※ History List Version Date Update Information 1.0 ’15.03.30 - 2015 New EHS Mono TDB Released. (Except SCOP / ESEER) 1.1 ‘15.04.06 - Add SCOP / ESEER 1.2 ’15.04.10 - Modify Capacity Table 1.3 ‘15.06.19 1.4 ’15.06.22 - Add 5kW Model / Control KIT (E03BN) - Modify : Change the Note for Refrigerant - Modify Product Gross for 5kW Model - Modify : Piping Diagram / Operating Range for DHW EHS Technical Data Book EHS Mono for Europe Model : AE***JXYDEH/EU AE***JXYDGH/EU I. Products 1. Nomenclature 2. Line-up II. Specifications 1. Specification 2. Capacity Tables 3. Dimensional Drawings 4. Piping Diagrams 5. Wiring Diagrams 6. Electric Specifications 7. Sound Pressure Level 8. Operation Range 9. Hydraulic Performance III. Application 1. Application Example I. Products 1. Nomenclature 2. Line-up EHS Mono I. Products 1. Nomenclature 1-1. Outdoor Unit Model Name (New) AE 090 J X Y D E H (1) (2) (3) (4) (5) (6) (7) (8) (1) Classification AE EHS (Buyer) Mono (Outdoor Unit) (6) Feature 1 x 1/10 kW (3 digits) (3) Version J EU (5) Type Y (2) Capacity / 2015 (4) Product Type N Indoor X Outdoor D DELUXE (Basic) (7) Rating Voltage E 1Φ, 220~240V, 50Hz G 3Φ, 380~415V, 50Hz (8) Mode H Heat Pump R410A 3 EHS Mono I. Products 2. Line-up 2-1. Outdoor Unit Mono Type Capacity (kW) 5.0 9.0 12.0 14.0 16.0 AE050JXYDEH AE090JXYDEH AE120JXYDEH AE140JXYDEH AE160JXYDEH AE090JXYDGH AE120JXYDGH AE140JXYDGH AE160JXYDGH 1 Phase 3 Phases N/A 2-2. Control Kit Control Unit MIM-E03A(B)N 4 II. Specifications 1. Specifications 2. Capacity Tables 3. Dimensional Drawings 4. Piping Diagrams 5. Wiring Diagrams 6. Electric Specifications 7. Sound Pressure Level 8. Operation Range 9. Hydraulic Performance EHS Mono II. Specifications 1. Specifications 1-1. Outdoor Unit Type Model Name Outdoor Unit Mode Heating Nominal Capacity Cooling Performance (A7/W35) *1 Power Input (Nominal) Heating Current Input (Nominal) Heating Cooling Cooling 30,700 40,900 W 5,000 7,500 12,000 Btu/h 17,100 25,600 40,900 1,060 2,140 2,660 1,210 1,950 3,160 5,1 9.2 12 5,7 9 14.3 4.51 W A 3.80 SCOP(35℃) - 4.50 4.41 4.46 - 5.29 5.07 4.98 Heating W 4,500 7,000 9,800 - 3.46 3.00 3.32 Heating W 4,700 7,600 10,300 COP - 2.69 2.39 2.61 MCA A 20 22 28 MFA Water Flow Rate (Heating/Cooling) Water Pressure (Max) A 25 27.5 35 LPM 14.5/14.5 26/22 35/35 COP Water Pipe bar 3 3 3 Inlet Φ, inch BSPP male 1" BSPP male 1" BSPP male 1" Outlet Φ, inch BSPP male 1" BSPP male 1" BSPP male 1" Heating °C 25~55 25~55 25~55 Cooling °C 5~25 5~25 5~25 Type - R410A R410A R410A Control Method - EEV INCLUDED EEV INCLUDED EEV INCLUDED g 1,150 1,400 2,600 V, Hz, Φ 220~240V, 50Hz, 1Ф 220~240V, 50Hz, 1Ф 220~240V, 50Hz, 1Ф Type - BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary Model - UG4TH200FUAE4 UG8TH8265FJW UG5T450FU Oil - POE POE PVE CMM 51 53 108 l/s 850 883 1800 Air Flow Rate Cooling Number of Unit EA 1 1 2 W N/A 150 150 Heating dB(A) 45 48 50 Cooling dB(A) 45 48 50 Heating dB 61 63 64 Cooling dB 62 64 65 kg 59.0 76.0 108.0 Base Heater Sound Pressure Sound*4 Sound Power Net Weight Operating Temp. Range 17,100 4.21 Factory Charging External Dimension 12,000 Btu/h 3.85 Power Supply Outdoor Unit 9,000 4,13 Leaving Water Temperature Fan Heat Pump (A2W) 5,000 4,72 Capacity Compressor Heat Pump (A2W) - Performance (A-7/W35) *3 Refrigerant Heat Pump (A2W) W - Capacity Water Connections Mono AE120JXYDEH/EU COP (Nominal Heating) Performance (A2/W35) *2 Field Wiring Mono AE090JXYDEH/EU EER (Nominal Cooling) ESEER System Mono AE050JXYDEH/EU Shipping Weight kg 63.0 84.0 118.0 Net Dimensions (WxHxD) mm 880 x 798 x 310 940 x 998 x 330 940 x 1,420 x 330 Shipping Dimensions (WxHxD) mm 1023 x 911 x 413 995 x 1,178 x 426 995 x 1,598 x 426 Heating*5 ℃ -25~35 -25~35 -25~35 Cooling ℃ 10~46 10~46 10~46 DHW Tank*6 ℃ -25~43 -25~43 -25~43 *1) A2W Condition #1 : (Heating) Water In/Out 30°C/35°C, Outdoor Air DB/WB 7°C/6°C; (Cooling) Water In/Out 23°C/18°C, Outdoor Air DB 35°C. *2) A2W Condition #2 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB 2°C/1°C *3) A2W Condition #3 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB -7°C/-8°C *4) Sound Pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. *5) At the temperature -25°C ~ -20°C, operation is available but capacity cannot be guaranteed. *6) Heat pump operating range of DHW : -25°C ~ 35°C. 7) These products contain R410A which is fluorinated greenhouse gas. 6 EHS Mono II. Specifications 1. Specifications 1-1. Outdoor Unit Type Model Name Outdoor Unit Mode Heating Nominal Capacity Cooling Performance (A7/W35) *1 Power Input (Nominal) Heating Current Input (Nominal) Heating Cooling Cooling System Mono AE090JXYDGH/EU Heat Pump (A2W) - Heat Pump (A2W) Heat Pump (A2W) W 14,000 16,000 9,000 Btu/h 47,800 54,600 30,700 W 13,000 14,000 7,000 Btu/h 44,300 47,800 23,900 3,140 3,800 2,140 3,500 3,840 1,920 14.3 17.1 3.5 15.7 17.3 3.2 4.21 W A COP (Nominal Heating) - 4.46 4.21 - 3.71 3.65 3.65 SCOP(35℃) - 4.43 4.41 4.41 Capacity - 4.97 4.92 4.69 Heating W 11,200 12,500 7,000 - 3.26 3.10 3.00 Heating W 10,800 13,400 7,600 2.39 COP Performance (A-7/W35) *3 Capacity COP - 2.56 2.47 Field Wiring MCA A 30 32 10 MFA Water Flow Rate (Heating/Cooling) Water Pressure (Max) A 37.5 40 16.1 LPM 40/37 46/40 26/21 Water Connections Water Pipe Leaving Water Temperature Refrigerant bar 3 3 3 Inlet Φ, inch BSPP male 1" BSPP male 1" BSPP male 1" Outlet Φ, inch BSPP male 1" BSPP male 1" BSPP male 1" Heating °C 25~55 25~55 25~55 Cooling °C 5~25 5~25 5~25 Type - R410A R410A R410A Control Method - EEV INCLUDED EEV INCLUDED EEV INCLUDED Factory Charging g 2,600 2,600 1,500 V, Hz, Φ 220~240V, 50Hz, 1Ф 220~240V, 50Hz, 1Ф 380~415V, 50Hz, 3Ф Type - BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary Model - UG5T450FU UG5T450FU UG8T300FUCJU Oil - PVE PVE PVE CMM 108 108 53 l/s 1800 1800 883 Power Supply Compressor Fan Air Flow Rate Cooling Number of Unit EA 2 2 1 W 150 150 150 Heating dB(A) 51 52 48 Cooling dB(A) 52 54 48 Heating dB 65 66 63 Cooling dB 66 69 64 kg 108.0 108.0 76.0 Base Heater Outdoor Unit Mono AE160JXYDEH/EU EER (Nominal Cooling) ESEER Performance (A2/W35) *2 Mono AE140JXYDEH/EU Sound Pressure Sound*4 Sound Power Net Weight External Dimension Operating Temp. Range Shipping Weight kg 118.0 118.0 84.0 Net Dimensions (WxHxD) mm 940 x 1,420 x 330 940 x 1,420 x 330 940 x 998 x 330 Shipping Dimensions (WxHxD) mm 995 x 1,598 x 426 995 x 1,598 x 426 995 x 1,178 x 426 Heating*5 ℃ -25~35 -25~35 -25~35 Cooling ℃ 10~46 10~46 10~46 DHW Tank*6 ℃ -25~43 -25~43 -25~43 *1) A2W Condition #1 : (Heating) Water In/Out 30°C/35°C, Outdoor Air DB/WB 7°C/6°C; (Cooling) Water In/Out 23°C/18°C, Outdoor Air DB 35°C. *2) A2W Condition #2 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB 2°C/1°C *3) A2W Condition #3 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB -7°C/-8°C *4) Sound Pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. *5) At the temperature -25°C ~ -20°C, operation is available but capacity cannot be guaranteed. *6) Heat pump operating range of DHW : -25°C ~ 35°C. 7) These products contain R410A which is fluorinated greenhouse gas. 7 EHS Mono II. Specifications 1. Specifications 1-1. Outdoor Unit Type Model Name Outdoor Unit Mode Heating Nominal Capacity Cooling Performance (A7/W35) *1 Power Input (Nominal) Heating Current Input (Nominal) Heating Cooling Cooling System Mono AE160JXYDGH/EU Heat Pump (A2W) - Heat Pump (A2W) Heat Pump (A2W) W 12,000 14,000 16,000 