Manual - RMT Ltd

THERMOELECTRIC GENERATOR DEVELOPMENT KIT
DX8130
USER GUIDE
MOSCOW 2015
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
EDITION FEBRUARY 2015
COPYRIGHT
All rights reserved.
Reproduction in any manner, in whole or in part is straightly prohibited without written permission
of RMT Ltd.
The information contained in this document is the subject to change without notice.
TRADEMARK ACKNOWLEDGMENTS
All trademarks are the property of their respective owners.
RMT Ltd.
46 Warshavskoe shosse. Moscow 115230 Russia
phones: +7-499-678-20-82
fax: +7-499-678-20-83
e-mail: [email protected]
Copyright © 2015 RMT Ltd.
Release 1.0
Page 2 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
CONTENTS
Contents ...................................................................................................................................................3
Introduction .............................................................................................................................................4
Specifications ...........................................................................................................................................5
Delivery Kit ...............................................................................................................................................6
Description of the Development Kit ........................................................................................................7
Thermoelectric Generator Unit............................................................................................................8
Controller of Heat Sources ...................................................................................................................9
Control and Indication Board ...............................................................................................................9
Boards of DC/DC Converters ..............................................................................................................11
Wiring Diagram ..................................................................................................................................15
Software TEGLab ....................................................................................................................................16
Program Window. Main Tab ..............................................................................................................16
Program Window. Terminal Tab. .......................................................................................................18
Work with Thermoelectric Generator Development Kit DX8130 ..........................................................19
Getting Ready.....................................................................................................................................19
How to Mount/Replace Thermoelectric Generator...........................................................................20
Checking Serviceability of Thermoelectric Generator Circuit ............................................................23
Checking Thermal Resistance of Contact Layers................................................................................27
Current-Voltage Characteristic of Thermoelectric Generator ...........................................................30
Checking the Circuit of Thermoelectric Generator with DC/DC converter........................................31
Current-Voltage Characteristic of the Circuit of Thermoelectric Generator with DC/DC Converter 35
Connection/replacement of DC/DC converter board ........................................................................37
Checking Load Capacity of Thermoelectric Generator ......................................................................38
Checking Load Capacity of Circuit of Thermoelectric Generator with DC/DC Converter ..................39
Release 1.0
Page 3 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
INTRODUCTION
The
Thermoelectric
Generator Development Kit
DX8130 (hereinafter the
Development Kit) is a
tabletop laboratory for
studying
thermoelectric
micro-generators,
testing
their operating parameters,
optimizing the design of
thermoelectric
devices
converting thermal energy
(energy
harvesting),
simulating their work in real
conditions.

Thermoelectric Generator Development Kit DX8130 is unique equipment having no
analogues.

It is a powerful assistant for designers, experienced users and researchers in the field of
thermoelectric energy harvesting
The tabletop laboratory is useful both for development of
practical devices and laboratory studies.
The Development Kit is based on an open circuit and
enables constructing "on the table" prototypes of
thermoelectric energy harvesting devices with
thermoelectric generators. High-performance miniature
thermoelectric generators can be selected from the
supplied Development Kit set. Other modules can be used
too.
Simple interconnections like in electronic snap circuits
allow building a thermoelectric converter circuit with
DC/DC converter. Modules of modern DC/DC converters
are included in the Development Kit.
Полярность
напряжения
2
1
HOT
6
5
4
3
DC
TEC1
Uout
OUT
FLUX1
DC
Uext
IN
T1
EXT
2
GEN
1
XP1
GN
Uin
3
4
5
COLD
6
1
2
T2
FLUX2
TEC2
Mounting scheme of generator
between thermal sources
Release 1.0
Iin
Ugn Ign
Wiring diagram of generator
Page 4 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
The controller modules, fine measurement electronics and precise programmable heat sources,
computer remote control and data logging provide modeling of operation of assembled
thermoelectric energy harvesting device prototypes in a wide range of operational conditions. The
measurement electronics provides data logging of acquired test data. The software provides data
processing, investigating standard performance parameters and plots, such as volt-ampere
characteristics, temperature dependences of performance parameters and others.
