DIESEL POWER MODULE MTU 16V4000 DS1955 Voltages: 2160 kWe / 2700 kVA / 60 Hz / Standby - 480V 1955 kWe / 2443 kVA / 60 Hz / Prime - 480V 1760 kWe / 2200 kVA / 60 Hz / Continuous - 480V 1900 kWe / 2375 kVA / 50 Hz / Standby - 400V 1721 kWe / 2151 kVA / 50 Hz / Prime - 400V 1500 kWe / 1875 kVA / 50 Hz / Continuous - 400V SYSTEM RATINGS 60 Hz Voltage (L-L) Phase PF Hz kW kVA Amps skVA@30% Voltage Dip Generator Model Temp Rise Connection 50 Hz 480V 3 0.8 60 2,160 2,700 3,251 480V 3 0.8 60 1,955 2,443 2,942 480V 3 0.8 60 1,760 2,200 2,649 400V 3 0.8 50 1,900 2,375 3,432 400V 3 0.8 50 1,721 2,151 3,108 400V 3 0.8 50 1,500 1,875 2,709 5,750 744RDL4056 150 °C/40 °C 5,750 744RDL4056 125 °C/40 °C 5,750 744RDL4056 105 °C/40 °C 4,530 744RDL4056 150 °C/40 °C 4,530 744RDL4056 125 °C/40 °C 4,530 744RDL4056 105 °C/40 °C 4 BAR WYE 4 BAR WYE 4 BAR WYE 4 BAR WYE 4 BAR WYE 4 BAR WYE CERTIFICATIONS AND STANDARDS // Emissions – Fuel Optimized // Generator set is designed and manufactured in facilities certified to standards ISO 9001:2008 and ISO 14001:2004 // Container – CSC Certified // Performance Assurance Certification (PAC) - Generator Set Tested to ISO 8528-5 for Transient Response - Verified product design, quality and performance integrity - All engine systems are prototype and factory tested // Power Rating - Permissible average power output during 24 hours of operation is approved up to 85% for standby rated unit. - Permissible average power output during 24 hours of operation is approved up to 75% for prime rated unit. - Permissible average power output during 24 hours of operation is approved up to 100% for continuous rated unit. 2 / // / MTU 16V4000 DS1955 (1955 kWe) - Power Module STANDARD FEATURES* MTU Onsite Energy is a single source supplier Global Product Support Consult factory for specific warranty terms 16V 4000 Diesel Engine - 76.3 Liter Displacement - Common Rail Fuel Injection - 4-Cycle // Engine-Generator Resilient Mounted // Complete Range of Accessories // // // // Generator - Brushless, Rotating Field Generator - 2/3 Pitch Windings - PMG (Permanent Magnet Generator) Supply to Regulator - 300% Short Circuit Capability // Digital Control Panel - Complete System Metering - LCD Display // Cooling System - Remote Mounted / Vertical Split Cores - Electrically Driven Fans // STANDARD EQUIPMENT* // Engine Air Cleaners Oil Pump Oil Drain Extension & S/O Valve Lube Oil Multi-Stage Filter Closed Crankcase Ventilation Jacket Water Pump Thermostats Radiator - Remote Mounted Electric Starting Motor - 24V Governor – Electronic Isochronous Base - Formed Steel SAE Flywheel & Bell Housing Charging Alternator - 24V Battery Rack & Cables Fuel Optimized (Both 60 Hz and 50 Hz) // Full Amortisseur Windings 125% Rotor Balancing 3-Phase Voltage Sensing ±0.25% Voltage Regulation 100% of Rated Load - One Step 5% Maximum Total Harmonic Distortion Note: Air filter will cause 5% derate in power output (kWe) and may also affect fuel consumption. // Digital Control Panel(s) Digital Metering Engine/Generator Protection Functions CANBus ECU Communications Multilingual Capability Programmable Contact Outputs Generator NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting Sustained short circuit current of up to 300% of the rated current for up to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation Brushless Alternator with Brushless Pilot Exciter 4 Pole, Rotating Field 2 Bearing, Sealed Close Coupling // Container 40’ High Cube ISO Container Rear Container Double Doors Three Lockable Personnel Access Doors 1,500 Liters (400 gallons) UL 142 Certified Diesel Fuel Tank Externally Mounted Critical Grade Exhaust Silencer (stored during transport between the split core radiator) NEMA 1 Floor-Standing Generator Set Breaker Panel Main Line Circuit Breaker Rated at 3200 Amps and 65KAIC 24 VDC Incandescent Lights Field Adjustable Timer, Factory Set to 60 Minutes * Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations. 