Btu/h 40,900 47,800 54,600 W 12,000 13,000 14,000 Btu/h 40,900 44,300 47,800 2,660 3,140 3,800 3,160 3,500 3,840 4.2 4.8 5.7 5.2 5.3 5.8 4.21 W A COP (Nominal Heating) - 4.51 4.46 - 3.80 3.71 3.65 SCOP(35℃) - 4.46 4.43 4.41 Capacity - 4.98 4.97 4.92 Heating W 9,800 11,200 12,500 - 3.32 3.26 3.10 Heating W 10,300 10,800 13,400 2.47 COP Performance (A-7/W35) *3 Capacity COP - 2.61 2.56 Field Wiring MCA A 10 12 12 MFA Water Flow Rate (Heating/Cooling) Water Pressure (Max) A 16.1 16.1 16.1 LPM 35/35 40/37 46/40 Water Connections Water Pipe Leaving Water Temperature Refrigerant bar 3 3 3 Inlet Φ, inch BSPP male 1" BSPP male 1" BSPP male 1" Outlet Φ, inch BSPP male 1" BSPP male 1" BSPP male 1" Heating °C 25~55 25~55 25~55 Cooling °C 5~25 5~25 5~25 Type - R410A R410A R410A Control Method - EEV INCLUDED EEV INCLUDED EEV INCLUDED Factory Charging g 2,600 2,600 2,600 V, Hz, Φ 380~415V, 50Hz, 3Ф 380~415V, 50Hz, 3Ф 380~415V, 50Hz, 3Ф Type - BLDC Twin Rotary BLDC Twin Rotary BLDC Twin Rotary Model - UG5T450FU UG5T450FU UG5T450FU Oil - PVE PVE PVE CMM 108 108 108 l/s 1800 1800 1800 Power Supply Compressor Fan Air Flow Rate Cooling Number of Unit EA 2 2 2 W 150 150 150 Heating dB(A) 50 51 52 Cooling dB(A) 50 52 54 Heating dB 64 65 66 Cooling dB 65 66 69 kg 108.0 108.0 108.0 Base Heater Outdoor Unit Mono AE140JXYDGH/EU EER (Nominal Cooling) ESEER Performance (A2/W35) *2 Mono AE120JXYDGH/EU Sound Pressure Sound*4 Sound Power Net Weight External Dimension Operating Temp. Range Shipping Weight kg 118.0 118.0 118.0 Net Dimensions (WxHxD) mm 940 x 1,420 x 330 940 x 1,420 x 330 940 x 1,420 x 330 Shipping Dimensions (WxHxD) mm 995 x 1,598 x 426 995 x 1,598 x 426 995 x 1,598 x 426 Heating*5 ℃ -25~35 -25~35 -25~35 Cooling ℃ 10~46 10~46 10~46 DHW Tank*6 ℃ -25~43 -25~43 -25~43 *1) A2W Condition #1 : (Heating) Water In/Out 30°C/35°C, Outdoor Air DB/WB 7°C/6°C; (Cooling) Water In/Out 23°C/18°C, Outdoor Air DB 35°C. *2) A2W Condition #2 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB 2°C/1°C *3) A2W Condition #3 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB -7°C/-8°C *4) Sound Pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions. *5) At the temperature -25°C ~ -20°C, operation is available but capacity cannot be guaranteed. *6) Heat pump operating range of DHW : -25°C ~ 35°C. 7) These products contain R410A which is fluorinated greenhouse gas. 8 EHS Mono II. Specifications 1. Specifications 1-2. Control Kit MIM-E03AN MIM-E03BN - 090/120/140/160 Model 050 Model Model Name Use with V, Hz, Φ 220~240V, 50Hz, 1Ф 220~240V, 50Hz, 1Ф Net kg 3.5 3.5 Gross kg 6.0 6.0 Net mm 370x110x290 370x110x290 Gross mm 439x168x329 439x168x329 Power Supply Weight External Dimension Flow Switch External Control Dimensions (WxHxD) LPM 16±1.5 7±1.5 Booster Heater Set Point (Min. flow rates) - AC 230V (Max 20A) AC 230V (Max 20A) Back up Heater (/Boiler) - AC 230V (Max 0.5A) AC 230V (Max 0.5A) Water Pump - AC 230V (Max 2A) AC 230V (Max 2A) 2way(or 3way) Valve - AC 230V (Max 0.5A / 120W) AC 230V (Max 0.5A / 120W) Room Thermostat - AC 230V (Max 10mA) AC 230V (Max 10mA) Solar Pump - AC 230V (Max 10mA) AC 230V (Max 10mA) Inverter Pump - AC 230V (Max 2A) (NEW) AC 230V (Max 2A) 3way Mixing Valve - AC 230V (Max 0.5A / 120W) (NEW) AC 230V (Max 0.5A / 120W) 9 EHS Mono II. Specifications 2. Capacity Tables 2-1. AE050/090/120/140/160JXYDEH/EU (1 Phase) 1) Maximum Heating Capacity (Peak Value) AE160JXYDEH/EU AE140JXYDEH/EU AE120JXYDEH/EU AE090JXYDEH/EU AE050JXYDEH/EU LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input) LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 30 HC(kW) 3.57 5.25 4.94 4.57 4.62 5.25 5.73 6.54 7.35 35 PI(kW) 1.47 1.78 1.69 1.20 1.04 0.94 0.95 0.97 0.98 HC(kW) 