Volt-ampere characteristics of thermoelectric
generator
Volt-ampere characteristics of thermoelectric
generator with DC-DC converter
SPECIFICATIONS
#
1
2
3
4
5
6
7
8
9
7.1
7.2
9.1
9.2
10
11
12
13
14
14.1
14.2
14.3
14.4
14.5
Parameter
Temperature range of stabilizing of every programmable
heat loads (two units in the Kit)
Maximal temperature difference between hot and cold
sides
Output voltage range of TEG
Electric current range of the TEG
Heat flux range
Output voltage of DC-DC converter
Load current
High current mode
Low current mode
Computer interface
Dimensions of TEGs, min…max
АхВ
Н
Power Supply of the Kit
Maximal power consumption
Overall dimensions of Kit АхВхН, max
Weight
Dimensions of main modules
Test bench
Electronic plate
Controller unit
Programmable heat flux unit
DC/DC converter unit
Release 1.0
Units
°С
value
+10 … +100
°C
50
V
A
W
V
0 … 9.999
0 … 1.000
0 … 9.999
0 … 9.999
A
mA
0 ... 0.100
0 … 5.0
USB
mm2
mm
V
W
mm3
Kg
2х2 … 30х30
0.5 … 5.0
110 … 240
60
200х300х80
3.0
mm3
mm3
mm3
mm3
mm3
200х300х20
100х200х25
55х55х35
55х55х8
55х55х10
Page 5 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
DELIVERY KIT
#
1
2
3
4
5
6
7
8
9
10
11
Item
Set of standard thermoelectric microgenerators of RMT (one unit
each):
Q-ty
1 set
Standard mounting frame (for mounting of optional TEG)
Set of DC-DC converter boards with standard DC-DC circuits (one unit
each):
1 pc
1 set
-
1MD06-127-08TEG (13х13х1.9 mm - 5.9 Ohm – 50 mV/K)
1MD04-127-08TEG (9.8х9.8х1.9 mm – 16.3 Ohm – 50 mV/K)
1MD06-071-05TEG (9.8х9.8х1.9 mm - 2.1 Ohm – 28 mV/K)
1MD03-060-05TEG (4.0х7.5х1.1 mm - 6.8 Ohm – 24 mV/K)
-
BQ25504RGT (Texas Instruments)
- LTC3108EGN (Linear Technology)
Programmable precise heat flux unit
OEM controller DX5100 to manage by heat flux units
Control electronic and indication board
Software TEGLab (flesh disk)
Power supply
Set of cables
User Guide (flesh disk)
Plastic safety bag
9
2 pc
1 set
1 pc
1 set
1 pc
1 set
1 pc
1 pc
8
5
6
1
11
1
4
3
2
Fig. 1 Delivery kit
Release 1.0
Page 6 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
DESCRIPTION OF THE DEVELOPMENT KIT
Thermoelectric
Generator Unit
Control and Indication
Board
Test Bench
Controller of Heat Sources
Board of DC/DC
Converter
Fig. 2 Thermoelectric Generator Development Kit with preset components assembled
The thermoelectric generator development kit consists of the following.
-
Set of standard thermoelectric micro-generators of RMT. The set may be extended at the
request of additional types of micro-generators produced by RMT, or a User can apply
another generator, of other manufacturers.
-
Fully functional boards with DC/DC converters to obtain voltage needed from the standard
generator. The kit consists of two boards with modern DC/DC converters from the
companies Linear Technology and Texas Instrument. Electronic circuits of DC/DC converters
of other types can be supplemented to the Development Kit on request.
-
Controlled precision heat sources. Two identical modules that stabilize the top temperature
(hot side) and bottom temperature (cold side) of a thermoelectric generator tested. They
include temperature and heat flux sensors.
-
Controller of heat sources. The controller is based on the range of commercially available
controllers DX5100 of RMT.
-
Control and indication board. The Development Kit provides a convenient way to connect all
the elements included, a detailed indication of the operating parameters of the experiment,
connection to an external computer. The Development Kit is controlled either by the control
elements on the board or by the software TEGLab on an external computer.
Release 1.0
Page 7 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
-
Software TEGLab to be installed on an external computer. It provides the control of the
Development Kit: setting of all operating parameters, work indication, recording currentvoltage characteristic of a generator and selected DC/DC converter, data logging.
-
Elements of the laboratory Development Kit are located on the test bench - a small
aluminum plate carrier. All the elements are accessible, can be easily installed and can be
removed by a User depending on experiments.
The Development Kit is supplied assembled and packed in the plastic case. The Development Kit with
pre-assembled components is ready to use.
Thermoelectric Generator Unit
The thermoelectric generator is placed between two
heat precision sources controlled.
In the Development Kit it is taken for the rule that the
upper heat source works as a heater (HOT), the
bottom one works as a cooler (COLD).
Each of the heat sources contains a built-in
thermoelectric module as a heat source, a
thermoelectric heat flux sensor and the platinum
thermistor Pt1000.
The heat flux sensor of the top (HOT) heat source
controls the heat generated. The lower heat flux
sensor (COLD) measures the amount of heat that passed through the tested thermoelectric module.
Fig. 3 Layout of the generator GEN between the heat sources (HOT and COLD)
Attention! The generator orientation should comply with the drawing.
The temperature sensors measure the given and maintained temperature and allow obtaining the
overall temperature difference between the heat sources. The overall temperature difference
Release 1.0
Page 8 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
includes that of the thermoelectric generator tested (operating temperature difference) and of
contact layers (losses).
To ensure a good thermal contact and to reduce losses on top, this sandwich (thermoelectric
generator-heat source) is pressed by a spring clamp.
Controller of Heat Sources
The precision heat sources are controlled by the two-channel controller created on the basis of the
controllers’ family DX5100 OEM (http://www.rmtltd.ru/products/devices/controllers/dx5100oem/).
Fig. 4 Controller of heat sources (HOT and COLD)
Control and Indication Board
All the measurements and indication control is performed by this board.
Fig. 5 Control and indication board
Release 1.0
Page 9 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
The control and display board is in the center of the test bench and includes several indicators,
commutation elements (terminals and switching connectors) and control elements (buttons,
switches).
Control and Indication Elements
ON
Power switch
Heater
temperature
indicator
1/0
C
Heater control buttons
Cooler
temperature
indicator
1/0
Cooler control buttons
W
Set
V
OUT
GEN
Voltmeter of load
Set
C
Voltmeter of
generator
Ammeter of
generator
W
0
COLD
Indicator of heat
flux
LOAD
Control of generator
connection.
Switch up - to connector
"OUT", down - to the
load.
A
LD
GN
IN
V
Ammeter of load
Power connector.
0
HOT
Indicator of heat
flux
12V
EXT
A
LO
CUR
Control of load
connection.
Switch up - to the
generator; down - to the
connector "IN".
Jumper of current limits
selection.
Regulator of load current
value.
Fig. 3 Elements of control and indication on the control board.
