.
(27.4)
4 1/2
(114.3)
2 1/4
(57.1)
2 1/4
(57.1)
2 1/16
(52.4)
2 1/16
(52.4)
Note: Mounting hole requirements for components — 3/4" - 14 NPSM.
➊ Sketch illustrates the minimum distance between center lines when mounting Bulletin 800H units with legend plates either side by side or one
above the other in non Allen-Bradley enclosures. Minimum spacing without legend plate: When units are mounted so that the contact block
terminals face each other, the 2-1/4" (57.2 mm) dimension must be used in order to get proper electrical clearance. When control units are
mounted so that the contact block terminals do not face each other, the 1-27/32" (46.8 mm) dimension can be used.
0
Panel Thickness Requirements
Long Barrel
[devices will fit panels up to 2-1/2" (63.5 mm)]
Standard Barrel
[devices will fit panels up to 1.0" (25.4 mm)]
1 Maximum
(25.4)
3 3/16
(81) ➌
5
(127) ➌
➋ When mounting in a panel thicker than 2-1/8" (54 mm) locking bracket
not required.
2 1/2 Maximum
(63.5) ➋
➌ This dimension for push buttons only.
Push Buttons
Dual Head
1 21/64
(34)
1 5/16
(33.3)
1 1/16
(27)
Dim.
1 31/32
(50)
1 31/32
(50)
1 13/16
(46)
A
B
C
10-144
1 5/16
(33.3)
Standard Barrel
Long Barrel
A
B
C
3-5/16
(84.1)
4-19/32
(116.7)
4-3/16
(106.4)
5-15/32
(138.9)
4-7/16
(112.7)
5-23/32
(145.2)
Ship. Wt.
Oz. (kg)
10-3/8
(0.30)
13
(0.37)
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Approximate Dimensions and Shipping Weights, Continued
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Push Buttons, Continued
Mushroom Head
1 21/64
(34)
2 7/16
(36.5)
1 31/32
(50)
2 1/4 Dia.
(57)
1 13/16
(46)
1 5/8 (41)
DIA.
A
B
C
Extended Head
Push Button with Extra Long Guard
Flush Head
29/
32
1 3/16
(30)
31/
32
(24.5)
(23)
1 3/8 Dia.
(35)
1 3/8 Dia.
(35)
1 3/8 Dia.
(35)
Standard Barrel
Type
Mushroom, Flush and Extended Head
Extra Long Guard
Long Barrel
A➊
B
C
3-3/16 (81)
3-3/16 (81)
4-1/8 (105)
4-1/8 (105)
4-3/8 (111)
4-3/8 (111)
Ship. Wt.
Oz. (kg)
9-7/8 (0.28)
10-7/8 (0.31)
A➋
B
C
5 (127)
5 (127)
5-7/8 (149.2)
5-7/8 (149.2)
6-1/8 (155.6)
6-1/8 (155.6)
Ship. Wt.
Oz. (kg)
13-5/16 (0.38)
14-5/16 (0.40)
Selector Switches
1
Standard Operator
1 21/64
(34)
1 3/32
(28)
1 3/8 Dia.
(35)
1 31/32
(50)
1 13/16
(46)
A
B
C
Knob Lever Operator
Wing Lever Operator
Cylinder Lock Operator
1 3/16
(30)
1 3/32
(28)
1 5/32
(29.5)
2 13/16
(71.5)
1 3/8 Dia.
(35)
1 3/8
(35)
2
(51)
1 1/4
(32)
Standard Barrel
Type
Standard and Knob Lever
Wing Lever
Cylinder Lock
2 1/4
(57)
A➊
B
C
3-3/16 (81)
3-3/16 (81)
3-3/16 (81)
4-1/8 (105)
4-1/8 (105)
4-1/8 (105)
4-3/8 (111)
4-3/8 (111)
4-3/8 (111)
Long Barrel
Ship. Wt.