3.40 5.00 4.70 4.36 4.40 5.00 5.46 6.23 7.00 PI(kW) 2.67 3.03 2.87 2.43 2.10 1.90 1.90 1.90 1.89 HC(kW) 6.00 8.60 8.08 7.84 7.92 9.00 9.89 11.36 12.84 PI(kW) 4.09 4.09 3.89 3.02 2.60 2.37 2.35 2.31 2.28 HC(kW) 9.35 11.80 11.09 10.45 10.56 12.00 13.25 15.32 17.40 PI(kW) 4.36 4.63 4.40 3.57 3.07 2.79 2.79 2.77 2.76 HC(kW) 9.65 12.80 12.03 12.20 12.32 14.00 14.92 16.46 18.00 PI(kW) 5.30 5.43 5.16 4.32 3.72 3.38 3.42 3.49 3.56 HC(kW) 11.30 14.40 13.54 13.94 14.08 16.00 17.38 19.69 22.00 30 HC(kW) 6.30 9.03 8.49 8.23 8.32 9.45 10.38 11.93 13.48 HC(kW) 5.85 8.34 7.84 7.45 7.52 8.55 9.47 11.01 12.55 PI(kW) 4.60 4.60 4.37 3.39 2.93 2.66 2.64 2.60 2.56 HC(kW) 8.93 11.45 10.76 10.19 10.30 11.70 12.89 14.88 16.86 PI(kW) 4.90 5.20 4.94 4.01 3.45 3.14 3.13 3.12 3.10 HC(kW) 9.33 12.42 11.67 11.76 11.88 13.50 14.42 15.96 17.50 PI(kW) 5.95 6.10 5.80 4.85 4.18 3.80 3.85 3.92 4.00 HC(kW) 10.75 13.97 13.13 13.37 13.51 15.35 16.71 18.98 21.25 45 PI(kW) 1.75 2.10 2.00 1.54 1.33 1.21 1.22 1.21 1.24 HC(kW) 3.36 4.70 4.42 4.09 4.14 4.70 5.18 5.99 6.80 PI(kW) 3.20 3.59 3.41 2.89 2.49 2.27 2.29 2.30 2.35 HC(kW) 5.70 8.08 7.60 7.06 7.13 8.10 9.06 10.66 12.26 PI(kW) 4.90 5.14 4.88 3.90 3.36 3.06 3.02 2.92 2.88 HC(kW) 8.50 11.09 10.43 9.93 10.03 11.40 12.54 14.43 16.32 PI(kW) 5.20 5.59 5.31 4.52 3.90 3.55 3.52 3.41 3.38 HC(kW) 9.01 12.03 11.31 11.33 11.44 13.00 13.92 15.46 17.00 PI(kW) 6.25 6.67 6.34 5.36 4.62 4.20 4.25 4.26 4.36 HC(kW) 10.20 13.54 12.72 12.81 12.94 14.70 16.04 18.27 20.50 40 PI(kW) HC(kW) PI(kW) 4.56 4.20 3.89 3.93 4.60 4.93 5.69 6.46 2.32 2.36 1.94 1.67 1.48 1.53 1.55 1.58 4.23 3.98 3.69 3.72 4.50 4.67 5.39 6.12 2.54 2.62 2.15 1.86 1.60 1.70 1.73 1.75 PI(kW) 3.53 3.78 3.59 3.05 2.63 2.39 2.44 2.53 2.62 HC(kW) PI(kW) HC(kW) PI(kW) 7.84 7.22 6.70 6.77 8.05 8.61 10.13 11.65 3.97 4.04 3.43 2.96 2.68 2.75 2.85 2.95 7.28 6.84 6.35 6.42 8.00 8.15 9.59 11.03 4.35 4.49 3.81 3.29 2.96 3.05 3.16 3.27 PI(kW) 5.29 5.67 5.39 4.40 3.80 3.45 3.40 3.33 3.25 HC(kW) PI(kW) HC(kW) PI(kW) 10.76 9.91 9.44 9.53 10.95 11.91 13.71 15.50 5.95 6.06 4.95 4.27 3.68 3.83 3.74 3.66 9.98 9.38 8.94 9.03 10.50 11.28 12.98 14.69 6.52 6.73 5.50 4.74 3.90 4.25 4.16 4.06 PI(kW) 5.59 5.99 5.69 5.04 4.35 3.95 3.90 3.81 3.73 HC(kW) PI(kW) HC(kW) PI(kW) 11.67 10.74 10.76 10.87 12.63 13.23 14.69 16.15 6.28 6.40 5.67 4.89 4.20 4.39 4.29 4.20 10.83 10.18 10.19 10.30 12.25 12.53 13.92 15.30 6.88 7.11 6.30 5.43 4.45 4.87 4.77 4.66 PI(kW) 6.76 7.25 6.88 5.87 5.06 4.60 4.65 4.72 4.80 HC(kW) PI(kW) HC(kW) PI(kW) 13.13 12.09 12.17 12.29 14.60 15.24 17.36 19.48 7.61 7.74 6.60 5.69 5.00 5.23 5.31 5.40 12.18 11.45 11.53 11.64 14.50 14.43 16.44 18.45 8.33 8.60 7.34 6.33 5.40 5.81 5.90 6.00 50 55 50 45 40 55 HC(kW) 45 40 35 50 PI(kW) 2.06 2.21 2.09 1.72 1.49 1.35 1.36 1.38 1.40 45 40 35 30 HC(kW) 11.87 15.12 14.21 14.64 14.78 16.80 18.25 20.68 23.10 PI(kW) 3.00 3.40 3.23 2.73 2.35 2.14 2.14 2.13 2.12 35 30 HC(kW) 10.13 13.44 12.63 12.81 12.94 14.70 15.67 17.28 18.90 HC(kW) 3.38 4.85 4.56 4.23 4.27 4.85 5.32 6.11 6.90 35 30 HC(kW) 9.82 12.39 11.65 10.98 11.09 12.60 13.91 16.09 18.27 40 PI(kW) 1.65 2.00 1.90 1.35 1.17 1.06 1.07 1.08 1.10 55 50 45 55 50 55 1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C 2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C 3. Power input : Power input is according to Eurovent rating standard OM-3-2015. 4. Peak value : Tested without defrost operation in accordance with EN14511 5. Integrated value : Tested with defrost operation in accordance with EN14511 ※ The real capacity would be changed according to the install environment. 