Buttons
Button of start and stop temperature control
Button to increase the setpoint temperature
! The cooler temperature setpoint cannot be
above that of the heater.
Button to go to the setpoint correction mode.
Exit from the mode setpoint correction if the
button is pushed, or after a time delay if no
button is pushed.
Release 1.0
Button to decrease the setpoint temperature
! The heater temperature setpoint cannot be
below that of the heater.
Page 10 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
Temperature Indication
control
The current temperature
regulation is on.
is
displayed. Temperature
Idle
(hold)
The current temperature is displayed with the index "H"
(Hold). Temperature regulation is off.
setting
The temperature indication is flashing in the setpoint
correction mode.
Current Indication and Selection of Current Limit
The current unit is 1 A (the jumper of current limits
selection LO is not connected). The value of the load
current is up to 500 mA. The minimum load resistance is 1
Ohm.
The current unit is 1mA (the jumper of current limits
selection LO is connected). The value of the load current is
up to 5 mA. The minimum load resistance is 100 Ohm.
The current value is regulated by the variable resistor (by a local control) or from the program (by a
computer). When operating by the computer the jumper of current limit selection should not be
connected.
Boards of DC/DC Converters
There are two variants of boards with DC/DC converters in the
Thermoelectric Generator Development Kit DX8130.
Generally a DC/DC converter is necessary for converting the
thermoelectric generator output voltage changing with
temperature difference to the standard value of the supply
voltage of electronic devices.
Most modern microcircuits of DC/DC converters provide the
majority of known standard voltages (3.3, 4, 5 V, etc.) by an
output switching of the circuit.
The important properties of using DC/DC converters with thermoelectric generator are:
-
Minimal input signal of starting the converter work;
-
Converter efficiency.
The minimum input signal providing the DC/DC converter startup and work is important as
thermoelectric microgenerators in energy harvesting applications operate by very low heat fluxes
and with small temperature differences. Therefore, the thermoelectric generator produces almost
zero thermoelectric power.
Release 1.0
Page 11 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
The efficiency of the DC/DC converter circuit is important in any case. In the case of a thermoelectric
generator, this value is even more critical as the efficiency of the thermoelectric generator itself is
very low - 0 ... 4-5% depending on the source of heat (difference of temperatures). Therefore, the
most effective subsequent energy conversion is crucial.
There are two boards with modern DC/DC converters optimized for use with a thermoelectric
generator in energy harvesting applications in this delivery kit:
-
BQ25504RGT (Texas Instruments)- Ultra Low-Power Boost Converter With Battery
Management for Energy Harvester Applications
-
LTC3108EGN (Linear Technology) - Ultralow Voltage Step-Up Converter and Power Manager
If necessary, a User can connect another board with a different DC/DC converter to the circuit of the
test bench. Replacement procedure is described in this manual.
Release 1.0
Page 12 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
Board with DC/DC Converter BQ25504RGT
Appearance
Layout of elements
Circuitry
Detailed technical documentation on the DC/DC converter BQ25504RGT (and related links) –
http://www.ti.com/product/BQ25504/description.
Release 1.0
Page 13 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
Board with DC/DC Converter LTC3108EGN
Appearance
Layout of elements
Circuitry
Detailed technical documentation on the DC/DC converter LTC3108 (and related links) http://www.linear.com/product/LTC3108.
Release 1.0
Page 14 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
Wiring Diagram
DC
Uout
Uext
DC
OUT
IN
EXT
GN
Uin
Iin
Ugn Ign
LOAD
GEN
Fig. 4. General wiring diagram
A thermoelectric generator is connected to the terminal block GN, the board of DC/DC converter is
connected between the terminal blocks OUT and IN. To terminal block EXT can be connected to the
external load. The wiring provides four ways of switching the thermoelectric generator shown in
Table 1.
Table 1. Connection options of thermoelectric generator
#
1
2
3
4
1)
2)
Option connection
Generator circuit is open 1)
Generator to internal load1)2)
Generator to DC/DC converter and internal load
Generator to DC/DC converter and external load
Position of switches
GEN is down/ LOAD is down
GEN is down/ LOAD is up
GEN is up/ LOAD is down
GEN is up/ LOAD is up
The voltmeter of the group LOAD (Uin) may show incorrect values, as it is not connected.
Internal load is controlled both by the board, and by a computer.
DC
Uout
OUT
DC
Uext
IN
EXT
GN
Uin
Iin
Ugn Ign
Fig. 4 Switching circuitry of the thermoelectric generator (red - to the board of the DC/DC converter;
blue - directly to the internal load)
Release 1.0
Page 15 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
SOFTWARE TEGLAB
There is control software TEGLab in the delivery kit.
To work with the program, simply copy its folder (a flash drive as part of delivery) to the control
computer.