Oz. (kg)
9-1/2 (0.27)
10-1/2 (0.30)
11-1/4 (0.32)
A➋
B
C
5 (127)
5 (127)
5 (127)
5-7/8 (149.2)
5-7/8 (149.2)
5-7/8 (149.2)
6-1/8 (155.6)
6-1/8 (155.6)
6-1/8 (155.6)
Ship. Wt.
Oz. (kg)
14-3/8 (0.41)
15 (0.42)
16 (0.45)
➊ When using sealed switch contact block, this dimension is 4-1/16" (103 mm).
➋ When using sealed switch contact block, this dimension is 5-7/8" (149.2 mm).
10-145
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Approximate Dimensions and Shipping Weights, Continued
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Illuminated Push Buttons or Push-to-Test Pilot Lights
Transformer Type
1 21/64
Full Voltage, Dual Input or Neon Type
1 21/64
(34)
2 9/32
(58)
(34)
2 1/8
(54)
2 Dia.
(51)
1 13/16
(46)
2 9/32
(58)
1 31/32
(50)
2 Dia.
(51)
1 13/16
(46)
A
A
B
B
C
C
Illuminated Push Buttons, Push-to-Test Pilot Lights
Description
A➊
Style
Transformer Type
Full Voltage Dual Input or Neon Type
B
Ship. Wt.
Oz. (kg)
C
Standard Barrel
3-5/32 (80.2)
3-29/32 (99)
4-1/8 (105)
14 (0.40)
Long Barrel
5-1/16 (128.6)
5-13/16 (147.6)
6-1/16 (154)
16-3/16 (0.45)
Standard Barrel
3-1/32 (77)
3-29/32 (99)
4-1/8 (105)
11-5/8 (0.33)
Long Barrel
4-15/16 (125.4)
5-13/16 (147.6)
6-1/16 (154)
13-7/16 (0.38)
Push-Pull Units
Illuminated
Non-Illuminated
1 21/64
(34)
1 21/64
(34)
1 7 /16
2 9/32
(58)
(36.5)
0
1 31/32
(50)
1 1/2
(38.1)
1 13 /16
(46)
2 1/8 Dia.
(54)
D
1 13/16
(46)
Note:
Jumbo Head
2 (51)
A
B
A
B
C
C
Illuminated Push Buttons, Push-to-Test Pilot Lights
Description
Illuminated Transformer Type
Illuminated Full Voltage Type
Non-Illuminated Push-Pull Units
A➊
B
Standard Barrel
3-9/16 (90.5)
Long Barrel
4-21/32 (118.3)
Standard Barrel
3-7/16 (87.3)
Long Barrel
4-17/32 (115.1)
Standard Barrel
Long Barrel
Style
D
4-9/16 (115.9)
4-5/8 (117.5)
2-1/8 (54)
15-1/2 (0.44)
5-13/32 (137)
5-21/32 (143.7)
2-1/8 (54)
17-7/16 (0.49)
4-9/16 (115.9)
4-5/8 (117.5)
1-31/32 (50)
12-13/16 (0.33)
5-13/32 (137)
5-21/32 (143.7)
1-31/32 (50)
14-3/4 (0.41)
3-1/2 (88.9)
4-3/8 (111.1)
4-5/8 (117.5)
—
11-1/8 (0.32)
4-17/32 (115.1)
5-13/32 (137)
5-21/32 (143.7)
—
12-5/16 (0.34)
➊ When using sealed switch contact block add 7/8" (22.2 mm) to the listed dimension.
10-146
Ship. Wt.
Oz. (kg)
C
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Approximate Dimensions and Shipping Weights, Continued
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Pilot Lights
Transformer Type
Full Voltage, Pigtail Type
1 21/64
(34)
1 11/16
(43)
1 11/16
(43)
2
(51)
1 49/64 Dia.
(45)
A
LEADS
7 (178)
1 3/8
Dia.
(35)
1 5/8
Dia.
(41)
1 5/8
Dia.
(41)
A
Full Voltage, Dual Input or Neon Type
1 21/64
(34)
1 11/16
(43)
1 7/8
(47.5)
1 5/8
Dia.