10 EHS Mono II. Specifications 2. Capacity Tables 2-1. AE050/090/120/140/160JXYDEH/EU (1 Phase) 2) Maximum Heating Capacity (Integrated Value) AE160JXYDEH/EU AE140JXYDEH/EU AE120JXYDEH/EU AE090JXYDEH/EU AE050JXYDEH/EU LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input) LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 30 HC(kW) 3.70 4.64 4.94 4.83 4.73 5.25 5.73 6.54 7.35 35 PI(kW) 1.50 1.54 1.56 1.36 1.16 0.94 0.95 0.97 0.98 HC(kW) 3.53 4.42 4.70 4.60 4.50 5.00 5.46 6.23 7.00 PI(kW) 2.72 2.80 2.83 2.45 2.07 1.90 1.90 1.90 1.89 HC(kW) 5.70 7.14 7.60 7.30 7.00 9.00 9.89 11.36 12.84 PI(kW) 3.37 3.48 3.52 3.07 2.63 2.37 2.35 2.31 2.28 HC(kW) 7.73 9.68 10.30 10.05 9.80 12.00 13.25 15.32 17.40 PI(kW) 3.61 3.72 3.76 3.41 3.06 2.79 2.79 2.77 2.76 HC(kW) 8.10 10.15 10.80 11.00 11.20 14.00 14.92 16.46 18.00 PI(kW) 4.63 4.78 4.82 4.21 3.59 3.38 3.42 3.49 3.56 HC(kW) 10.05 12.60 13.40 12.95 12.50 16.00 17.38 19.69 22.00 30 HC(kW) 5.99 7.50 7.98 7.67 7.35 9.45 10.38 11.93 13.48 HC(kW) 5.53 6.93 7.38 7.06 6.75 8.55 9.47 11.01 12.55 PI(kW) 3.79 3.91 3.95 3.45 2.95 2.66 2.64 2.60 2.56 HC(kW) 7.38 9.25 9.85 9.87 9.90 11.70 12.89 14.88 16.86 PI(kW) 4.05 4.18 4.22 3.83 3.44 3.14 3.13 3.12 3.10 HC(kW) 8.06 10.11 10.75 10.96 11.18 13.50 14.42 15.96 17.50 PI(kW) 5.20 5.37 5.42 4.73 4.03 3.80 3.85 3.92 4.00 HC(kW) 10.09 12.64 13.45 12.49 11.53 15.35 16.71 18.98 21.25 45 PI(kW) 1.90 1.96 1.98 1.68 1.38 1.21 1.22 1.21 1.24 HC(kW) 3.38 4.23 4.50 4.25 4.00 4.70 5.18 5.99 6.80 PI(kW) 3.21 3.31 3.34 2.90 2.47 2.27 2.29 2.30 2.35 HC(kW) 5.36 6.72 7.15 6.83 6.50 8.10 9.06 10.66 12.26 PI(kW) 4.17 4.30 4.34 3.86 3.38 3.06 3.02 2.92 2.88 HC(kW) 7.04 8.83 9.39 9.70 10.00 11.40 12.54 14.43 16.32 PI(kW) 4.75 4.89 4.94 4.45 3.97 3.55 3.52 3.41 3.38 HC(kW) 8.03 10.06 10.70 10.93 11.15 13.00 13.92 15.46 17.00 PI(kW) 5.88 6.05 6.11 5.13 4.15 4.20 4.25 4.26 4.36 HC(kW) 10.13 12.69 13.50 12.03 10.55 14.70 16.04 18.27 20.50 40 PI(kW) HC(kW) PI(kW) 4.02 4.60 4.04 3.80 4.60 4.93 5.69 6.46 2.45 2.40 2.05 1.63 1.48 1.53 1.55 1.58 3.81 4.70 3.83 3.60 4.50 4.67 5.39 6.12 2.72 2.60 2.28 1.81 1.60 1.70 1.73 1.75 PI(kW) 3.36 3.47 3.50 3.05 2.60 2.39 2.44 2.53 2.62 HC(kW) PI(kW) HC(kW) PI(kW) 6.38 6.53 6.48 6.18 8.05 8.61 10.13 11.65 3.90 3.60 3.43 2.93 2.68 2.75 2.85 2.95 6.05 5.90 6.14 5.85 8.00 8.15 9.59 11.03 4.33 3.70 3.81 3.25 2.96 3.05 3.16 3.27 PI(kW) 4.54 4.68 4.73 4.27 3.80 3.45 3.40 3.33 3.25 HC(kW) PI(kW) HC(kW) PI(kW) 8.39 8.93 9.21 9.50 10.95 11.91 13.71 15.50 5.27 5.12 4.80 4.28 3.68 3.83 3.74 3.66 7.94 8.47 8.73 9.00 10.50 11.28 12.98 14.69 5.85 5.51 5.33 4.75 3.90 4.25 4.16 4.06 PI(kW) 5.42 5.59 5.65 5.08 4.50 3.95 3.90 3.81 3.73 HC(kW) PI(kW) HC(kW) PI(kW) 9.56 10.35 10.38 10.59 12.63 13.23 14.69 16.15 6.29 5.78 5.71 5.06 4.20 4.39 4.29 4.20 9.05 10.00 9.83 10.04 12.25 12.53 13.92 15.30 6.99 5.90 6.34 5.63 4.45 4.87 4.77 4.66 PI(kW) 6.53 6.73 6.80 5.54 4.27 4.60 4.65 4.72 4.80 HC(kW) PI(kW) HC(kW) PI(kW) 12.06 12.65 11.42 10.02 14.60 15.24 17.36 19.48 7.57 6.90 6.23 4.80 5.00 5.23 5.31 5.40 11.42 11.80 10.82 9.50 14.50 14.43 16.44 18.45 8.42 7.00 6.92 5.34 5.40 5.81 5.90 6.00 50 55 50 45 40 55 HC(kW) 45 40 35 50 PI(kW) 2.11 2.18 2.20 1.83 1.45 1.35 1.36 1.38 1.40 45 40 35 30 HC(kW) 10.55 13.23 14.07 13.60 13.13 16.80 18.25 20.68 23.10 PI(kW) 3.05 3.15 3.18 2.76 2.33 2.14 2.14 2.13 2.12 35 30 HC(kW) 8.51 10.66 11.34 11.55 11.76 14.70 15.67 17.28 18.90 HC(kW) 3.45 4.32 4.60 4.43 4.25 4.85 5.32 6.11 6.90 35 30 HC(kW) 8.11 10.17 10.82 10.55 10.29 12.60 13.91 16.09 18.27 40 PI(kW) 1.68 1.73 1.75 1.53 1.30 1.06 1.07 1.08 1.10 55 50 45 55 50 55 1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C 2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C 3. Power input : Power input is according to Eurovent rating standard OM-3-2015. 