Program Window. Main Tab
T0
T1
34
35
1
2
4
3
5
8
6
7
12
13
10
9
11
14
19
16
15
17
21
20
18
24
23
25
22
26
29
27
31
28
30
33
32
Fig. 5. The main window of the software TEGLab
Elements of software main window
#
Description
1
Indicator of commutation of the program and test bench
Heater (HOT)
Current temperature
Heat flux from heater (Qhot)
Current setpoint of temperature
2
3
4
Release 1.0
Conditions of
indication
Page 16 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
#
Description
5
6
7
31
32
33
34
35
Entering the setpoint temperature
Status indicator and start/stop of control (temperature maintenance)
Voltage of heat flux sensor
Cooler (COLD)
Current temperature
Heat flux to cooler (Qcold) through the generator
Current setpoint of temperature
Entering the setpoint temperature
Status indicator and start/stop of control (temperature maintenance)
Voltage of heat flux sensor
Generator
Thermoelectric generator voltage (Ugn)
Generator current (Ign)
Voltage at the terminals OUT (Uout=Ugn –Ign*Rshunt)
Field to enter the number of generator pairs of elements
Generator temperature difference estimated
Generator power (Pgen=Ugn*Ign)
Generator effeciency (eff=Pgn/Qcold)
Load
Voltage at the terminals IN (Uin)
Current of the terminals IN (Iin)
Voltage at the terminals EXT (Uext=Uin-Iin*Rshunt)
Power at the terminals IN (Pin=Uin*Iin) Pin=Pload
Effeciency of DC/DC converter eff= Pload / Pgn
Load current
Indicator / Switch of load current control locally/by computer
Indicator / Switch of load current control LO / HIGHT
Load current controller
Indication of load current - % of the maximal value
Current-voltage characteristic (CVC)
Place of load connection
Switch of group
Switch of group
GEN (top)
LOAD (bottom)
GEN
down
up
Generator CVC
LOAD
up
down
DC/DC converter CVC
Delay before measurement after setting the current
Number of measurement points (number of intervals of current change)
Button of starting CVC.
Button of recording current measurements in the logging file.
Display of the logging file saved
T0
T1
Terminal tab
Main tab
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Release 1.0
Conditions of
indication
1
1
2
3
4
5
5
5
5
5
5
5
1
1
Page 17 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
Indication Conditions
1
Displayed if the expert mode is enabled.
2
3
4
5
Expert mode is on/off with the key combination CNTRL+DEL
Displayed at the generator current less than 3mA.
Displayed if Pgn >10 mW.
Displayed if Pload >0.5 mW.
Control of load current from the computer
Program Window. Terminal Tab.
By the keys CNTRL+DEL the Expert mode is enabled - tab TabDebug and debug window.
The debug window shows the current telemetry of the device.
Fig. 6 Additional window of the program TEGLab. It is only enabled in the expert mode by the keys
CNTRL+DEL.
Release 1.0
Page 18 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
WORK WITH THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
Getting Ready
-
Remove the test bench of Thermoelectric Generator Development Kit DX8130 from the
plastic case.
-
Place the test bench on a flat surface of the table.
Make sure that the toggle switch on the control circuit board is in the "off" position (1).
-
Connect the power supply to the control board (2).
-
Connect the power supply to an AC outlet.
In this case, the blue LED on the control board near the toggle switch lights steadily (3).
-
Connect the USB cable to the controller (4) that controls the heat sources and to a
computer with pre-installed program TEGLab running.
On top of the controller board the blue LED RST will light up, which indicates connection
to the computer (5).
-
Turn on the power switch of the control board (6).
The indicators on the control board turn ON. Similar indicators of the control program
are beginning to give out similar information.
The fan of the heat sink turns on (a poor sound) on the test bench.
-
The test bench and all its components are ready for operation.
Indicators of heat sources on the hot and cold sides indicate the status Hold.
6
1
3
2
5
4
Release 1.0
Page 19 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
How to Mount/Replace Thermoelectric Generator
In the Thermoelectric Generator Development Kit
assembled, the unit of thermoelectric generator is
located in the left half of the test bench. It is assembled
using one of the standard thermoelectric microgenerators of the supplied kit (see the Section
"Delivery Kit").
Before mounting/replacing, make sure that the
control board is switched off. The toggle switch is in
the "OFF" position.
The microgenerator is replaced in the following
sequence.
A. Hold the upper spring-loaded clamp and, press
lightly on top.
Keep a little closer the locks of the spring-loaded
clamp (indicated by arrows).
B. Remove the spring-loaded cover.
C. Carefully remove the upper controlled heat source
along the guides (arrow) upwards.
It is not necessary to disconnect the heat source
from the connector.
Release 1.0
Page 20 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
D. Carefully by the guides (see the arrow) remove the
frame with the soldered thermoelectric generator
upwards.
E. Disconnect the cable from the connector on the
frame (see the arrow).
F. After removing the frame with the generator there
is only a bottom heat source left in the generator
unit.
It is not necessary to dismount it.
G. Select another thermoelectric generator from the
kit (there are four thermoelectric micro-generators
produced by RMT).
H. If you want to apply another thermoelectric
generator, use the free frame supplied.
I. Solder the terminals of the generator to the
contacts on the frame as done for the samples
available.
Polarity should be observed in accordance
with the Figure.
Release 1.0
Page 21 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
The generator unit is assembled in the reverse
order.
J. Connect the generator cable back to the connector
on the frame.
K. Carefully lower the frame by the guides to the
bottom controllable heat source.
The connector on the generator frame should
be turned down.
L. L. Lower the upper heat source by the guides on the
frame with the generator.
M. From above put on the spring-loaded clamp.
N. Keep slightly closer the side locks and push the top
of the spring-loaded clamp. Release the side locks.
Release 1.0
Page 22 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
O. The unit is assembled.
Checking Serviceability of Thermoelectric Generator Circuit
Prepare the test bench of Thermoelectric Generator Development Kit DX8130 for work in accordance
with the instructions "Getting Ready".
As an example, a generator from the delivery kit is installed in the thermoelectric generator unit.
For example, the module 1MD06-127-08.
The specification for this type is available from RMT’s site http://www.rmtltd.ru/datasheets/Thermoelectric_Generators/1md06127_teg.pdf
A. Turn the switch of the group GEN to the position down, and
the switch of the group LOAD to the position down.
