Enclosure and Sound Data Sheet Diesel 350

ENCLOSURE AND SOUND DATA SHEET - DIESEL
350-600 kW Standby / 325-550 kW Prime
ENCLOSURE LEVEL IDENTIFICATION
Level 1
Weather-protective enclosure constructed of heavy gauge steel or aluminum with
fixed storm proof panels designed for 130 mph wind load rating. Enclosure consists
of a bolted and welded construction with unit-mounted internal muffler included.
Hinged, lockable double-door access on both sides of the enclosure.
Level 2
Level 1 enclosure with UL 94 HF-1 compliant, 1.5" thick sound attenuated foam
insulation installed inside enclosure walls.
Level 3
Level 2 enclosure with air intake and exhaust scoops with UL 94 HF-1 compliant, 1.5"
thick sound attenuated foam insulation installed in scoops.
CERTIFICATIONS AND STANDARDS
• UL 2200
• CSA
• ISO 9001:2008
• IBC / OSHPD
STANDARD FEATURES FOR ALL LEVELS
• Heavy material construction
- Steel Enclosure: 14 gauge or greater
- Aluminum Enclosure: 0.09” thick or
greater
• 130 mph wind rating
• Serviceability access
- Double door access gives ease of
serviceability to all components
• Pitched roof
• Rain shroud and rain cap
• Rodent barriers
• Scoop access panels and drain
• Hardware
- Powder coated hinges with stainless steel pins
- Key-lockable and pad-lockable powder coated
door handles
• Finish Paint: ANSI 61 Grey standard
- Custom colors available upon request
• Internal silencer (Critical grade or better)
- Insulated or wrapped mufflers and exhaust
pipes
- Stainless steel flexible exhaust connections
(where applicable)
// Page 1 of 3
ENCLOSURE AND SOUND DATA SHEET - DIESEL
350-600 kW Standby / 325-550 kW Prime
OPTIONAL FEATURES
• Door restraints
• AC or DC light package
• Motorized / gravity louvers (where available)
• 190 mph wind rating
• For other custom options, please consult factory.
SOUND RATINGS dB(A) AT 7 METERS
Application
Standby
Prime
Model
MTU 8V1600 DS350
MTU 8V1600 DS400
MTU 10V1600 DS450
MTU 10V1600 DS500
MTU 12V1600 DS550
MTU 12V1600 DS600
MTU 8V1600 DS350
MTU 8V1600 DS400
MTU 10V1600 DS450
MTU 10V1600 DS500
MTU 12V1600 DS550
MTU 12V1600 DS600
Power Node
350 kW
400 kW
450 kW
500 kW
550 kW
600 kW
325 kW
365 kW
400 kW
450 kW
500 kW
550 kW
Level 1
85.3
85.9
87.6
87.8
88.5
88.5
85.5
85.5
C/F
87.6
88.5
88.3
Level 2
84.3
84.6
87.1
87.1
86.9
86.8
84.2
84.1
87.1
87.1
86.9
86.9
Level 3
72.8
72.9
75.4
75.4
76.5
76.7
72.7
72.8
C/F
75.4
76.1
76.5
// Page 2 of 3
ENCLOSURE AND SOUND DATA SHEET - DIESEL
350-600 kW Standby / 325-550 kW Prime
NOTE:
• Aluminum enclosure sound levels are approximately 2 dB(A) higher than listed sound levels for steel
enclosures
• Sound pressure levels subject to instrumentation, measurement, installation, and generator set variability
• Sound power levels per ISO 8528-10 and ANSI S1.13-2005
• Sound data measured with:
- Full-rated load
- Standard radiator package
- Infinite exhaust connection
Refer to the MTU Business Portal Acoustics Data for exhaust noise ratings.
© MTU Onsite Energy. Subject to alteration due to technological advances. 2015-01
C/F = Consult Factory
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com
// Page 3 of 3