4. Peak value : Tested without defrost operation in accordance with EN14511 5. Integrated value : Tested with defrost operation in accordance with EN14511 ※ The real capacity would be changed according to the install environment. 11 EHS Mono II. Specifications 2. Capacity Tables 2-1. AE050/090/120/140/160JXYDEH/EU (1 Phase) 3) Maximum Cooling Capacity AE160JXYDEH/EU AE140JXYDEH/EU AE120JXYDEH/EU AE090JXYDEH/EU AE050JXYDEH/EU LWT (Leaving Water Temp.), Tamb (Ambient Temp.), CC (Cooling Capacity), PI (Power input) LWE(℃) 7 10 13 15 18 25 Tamb(℃) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) 10 4.21 0.90 4.54 0.90 4.87 0.90 5.20 0.90 5.54 0.90 6.09 0.92 20 4.05 1.02 4.37 1.02 4.69 1.02 5.01 1.02 5.33 1.02 5.86 1.04 30 3.88 1.14 4.19 1.14 4.50 1.14 4.80 1.14 5.11 1.14 5.62 1.17 35 3.80 1.21 4.10 1.21 4.40 1.21 4.70 1.21 5.00 1.21 5.50 1.23 46 3.62 1.34 3.91 1.34 4.19 1.34 4.48 1.34 4.77 1.34 5.24 1.36 LWE(℃) 7 10 13 15 18 25 Tamb(℃) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) 10 6.09 1.39 6.64 1.41 7.18 1.44 7.55 1.46 8.09 1.49 8.82 1.52 20 5.86 1.57 6.40 1.60 6.95 1.63 7.31 1.65 7.86 1.67 8.58 1.71 30 5.62 1.76 6.16 1.78 6.71 1.81 7.07 1.83 7.62 1.86 8.35 1.89 35 5.50 1.85 6.05 1.88 6.59 1.90 6.95 1.92 7.50 1.95 8.23 1.99 46 5.24 2.05 5.78 2.08 6.33 2.11 6.69 2.13 7.24 2.15 7.97 2.19 LWE(℃) 7 10 13 15 18 25 Tamb(℃) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) 10 9.97 2.37 10.79 2.37 11.61 2.37 12.15 2.37 12.97 2.37 14.06 2.37 20 9.58 2.69 10.40 2.69 11.22 2.69 11.77 2.69 12.58 2.69 13.67 2.69 30 9.19 3.00 10.01 3.00 10.83 3.00 11.38 3.00 12.19 3.00 13.29 3.00 35 9.00 3.16 9.82 3.16 10.64 3.16 11.18 3.16 12.00 3.16 13.09 3.16 46 8.57 3.51 9.39 3.51 10.21 3.51 10.75 3.51 11.57 3.51 12.66 3.51 LWE(℃) 7 10 13 15 18 25 Tamb(℃) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) 10 10.76 2.62 11.66 2.63 12.56 2.64 13.16 2.65 14.06 2.67 15.26 2.68 20 10.33 2.95 11.23 2.96 12.13 2.98 12.73 2.99 13.63 3.00 14.83 3.02 30 9.91 3.28 10.81 3.30 11.71 3.31 12.31 3.32 13.21 3.33 14.41 3.35 35 9.70 3.45 10.60 3.46 11.50 3.48 12.10 3.49 13.00 3.50 14.20 3.52 46 9.24 3.82 10.14 3.83 11.04 3.84 11.64 3.85 12.54 3.87 13.74 3.89 LWE(℃) 7 10 13 15 18 25 Tamb(℃) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) 10 11.54 2.85 12.52 2.88 13.50 2.90 14.15 2.92 15.14 2.94 16.44 2.98 20 11.08 3.21 12.06 3.24 13.04 3.26 13.70 3.28 14.68 3.30 15.99 3.34 30 10.63 3.57 11.61 3.60 12.59 3.62 13.25 3.64 14.23 3.66 15.54 3.69 35 10.40 3.75 11.38 3.77 12.36 3.80 13.02 3.82 14.00 3.84 15.31 3.87 46 9.90 4.14 10.88 4.17 11.86 4.19 12.52 4.21 13.50 4.23 14.81 4.27 1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C 2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C 3. Power input : Power input is according to Eurovent rating standard OM-3-2015. 4. Peak value : Tested without defrost operation in accordance with EN14511 5. Integrated value : Tested with defrost operation in accordance with EN14511 ※ The real capacity would be changed according to the install environment. 12 EHS Mono II. Specifications 2. Capacity Tables 2-2. AE090/120/140/160JXYDGH/EU (3 Phase) 1) Maximum Heating Capacity (Peak Value) AE160JXYDGH/EU AE140JXYDGH/EU AE120JXYDGH/EU AE090JXYDGH/EU LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input) LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 30 HC(kW) 6.30 9.03 8.49 8.23 8.32 9.45 10.38 11.93 13.48 35 PI(kW) 2.67 3.03 2.87 2.43 2.10 1.90 1.90 1.90 1.89 HC(kW) 6.00 8.60 8.08 7.84 7.92 9.00 9.89 11.36 12.84 PI(kW) 4.09 4.09 3.89 3.02 2.60 2.37 2.35 2.31 2.28 HC(kW) 9.35 11.80 11.09 10.45 10.56 12.00 13.25 15.32 17.40 PI(kW) 4.36 4.63 4.40 3.57 3.07 2.79 2.79 2.77 2.76 HC(kW) 9.65 12.80 12.03 12.20 12.32 14.00 14.92 16.46 18.00 PI(kW) 5.30 5.43 5.16 4.32 3.72 3.38 3.42 3.49 3.56 HC(kW) 11.30 14.40 