So, this is the case "Generator is open" (Section "Wiring
Diagram", Table 1)
B. Press the button "Set" of the group "HOT".
Release 1.0
Page 23 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
C. The temperature indicator in the flashing mode will start
showing the preset temperature of the upper heat source.
D. The settings can be changed using the arrow buttons "up"
and "down".
After setting the desired temperature, press "Set".
E. The temperature indicator shows the current temperature.
The index "H" (Hold) before the temperature readings
indicates that the heat source is turned off, not active.
F. Press the power button on the heat source "1/0".
The symbol "H" disappears. The temperature indicator
shows the actual temperature reaching the set point.
This process takes time - a few minutes.
G. Repeat the same temperature setting of the bottom heat
source by the group "COLD.
Take steps as in items B-F, but for the bottom heat source
"COLD".
Press the button "Set" of the group "COLD".
Release 1.0
Page 24 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
H. The temperature indicator in the flashing mode will start
showing the preset temperature of the bottom heat source.
The settings can be changed using the arrow buttons "up"
and "down".
After setting the desired temperature, press "Set".
I. The temperature indicator shows the current temperature.
The index "H" (Hold) before the temperature a reading
indicates that the heat source is turned off, not active.
J. Press the power button on the heat source "1/0".
The symbol "H" disappears. The temperature indicator
shows the actual temperature reaching the set point.
This process takes time - a few minutes.
K. Wait for the temperature values of both heat sources
achieving the steady state.
The overall temperature difference is the difference of the
top and bottom steady-state temperatures.
In the case shown ∆T=45°C - 25°C=20°C.
L. In the steady state the heat flux indicator of the group
"COLD" displays the heat flux through the sample
thermoelectric generator.
The voltage indicator of the group "GEN" shows the thermal
e.m.f. of tested the thermoelectric generator under these
conditions (at a steady-state temperature difference).
Release 1.0
Q
E
Page 25 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
More information on the system operation is displayed in
the main window of the running software TEGLab.
M. To control the Development Kit by your computer, click on
the button "Local".
N. The additional control elements are open.
The button switches to the status "PC Mode" meaning
control of the advanced settings from the computer (see
below).
To be able to control the load current as fully as possible,
the jumper "LO" should be removed from the board.
O. The indications of the indicators in the program repeat
those of the indicators on the control board.
However, there are some differences.
The values of the heat flux indicators on the board are
limited to one digit of integer. Therefore, the maximum
displayed value is 9.999. The corresponding indicator in the
program TEGLab is free of this drawback and shows the true
value even if it exceeds 9.999. The program also indicates a
sign (direction) of the hat flux.
P. The software also enables calculating operating
temperature difference on the sides of the generator ∆Tw.
For that, it is necessary:
- Press the button "N="
- Specify the number of pairs of elements of the generator
tested.
- "ОК"
Q. By the approximate value of thermal e.m.f. per elements
pair, the program calculates and displays the value of the
working temperature difference ∆Tw on the generator. This
value is always less than the total temperature difference
∆T.
The difference (∆T-∆Tw) is thermal loss on the interfaces –
contacts of the heat sources with the tested generator.
∆T
∆Tw
R. In the example above (A-Q) the thermoelectric generator operation is checked at given top and
bottom temperatures.
Release 1.0
Page 26 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
The generator at a given temperature difference produces thermal e.m.f., displayed on the indicators
of the control board (L) and of the program TEGLab (O).
To test the thermoelectric generator at different temperatures, it is necessary to repeat items A-Q
for other temperature conditions.
Checking Thermal Resistance of Contact Layers
One of the challenges of effective use of a thermoelectric generator is taking into account thermal
losses in a particular design.
A thermoelectric generator efficiency (E) directly depends on the operating temperature difference
on its sides (∆Tw).
𝐸𝐸 = 𝛼𝛼 × ∆𝑇𝑇𝑤𝑤
Here α is the Seebeck coefficient per pair of elements (in average about 400 µV/°C); N is a number of
pairs of elements in the generator.
However, when the heat flux passing through the assembly with a thermoelectric generator, there
are several contact areas where the useful temperature drop is lost due to the heat resistance of
contact layers and materials.
In the Thermoelectric Generator Development Kit DX8130 a tested thermoelectric generator is
located between two controlled heat sources. Thus, there are two contact areas (top and bottom)
that have thermal resistance.
Полярность
напряжения
2
1
HOT
6
5
4
3
2
GEN
1
3
4
5
COLD
6
1
2
TEC1
FLUX1
T1
XP1
∆T
T2
δT
∆Tw
δT
FLUX2
TEC2
∆𝑇𝑇 = δ𝑇𝑇 + ∆𝑇𝑇𝑤𝑤 + δ𝑇𝑇
To decrease the temperature losses (δT) special conductive layers are applied (3M™ Thermally
Conductive Silicone Interface Pads 5519 0.5mm).
Nevertheless, the loss of temperature difference should be taken into account.
Release 1.0
Page 27 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
A. Repeat the actions of the items A-Q of the Section
"Checking Thermoelectric Generator Operation".
The exemplary temperature values set on the temperature
indicators of the hot and cold sides are 25 and 45°С,
respectively.
∆T
∆Tw
B. For the tested thermoelectric generator with the number of pairs of elements 127, the estimated
value of the operating temperature difference providing generation of working thermal e.m.f. is
11.6 °C.