3 / // / MTU 16V4000 DS1955 (1955 kWe) - Power Module APPLICATION DATA // Engine // Manufacturer Model 60 Hz Standby Model 60 Hz Prime Model 60 Hz Continuous Model 50 Hz Standby Model 50 Hz Prime Model 50 Hz Continuous Type Arrangement Displacement: L (Cu In) Bore: cm (in) Stroke: cm (in) Compression Ratio Rated RPM: 60 Hz Rated RPM: 50 Hz Engine Governor Standby Rated Power: MTU 16V 4000 G83 3D 16V 4000 G83 3B 16V 4000 G83 3A 16V 4000 G63 3D 16V 4000 G63 3B 16V 4000 G63 3A 4-Cycle 16-V 76.3 (4,656) 17 (6.69) 21 (8.27) 16.5:1 1,800 1,500 Electronic Isochronous (ADEC) 60 Hz: kWm (hp) 2,500 (3,352) 50 Hz: kWm (hp) 2,185 (2,930) Prime Rated Power: 60 Hz: kWm (hp) 2,280 (3,057) 50 Hz: kWm (hp) 1,965 (2,635) Continuous Rated Power: 60 Hz: kWm (hp) 1,950 (2,614) 50 Hz: kWm (hp) 1,635 (2,192) Speed Regulation ±0.25% Air Cleaner Dry // Fuel Consumption 60 Hz At 100% of Power Rating: L/hr (gal/hr) At 75% of Power Rating: L/hr (gal/hr) At 50% of Power Rating: L/hr (gal/hr) STANDBY PRIME 613 (162) 538 (142) 458 (121) 435 (115) 397 (105) 352 (93) 303 (80) 276 (73) 254 (67) 50 Hz At 100% of Power Rating: L/hr (gal/hr) At 75% of Power Rating: L/hr (gal/hr) At 50% of Power Rating: L/hr (gal/hr) STANDBY PRIME // CONTINUOUS CONTINUOUS 500 (132) 435 (115) 367 (97) 371 (98) 329 (87) 284 (75) 254 (67) 231 (61) 201 (53) Cooling - Radiator System Ambient Capacity of Radiator: °C (°F) Max. Restriction of Cooling Air, Intake, and Discharge Side of Rad.: kPa (in. H20) Water Pump Capacity: L/min (gpm) Heat Rejection to Coolant: kW (BTUM) Heat Rejection to After Cooler: kW (BTUM) Fan Power: kW (hp) 55 (131) 0.125 (0.5) 1,350 (357) **960 (54,593) **560 (31,846) 99.5 (133.4) Liquid Capacity (Lubrication) Total Oil System: L (gal) Total Oil Change: L (gal) Engine Jacket Water Capacity: L (gal) After Cooler Water Capacity: L (gal) System Coolant Capacity: L (gal) 300 (79.3) 240 (63.4) 175 (46.2) 50 (13.2) 852 (225) // Air Requirements Aspirating: *(m3/min) SCFM Air Flow Required for Rad. Cooled Unit: *(m3/min) SCFM **192 (6,780) 3,862 (136,409) * Air density = 1.184 kg/m3 (0.0739 lbm/ft3) // Electrical Electric Volts DC Cold Cranking Amps Under -17.8 °C (0 °F) // 24 2,600 Fuel System Maximum Fuel Lift: m (ft) Recommended Fuel Total Fuel Flow: L/hr (gal/hr) 3 (10) Diesel #2 1,200 (317) // Exhaust System Gas Temp. (Stack): °C (°F) Gas Volume at Stack Temp: m3/min (CFM) Maximum Allowable Back Pressure: kPa (in. H20) ** For 60 Hz Standby Rated Power **505 (941) **504 (17,799) 8.5 (34.1) 4 / // / MTU 16V4000 DS1955 (1955 kWe) - Power Module WEIGHTS AND DIMENSIONS Drawing above for illustration purposes only. Do not use for installation design. System Power Module Dimensions (L x W x H) 12,203 x 2,438 x 2,896 mm (480 x 96 x 114 in) Weight (wet/no fuel) 30,546 kg (67,201 lb) Weights and dimensions are based on containerized units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set. SOUND DATA Unit Type Power Module dB(A) Full Load - Standby C/F Full Load - Prime C/F Full Load - Continuous C/F RATING DEFINITIONS AND CONDITIONS Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO 8528-1, ISO-3046-1, BS 5514, and AS 2789. Average load factor: ≤ 85%. Standby 50 Hz operating hours per year: Max. 500. // Prime power and continuous ratings apply to installations where utility power is unavailable or unreliable. At varying load for prime power ratings or non-varying load for continuous ratings, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve for both ratings. Ratings are in accordance with ISO 8528-1, ISO 3046-1, BS 5514, and AS 2789. Average load factor: ≤ 75% (Prime) ≤ 100% (Continuous). // Deration Factor: Altitude: Consult your local MTU Onsite Energy Power Generation Distributor for altitude derations. Temperature: Consult your local MTU Onsite Energy Power Generation Distributor for temperature derations. // Product intended for use outside of the United States. C/F = Consult Factory/MTU Onsite Energy Distributor N/A = Not Available MTU Onsite Energy A Rolls-Royce Power Systems Brand www.mtuonsiteenergy.com © MTU Onsite Energy. Subject to alteration due to technological advances. 2015-03 Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.