13.54 13.94 14.08 16.00 17.38 19.69 22.00 30 HC(kW) 9.82 12.39 11.65 10.98 11.09 12.60 13.91 16.09 18.27 PI(kW) 4.60 4.60 4.37 3.39 2.93 2.66 2.64 2.60 2.56 HC(kW) 8.93 11.45 10.76 10.19 10.30 11.70 12.89 14.88 16.86 PI(kW) 4.90 5.20 4.94 4.01 3.45 3.14 3.13 3.12 3.10 HC(kW) 9.33 12.42 11.67 11.76 11.88 13.50 14.42 15.96 17.50 PI(kW) 5.95 6.10 5.80 4.85 4.18 3.80 3.85 3.92 4.00 HC(kW) 10.75 13.97 13.13 13.37 13.51 15.35 16.71 18.98 21.25 45 PI(kW) 3.20 3.59 3.41 2.89 2.49 2.27 2.29 2.30 2.35 HC(kW) 5.70 8.08 7.60 7.06 7.13 8.10 9.06 10.66 12.26 PI(kW) 4.90 5.14 4.88 3.90 3.36 3.06 3.02 2.92 2.88 HC(kW) 8.50 11.09 10.43 9.93 10.03 11.40 12.54 14.43 16.32 PI(kW) 5.20 5.59 5.31 4.52 3.90 3.55 3.52 3.41 3.38 HC(kW) 9.01 12.03 11.31 11.33 11.44 13.00 13.92 15.46 17.00 PI(kW) 6.25 6.67 6.34 5.36 4.62 4.20 4.25 4.26 4.36 HC(kW) 10.20 13.54 12.72 12.81 12.94 14.70 16.04 18.27 20.50 40 35 30 HC(kW) 11.87 15.12 14.21 14.64 14.78 16.80 18.25 20.68 23.10 HC(kW) 5.85 8.34 7.84 7.45 7.52 8.55 9.47 11.01 12.55 35 30 HC(kW) 10.13 13.44 12.63 12.81 12.94 14.70 15.67 17.28 18.90 40 PI(kW) 3.00 3.40 3.23 2.73 2.35 2.14 2.14 2.13 2.12 PI(kW) HC(kW) PI(kW) 7.84 7.22 6.70 6.77 8.05 8.61 10.13 11.65 3.97 4.04 3.43 2.96 2.68 2.75 2.85 2.95 7.28 6.84 6.35 6.42 8.00 8.15 9.59 11.03 4.35 4.49 3.81 3.29 2.96 3.05 3.16 3.27 PI(kW) 5.29 5.67 5.39 4.40 3.80 3.45 3.40 3.33 3.25 HC(kW) PI(kW) HC(kW) PI(kW) 10.76 9.91 9.44 9.53 10.95 11.91 13.71 15.50 5.95 6.06 4.95 4.27 3.68 3.83 3.74 3.66 9.98 9.38 8.94 9.03 10.50 11.28 12.98 14.69 6.52 6.73 5.50 4.74 3.90 4.25 4.16 4.06 PI(kW) 5.59 5.99 5.69 5.04 4.35 3.95 3.90 3.81 3.73 HC(kW) PI(kW) HC(kW) PI(kW) 11.67 10.74 10.76 10.87 12.63 13.23 14.69 16.15 6.28 6.40 5.67 4.89 4.20 4.39 4.29 4.20 10.83 10.18 10.19 10.30 12.25 12.53 13.92 15.30 6.88 7.11 6.30 5.43 4.45 4.87 4.77 4.66 PI(kW) 6.76 7.25 6.88 5.87 5.06 4.60 4.65 4.72 4.80 HC(kW) PI(kW) HC(kW) PI(kW) 13.13 12.09 12.17 12.29 14.60 15.24 17.36 19.48 7.61 7.74 6.60 5.69 5.00 5.23 5.31 5.40 12.18 11.45 11.53 11.64 14.50 14.43 16.44 18.45 8.33 8.60 7.34 6.33 5.40 5.81 5.90 6.00 50 45 40 55 HC(kW) 45 40 35 50 PI(kW) 3.53 3.78 3.59 3.05 2.63 2.39 2.44 2.53 2.62 55 50 45 55 50 55 1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C 2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C 3. Power input : Power input is according to Eurovent rating standard OM-3-2015. 4. Peak value : Tested without defrost operation in accordance with EN14511 5. Integrated value : Tested with defrost operation in accordance with EN14511 ※ The real capacity would be changed according to the install environment. 13 EHS Mono II. Specifications 2. Capacity Tables 2-2. AE090/120/140/160JXYDGH/EU (3 Phase) 2) Maximum Heating Capacity (Integrated Value) AE160JXYDGH/EU AE140JXYDGH/EU AE120JXYDGH/EU AE090JXYDGH/EU LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input) LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 LWE(℃) Tamb(℃) -20 -10 -7 -2 2 7 10 15 20 30 HC(kW) 5.99 7.50 7.98 7.67 7.35 9.45 10.38 11.93 13.48 35 PI(kW) 2.72 2.80 2.83 2.45 2.07 1.90 1.90 1.90 1.89 HC(kW) 5.70 7.14 7.60 7.30 7.00 9.00 9.89 11.36 12.84 PI(kW) 3.37 3.48 3.52 3.07 2.63 2.37 2.35 2.31 2.28 HC(kW) 7.73 9.68 10.30 10.05 9.80 12.00 13.25 15.32 17.40 PI(kW) 3.61 3.72 3.76 3.41 3.06 2.79 2.79 2.77 2.76 HC(kW) 8.10 10.15 10.80 11.00 11.20 14.00 14.92 16.46 18.00 PI(kW) 4.63 4.78 4.82 4.21 3.59 3.38 3.42 3.49 3.56 HC(kW) 10.05 12.60 13.40 12.95 12.50 16.00 17.38 19.69 22.00 30 HC(kW) 8.11 10.17 10.82 10.55 10.29 12.60 13.91 16.09 18.27 PI(kW) 3.79 3.91 3.95 3.45 2.95 2.66 2.64 2.60 2.56 HC(kW) 7.38 9.25 9.85 9.87 9.90 11.70 12.89 14.88 16.86 PI(kW) 4.05 4.18 4.22 3.83 3.44 3.14 3.13 3.12 3.10 HC(kW) 8.06 10.11 10.75 10.96 11.18 