Therefore:
-
∆T=20 °С (=45-25°С)
-
∆Tw=11.6°С
-
2 x dT=8.4 °С (20-11.6°С)
-
δT=4.2°С.
The heat flux that passed through the generator and measured by the bottom heat source sensor
is Q=2.09 W.
The thermal resistance of the contact layer is:
𝑅𝑅𝑡𝑡 =
δ𝑇𝑇
𝑄𝑄
=
4.2
≈ 2 𝐾𝐾/𝑊𝑊
2.09
The thermal resistance of the thermoelectric generator is:
𝑅𝑅𝑇𝑇𝑇𝑇𝑇𝑇 =
∆𝑇𝑇𝑊𝑊 11.6
=
≈ 5.6 𝐾𝐾/𝑊𝑊
𝑄𝑄
2.09
C. Generally the thermal resistance has temperature dependence.
Check the thermal resistance in other temperature conditions, as described below.
D. Repeat actions of items A-Q of the Section "Checking Thermoelectric Generator Operation" but
with other temperatures of the top and bottom heat sources. For example:
-
Thot=50°C
-
Tcold=20°C
-
∆T=30°C
Release 1.0
Page 28 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
E. After temperature stabilizing, the generator thermal e.m.f.
power reaches a stationary value.
F. Repeat the calculations of the item B.
-
∆T=30 °C (=50-20°C)
-
∆Tw=17.7°C
-
2 x δT=12.3 °C(=30-17.7°C)
-
δT=6.15 °C
The heat flux that passed through the generator and measured by the bottom heat source sensor
is Q=3.503 W.
The thermal resistance of one contact layer is
𝑅𝑅𝑡𝑡 =
δ𝑇𝑇
𝑄𝑄
=
6.15
≈ 1,76 𝐾𝐾/𝑊𝑊
3.503
The thermal resistance of the thermoelectric generator is:
𝑅𝑅𝑇𝑇𝑇𝑇𝑇𝑇 =
∆𝑇𝑇𝑊𝑊
17.7
=
≈ 5.05 𝐾𝐾/𝑊𝑊
𝑄𝑄
3.503
G. By measuring the thermal resistance under various temperatures, we can plot the thermal
resistance dependence on the temperature difference.
Rt, K/Wt
The figure shows an example measured for one of the microgenerators from the supplied kit
(1MD06-127-08TEG).
5,0
4,5
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
RTEG
Rt
10
20
30
40
50
∆T, K
Release 1.0
Page 29 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
Current-Voltage Characteristic of Thermoelectric Generator
A. Repeat the actions of the items A-Q of the Section
"Checking Thermoelectric Generator Operation".
B. Set the range of workloads by the button Low/High.
- In the case "High" the load will be set in the range of
current – 0…100 mA
- In the case "Low" the load will be set in the range of
current – 0…5 mA.
C. Set the following parameters of the current-voltage
characteristic (CVC):
- value of stabilization time before the measurement,
- number of points on the current-voltage characteristic
Or use the software defaults (2 seconds and 10 points).
The switch "GEN-LOAD" must be in the position "GEN"measuring current-voltage characteristic of the generator.
Choose the connection of the load to the generator by the
switches on the board: the top switch - down; the bottom
switch - up.
D. Press the button "GO". The current-voltage characteristic window will appear and the real-time
CVC will start plotting: on the X axis - the generator voltage, on the Y axis – the load current.
Example of CVC at high current
Release 1.0
Page 30 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
Example of CVC at small loads
Checking the Circuit of Thermoelectric Generator with DC/DC converter
Prepare the Thermoelectric Generator Development Kit DX8130 to work in accordance with the
instructions "Getting Ready".
As an example, a thermoelectric generator module is installed from the supplied kit - 1MD06-127-08.
The specification for this type is available on RMT's site http://www.rmtltd.ru/datasheets/Thermoelectric_Generators/1md06127_teg.pdf.
A. The board of the DC/DC converter BQ25504RGT (Texas
Instruments) is mounted and connected on the test bench.
Schemes of the boards with converters are given in the
Section "Boards of DC/DC Converters".
In the delivery kit there is also a board with the converter
LTC3108EGN (Linear Technology).
If it is necessary to replace the converter, use the
instructions in Section "Connection/replacement of DC/DC
converter board".
B. Turn the switch of the group GEN in the "up" position.
Turn the switch of the group LOAD in the "down" position.
C. Thus, the connection "Generator to DC/DC converter and
internal load" is done (Table 1).
Release 1.0
Page 31 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
D. Press the button "Set" of the group "HOT".
E. The temperature indicator flashing will start showing the
preset temperature of the top heat source.
F. The setting can be changed by the arrows up/down.
After setting the desired temperature, press "Set".
G. The temperature
temperature.
indicator
shows
the
current
The index "H" (Hold) before temperature readings indicates
that the heat source is turned off.
H. Switch on the heat source "1/0".
The index "H" disappears. The temperature indicator shows
the actual temperature reaching the desired value.
Temperature steadying takes time - a few minutes.
Release 1.0
Page 32 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
I. Repeat the same procedure of bottom heat source
temperature setting by the group "COLD" – see items B-F for
the bottom heat source "COLD".
Press the button "Set" of the "HOT".
J. The temperature indicator flashing will start showing the
preset temperature of the bottom heat source.
The setting can be changed by the arrows up/down.
After setting the desired temperature, press "Set".
K. The temperature indicator shows the current temperature.
The index "H" (Hold) before temperature readings indicates
that the heat source is turned off.
L. Switch on the heat source "1/0".
The index "H" disappears. The temperature indicator shows
the actual temperature reaching the desired value.