(41)
1 49/64 Dia.
(45)
A
Description
Transformer Type and Dual Input Transformer Type Pilot Lights
Full Voltage, Neon or Dual Input Diode and Resistor Type Pilot Lights
Full Voltage Pigtail Type Pilot Lights
Style
A
Ship. Wt. Oz. (kg)
Standard Barrel
3-5/32 (80)
8-9/16 (0.24)
Long Barrel
4-9/16 (115.9)
30-1/4 (0.85)
Standard Barrel
3-1/32 (77)
5-13/16 (0.17)
Long Barrel
4-7/16 (112.7)
27-1/2 (0.77)
Standard Barrel
2-3/16 (55.5)
5-5/8 (0.16)
Long Barrel
3-43/64 (94)
8-5/16 (0.24)
Potentiometer Units
1 21/64
(34)
1 11/32
(34)
1 13/16
Dia.
(46)
1 3/8
Dia.
(35)
A
Style
A
Ship. Wt. — Oz. (kg)
Standard Barrel
3-1/8 (79.5)
5-3/8 (0.16)
Long Barrel
4-1/2 (114.3)
8 (0.23)
10-147
1
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Approximate Dimensions and Shipping Weights, Continued
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Shallow Base Stations
1 5/16
(33.3)
1 5/16
(33.3)
11/ Dia.
32
4 Mtg. Holes
(8.7∅)
19/
32
(15.1)
2 3/16
(55.6)
11/ Dia.
32
4 Mtg. Holes
(8.7∅)
19/
32
(15.1)
6 1/8
(155.6)
6 1/8
(155.6)
6 3/4
(171.5)
6 3/4
(171.5)
5/
16
19/
32
(7.9)
3/ -14 NPT
4
➊1
2 3/16
(55.6)
1 5/16
(33.3)
3 51/64
(96.4)
(15.1)
1/
16
(1.6)
3/
4
5/
16
(19)
1 15/32
(37.3)
3 21/32
(92.9)
(7.9)
1/
64
(.4)
1 5/16
(33.3)
19/
32
(15.1)
3 51/64
(96.4)
3/ -14 NPT
4
➊
➋
1 49/64
(44.8)
1/
16
(1.6)
3/
4
(19)
3 61/64
(100.4)
Figure 2
Shallow Base Station Component Type
1-Gang (1 or 2 devices)
Figure 1
Shallow Base Station Lever Type
Shipping Wt. 3 lbs (1.36 kg)
Shipping Wt. 3-1/2 lbs (1.58 kg)
0
Deep Base Stations
1 5/16
(33.3)
1 5/16
(33.3)
Optional
Conduit Entry
3/ -14 NPT
4
or
1-111/2 NPT
11/
32
(8.7)
3 11/32
(84.9)
Optional
Conduit Entry
3/ -14 NPT
4
or
1-111/2 NPT
11/
32
(8.7)
6 1/8
(155.6)
3 11/32
(84.9)
6 1/8
(155.6)
11/ Dia.
32
6 3/4
(171.5)
6 3/4
(171.5)
2 Mtg.
Holes
(8.7∅)
1/
16
5/
16
(1.6)
11/
32
(7.9)
7/
8
(22.2)
(8.7)
1 5/16
3/ -14 NPT
4
(33.3)
➊ Optional
3 3/4
1 -111/2 NPT
(95.2)
1 15/32
(37.3)
5/
16
(7.9)
3/ -14 NPT
4
➊Optional
4 13/16
(122.2)
➋
Figure 3
Deep Base Station Lever Type
1-Gang
Shipping Wt. 4 lbs (1.81 kg)
1 -111/2 NPT
1 5/16
(33.3) 11/
32
(8.7)
3 3/4
(95.2)
1/
64
(.4)
1 49/64
(44.8)
1/
16
(1.6)
7/
8
(22.2)
5 7/64
(129.8)
11/ Dia.