Temperature steadying takes time - a few minutes.
M. Wait for the temperature values of both heat sources
achieving the steady state.
The overall temperature difference is the difference of the
top and bottom steady-state temperatures.
In the case shown ∆T=45°C - 25°C=20°C.
Release 1.0
Page 33 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
N. In the steady state the heat flux indicator of the group
"COLD" displays the heat flux through the sample
thermoelectric generator.
The voltage indicator of the group "GEN" shows the thermal
e.m.f. of tested the thermoelectric generator under these
conditions (at the temperature difference given).
Q
E
O. The group LOAD indicator shows the standard voltage at the
output of the DC/DC converter board.
The voltage 4.0 V indicates that the converter is in the
operational mode. The input voltage from the
thermoelectric generator made the converter start up and
get the standard voltage (for charging an accumulator or
supercapacitor).
More information on the system operation is displayed in
the main window of the running software TEGLab.
P. To control the Development Kit by your computer, click on
the button "Local".
Q. The additional control elements are open.
The button switches to the status "PC Mode" meaning
control of the advanced settings from the computer (see
below).
R. The indications of the indicators in the program repeat
those of the indicators on the control board.
However, there are some differences.
The values of the heat flux indicators on the board are
limited to one digit of integer. Therefore, the maximum
displayed value is 9.999. The corresponding indicator in the
program TEGLab is free of this drawback and shows the true
value even if it exceeds 9.999. The program also indicates a
sign (direction) of the hat flux.
Release 1.0
Page 34 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
S. The software also enables calculating operating
temperature difference on the sides of the generator ∆Tw.
For that, it is necessary:
- Press the button "N="
- Specify the number of pairs of elements of the generator
tested.
- "ОК".
S. By the approximate value of thermal e.m.f. per elements
pair, the program calculates and displays the value of the
working temperature difference ∆Tw on the generator. This
value is always less than the total temperature difference
∆T.
The difference (∆T-∆Tw) is thermal loss on the interfaces –
contacts of the heat sources with the tested generator.
T. In the example above (A-Q) the operation of the thermoelectric generator with DC/DC converter is
checked at given top and bottom temperatures.
The generator at a given temperature difference produces thermal e.m.f., displayed on the indicators
of the control board (L) and of the program TEGLab (O).
To test the thermoelectric generator at different temperatures, it is necessary to repeat items A-Q
for other temperature conditions.
Current-Voltage Characteristic of the Circuit of Thermoelectric Generator with DC/DC
Converter
E. Repeat the actions of the items A-Q of the Section
"Checking the Circuit of Thermoelectric Generator with
DC/DC converter".
Release 1.0
Page 35 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
F. Set the range of workloads by the button Low/High.
- In the case "High" the load will be set in the range of
current – 0…90 mA
- In the case "Low" the load will be set in the range of
current – 0…5 mA
G. Set the following parameters of the current-voltage
characteristic (CVC):
- value of stabilization time before the measurement,
- number of points on the current-voltage characteristic
Or use the software defaults (2 seconds and 10 points).
The switch must be in the position "LOAD"- measuring
current-voltage characteristic of the generator. Choose the
connection of the load to the generator by the switches on
the board: the top switch - up; the top switch – down.
H. Press the button "GO". The current-voltage characteristic window will appear and the real-time
CVC will start plotting: on the X axis - the DC/DC converter voltage, on the Y axis – the load
current.
Example of CVC of DC/DC converter
The CVC of DC/DC converter has a characteristic threshold appearance:
- From the zero load up to a certain threshold current (in the example 4 mA), the converter voltage
is a fixed operational value 4.0V.
- By increasing the voltage above the threshold, the signal from the thermoelectric generator is not
enough for the DC/DC converter stable operation, and the output voltage sharply drops.
Thus, in this example, the selected operating conditions of the thermoelectric generator (Thot = 45 °C,
Release 1.0
Page 36 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
Tcold = 25 °C and at the operating temperature difference ∆Tw=11,7 °C) the maximum output power
of the device is 16 mW (= 4 mA x 4 V).
Connection/replacement of DC/DC converter board
In the Thermoelectric Generator Development Kit the
pre-installed DC/DC converter board is located in the
lower right corner of the test bench.
It is one of the two boards of the Kit (Section "Delivery
Kit").
The procedure for replacing a board of the DC/DC
converter is the following.
A.
Before connecting/replacing the DC/DC
converter board, make sure that the control board
is switched off. The toggle switch is in the "off"
position.
B. Use a screwdriver to release the wires "IN" and
"OUT" from the terminal on the board of the
DC/DC converter.
C. Using a wrench, unscrew the screws fixing the
board to the test bench. Remove the board.
Release 1.0
Page 37 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
D. Place another board of the DC/DC converter on
the seat.
E. Tighten the mounting screws.
F. Connect respectively: the wires "IN" to the
input of the DC/DC converter, the wires "OUT"
to the output of the DC/DC converter.
Observe the polarity markings on the
board and the color of the wires (red - "+").
Checking Load Capacity of Thermoelectric Generator
In the section "Checking Serviceability of Thermoelectric Generator Circuit" it is only the ability of the
thermoelectric generator to generate thermoelectric power for a given temperature difference that is
checked.
The generator can perform useful work if there is a load connected.
In this section, the load capacity of the thermoelectric generator is checked.
A. Repeat fully the procedure of checking the thermoelectric
generator ("Checking Serviceability of Thermoelectric
Generator Circuit ") items A-Q.