32
2 Mtg. Holes
(8.7∅)
Figure 4
Deep Base Station Component Type
1-Gang (1 or 2 devices)
Shipping Wt. 4-1/2 lbs (2.04 kg)
➊ When using a flange seal, an approved drain fitting must be provided (refer to National Electrical Code).
➋ When used add the following to the max. depth: Flange seal add 3/16" (4.8 mm). Sealing well with or without integral flange seal add 1/2" (12.7 mm).
10-148
Bulletin 800H
Hazardous Location Push Buttons
Type 7 & 9, for Divisions 1 & 2
Approximate Dimensions and Shipping Weights, Continued
Dimensions in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.
Factory-Assembled Stations
For depth dimension refer to Figure 3 or 4 on page 10-148.
3 3/4
(95.2)
5/
16
(7.9)
2 5/8
(66.7)
4 1/4
(108)
7 15/16
(201.6)
18 9/32
(464.3)
5/
16
9/
16
(14.3)
(7.9)
17 21/32
(448.5)
6 3/4
(171.4)
6 1/8
(155.6)
➊ Conduit Entry
➊ Pipe Plug 1 (25.4)
1-11 1/2 NPT
Conduit Entry ➊
1-11 1/2 NPT
4 1/4
(108)
2 5/8
(66.7)
Figure 5
Control Station, 2-Gang (up to 4 devices)
9/
16
(14.3)
Figure 6
Control Station, 3-Gang (up to 6 devices)
Shipping Wt. 10 lbs (4.54 kg)
Shipping Wt. 16 lbs (7.26 kg)
4 1/4
(108)
2 5/8
(66.7)
3 1/4
(95.2)
5/
16
(7.9)
Conduit Entry
1-11 1/2 NPT
7 15/16
(201.6)
9/
16
(14.3)
Conduit Entry
1-11 1/2 NPT
➊ Conduit Entry
(14.3)
➊ Conduit Entry
1-11 1/2 NPT
Figure 7
Control Station, 2-Gang (up to 4 devices)
(14.3)
Pipe Plug 1 (25.4)
➊ Conduit Entry 1-111/2 NPT
Optional 2-111/2 NPT
1 Pipe Plug
Pipe Plug 1 (25.4) ➊
1-11 1/2 NPT
2 5/8
(66.7)
4 1/4 (108)
Figure 8
Control Station, 4-Gang (up to 8 devices)
Shipping Wt. 10 lbs (4.54 kg)
12
(304.8)
8 1/2
(215.9)
1
12 1/2
(317.5)
11 13/16
(300)
11 13/16
(300)
9/
16
5/
16
(7.9)
1 Pipe Plug
12 1/2
(317.5)
9/
16
Conduit Entry
1-11 1/2 NPT
Shipping Wt. 20 lbs (9.07 kg)
9/
16
(14.3)
16 5/16
(414.3)
12 3/4
(323.9)
5/
16
(7.9)
Pipe Plug 1 (25.4)
➊ Conduit
Entry 1-111/2
NPT Optional
2-111/2 NPT
11 13/16
(300)
Pipe Plug 1 (25.4)➊
2 5/8
(66.7)
Pipe Plug 1 (25.4) ➊
8 1/2
(215.9)
11 13/16 12 1/2
(300) (317.5)
12 1/2
(317.5)
➊ Conduit Entry
1-11 1/2 NPT
Optional
2-11 1/2 NPT
Figure 9
Control Station, 6-Gang (up to 12 devices)
Shipping Wt. 32 lbs (14.5 kg)
Pipe Plug 1 (25.4) ➊
Pipe Plug 1 (25.4) ➊
2 5/8
(66.7)
12 3/4
(323.9)
➊ Conduit Entry
1-11 1/2 NPT
Optional
2-11 1/2 NPT
Figure 10
Control Station, 8-Gang (up to 16 devices)
Shipping Wt. 40 lbs (18.1 kg)
➊ When using a large flange seal, an approved drain fitting must be provided (refer to National Electric Code).
10-149