∆T
∆Tw
B. Turn the switch of the group GEN to the position "down".
C. Turn the switch of the group LOAD to the position "up".
Thus, the commutation "Generator to internal load" is
provided (Section "Wiring Diagram", Table 1)
Release 1.0
Page 38 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
D. In the main window of the software TEGLab set the load
switch in the position High or Low:
-
In case "High" the load is set in the range of currents –
0…100 mA
-
In case "Low" load is set in the range of currents – 0…5
mA.
E. By the slider set the load as a percentage of the
maximum value for the range given, using the readings
in %.
F. The operational load current and the corresponding
value of the input load voltage will be displayed in the
group of indicators GEN.
It will be seen that with increasing load (electric current)
voltage decreases. It is the behavior of the generator
current-voltage characteristics (see the Section
"Current-Voltage Characteristic of Thermoelectric
Generator").
G. It is also useful to calculate the generator efficiency.
This value is given in the main window of the software.
The value of efficiency at a steady temperature
difference (Thot and Tcold) is calculated as:
𝑄𝑄
%
𝑈𝑈 × 𝐼𝐼
Here Q is the value given by the heat flux indicator of
the group COLD, U and I are the readings of the
indicators of the group GEN.
𝑛𝑛 =
Checking Load Capacity of Circuit of Thermoelectric Generator with DC/DC Converter
In the section "Checking Circuit of Thermoelectric Generator with DC/DC Converter" we only check the
thermoelectric generator ability to generate thermal Electromotive Force for a given temperature
difference.
The generator circuit can carry out useful work only in case the current is supplied to the output DC/DC
Release 1.0
Page 39 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
converter load connected.
In this section the load capacity of the thermoelectric generator circuit with DC/DC converter is checked.
H. Repeat the full procedure of checking thermoelectric
generator (see "Checking Circuit of Thermoelectric
Generator with DC/DC Converter"), items A-T.
I. Turn the switch of the group GEN to the position "up".
J. Turn the switch of the group LOAD to the position "down".
Thus, the commutation "Generator to DC/DC converter and
internal load" is done (Section "Wiring Diagram", Table 1).
K. In the main window of the software TEGLab click the load
switch in the position Low.
L. By the slider set the load as a percentage of the maximum
value for the range given, using the readings in %.
Release 1.0
Page 40 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
M. The operational load current and the corresponding value of
the input load voltage will be displayed in the group of
indicators LOAD.
It will be seen that up to a certain load current (for given
temperature conditions) the DC/DC converter provides
stable voltage supply. However, above a certain threshold,
the voltage drops sharply. The DC/DC converter is out of the
operating mode.
∆T
∆Tw
It is the behavior of the generator current-voltage
characteristic
(see
the
Section
"Current-Voltage
Characteristic of Thermoelectric Generator with Dc/DC
converter").
N. It is also useful to calculate the generator efficiency.
This value is given in the main window of the software.
∆T
The value of efficiency at a steady temperature difference
(Thot and Tcold) is calculated as:
𝑄𝑄
%
𝑈𝑈 × 𝐼𝐼
Here Q is the value given by the heat flux indicator of the
group COLD, U and I are the readings of the indicators of the
group GEN.
𝑛𝑛 =
O. The value of DC/DC converter efficiency can be estimated
additionally. This value is also displayed in the main window.
The DC/DC converter efficiency is calculated as:
𝑛𝑛𝐷𝐷𝐷𝐷/𝐷𝐷𝐷𝐷 =
𝑈𝑈𝐺𝐺𝐺𝐺𝐺𝐺 × 𝐼𝐼𝐺𝐺𝐺𝐺𝐺𝐺
%
𝑈𝑈𝐿𝐿𝐿𝐿𝐿𝐿𝐿𝐿 × 𝐼𝐼𝐿𝐿𝐿𝐿𝐿𝐿𝐿𝐿
Here in the numerator of the fraction there are current and
voltage at the input of the converter (from the generator).
In the denominator there are current and voltage on the
load (output of the DC/DC converter).
Release 1.0
∆Tw
∆T
∆Tw
Page 41 of 42
THERMOELECTRIC GENERATOR DEVELOPMENT KIT DX8130
WARRANTY
RMT Ltd. ensures that the delivered product is free from defects. The warranty period is 1 year.
RMT Ltd. also provides a 3-month warranty for the following parts and components, if included in the
standard delivery set of the product: cables, software disks and documentation.
If the product fails during the warranty period, RMT shall repair or replace it or its parts.
For the warranty support a Consumer can address to the office of the company RMT or its sales
representative. An immediate assistance shall be provided.
The product either repaired or replaced in whole or in part, will keep the warranty period from its
start but not less than 3 months.
TECHNICAL SUPPORT
For the technical support and repair within and after the warranty period, please, address to the
office of the company RMT Ltd. or its sales representatives:
In Russia and CIS
RMT Ltd.
46 Warshavskoe shosse, Moscow 115230, Russia
Phone: +7-499-678-2082
Fax:
+7-499-678-2083
e-mail: [email protected]
In Europe, the USA and other countries
TEC Microsystems GmbH
Schwarzschildstrasse 8, Berlin 12489, Germany
Phone: +49-(0)30-6789-3314
Fax:
+49-(0)30-6789-3315
e-mail: [email protected]
RMT Ltd.
46 Warshavskoe shosse. Moscow 115230 Russia
phones: +7-499-678-20-82
fax: +7-499-678-20-83
e-mail: [email protected]
Copyright © 2015 RMT Ltd.
Release 1.0
Page 42 of 42