13.50 14.42 15.96 17.50 PI(kW) 5.20 5.37 5.42 4.73 4.03 3.80 3.85 3.92 4.00 HC(kW) 10.09 12.64 13.45 12.49 11.53 15.35 16.71 18.98 21.25 45 PI(kW) 3.21 3.31 3.34 2.90 2.47 2.27 2.29 2.30 2.35 HC(kW) 5.36 6.72 7.15 6.83 6.50 8.10 9.06 10.66 12.26 PI(kW) 4.17 4.30 4.34 3.86 3.38 3.06 3.02 2.92 2.88 HC(kW) 7.04 8.83 9.39 9.70 10.00 11.40 12.54 14.43 16.32 PI(kW) 4.75 4.89 4.94 4.45 3.97 3.55 3.52 3.41 3.38 HC(kW) 8.03 10.06 10.70 10.93 11.15 13.00 13.92 15.46 17.00 PI(kW) 5.88 6.05 6.11 5.13 4.15 4.20 4.25 4.26 4.36 HC(kW) 10.13 12.69 13.50 12.03 10.55 14.70 16.04 18.27 20.50 40 35 30 HC(kW) 10.55 13.23 14.07 13.60 13.13 16.80 18.25 20.68 23.10 HC(kW) 5.53 6.93 7.38 7.06 6.75 8.55 9.47 11.01 12.55 35 30 HC(kW) 8.51 10.66 11.34 11.55 11.76 14.70 15.67 17.28 18.90 40 PI(kW) 3.05 3.15 3.18 2.76 2.33 2.14 2.14 2.13 2.12 PI(kW) HC(kW) PI(kW) 6.38 6.53 6.48 6.18 8.05 8.61 10.13 11.65 3.90 3.60 3.43 2.93 2.68 2.75 2.85 2.95 6.05 5.90 6.14 5.85 8.00 8.15 9.59 11.03 4.33 3.70 3.81 3.25 2.96 3.05 3.16 3.27 PI(kW) 4.54 4.68 4.73 4.27 3.80 3.45 3.40 3.33 3.25 HC(kW) PI(kW) HC(kW) PI(kW) 8.39 8.93 9.21 9.50 10.95 11.91 13.71 15.50 5.27 5.12 4.80 4.28 3.68 3.83 3.74 3.66 7.94 8.47 8.73 9.00 10.50 11.28 12.98 14.69 5.85 5.51 5.33 4.75 3.90 4.25 4.16 4.06 PI(kW) 5.42 5.59 5.65 5.08 4.50 3.95 3.90 3.81 3.73 HC(kW) PI(kW) HC(kW) PI(kW) 9.56 10.35 10.38 10.59 12.63 13.23 14.69 16.15 6.29 5.78 5.71 5.06 4.20 4.39 4.29 4.20 9.05 10.00 9.83 10.04 12.25 12.53 13.92 15.30 6.99 5.90 6.34 5.63 4.45 4.87 4.77 4.66 PI(kW) 6.53 6.73 6.80 5.54 4.27 4.60 4.65 4.72 4.80 HC(kW) PI(kW) HC(kW) PI(kW) 12.06 12.65 11.42 10.02 14.60 15.24 17.36 19.48 7.57 6.90 6.23 4.80 5.00 5.23 5.31 5.40 11.42 11.80 10.82 9.50 14.50 14.43 16.44 18.45 8.42 7.00 6.92 5.34 5.40 5.81 5.90 6.00 50 45 40 55 HC(kW) 45 40 35 50 PI(kW) 3.36 3.47 3.50 3.05 2.60 2.39 2.44 2.53 2.62 55 50 45 55 50 55 1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C 2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C 3. Power input : Power input is according to Eurovent rating standard OM-3-2015. 4. Peak value : Tested without defrost operation in accordance with EN14511 5. Integrated value : Tested with defrost operation in accordance with EN14511 ※ The real capacity would be changed according to the install environment. 14 EHS Mono II. Specifications 2. Capacity Tables 2-2. AE090/120/140/160JXYDGH/EU (3 Phase) 3) Maximum Cooling Capacity AE160JXYDGH/EU AE140JXYDGH/EU AE120JXYDGH/EU AE090JXYDGH/EU LWT (Leaving Water Temp.), Tamb (Ambient Temp.), CC (Cooling Capacity), PI (Power input) LWE(℃) 7 10 13 15 18 25 Tamb(℃) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) 10 6.09 1.19 6.50 1.41 6.91 1.44 7.18 1.46 7.59 1.49 8.14 1.55 20 5.86 1.23 6.27 1.60 6.67 1.63 6.95 1.65 7.36 1.67 7.90 1.74 30 5.62 1.24 6.03 1.78 6.44 1.81 6.71 1.83 7.12 1.86 7.66 1.92 35 5.50 1.94 5.91 1.88 6.32 1.90 6.59 1.92 7.00 1.92 7.55 2.01 46 5.24 1.24 5.65 2.08 6.06 2.11 6.33 2.13 6.74 2.15 7.28 2.22 LWE(℃) 7 10 13 15 18 25 Tamb(℃) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) 10 9.97 2.37 10.79 2.37 11.61 2.37 12.15 2.37 12.97 2.37 14.06 2.37 20 9.58 2.69 10.40 2.69 11.22 2.69 11.77 2.69 12.58 2.69 13.67 2.69 30 9.19 3.00 10.01 3.00 10.83 3.00 11.38 3.00 12.19 3.00 13.29 3.00 35 9.00 3.16 9.82 3.16 10.64 3.16 11.18 3.16 12.00 3.16 13.09 3.16 46 8.57 3.51 9.39 3.51 10.21 3.51 10.75 3.51 11.57 3.51 12.66 3.51 LWE(℃) 7 10 13 15 18 25 Tamb(℃) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) 10 10.76 2.62 11.66 2.63 12.56 2.64 13.16 2.65 14.06 2.67 15.26 2.68 20 10.33 2.95 11.23 2.96 12.13 2.98 12.73 2.99 13.63 3.00 14.83 3.02 30 9.91 3.28 10.81 3.30 11.71 3.31 12.31 3.32 13.21 3.33 14.41 3.35 35 9.70 3.45 10.60 3.46 11.50 3.48 12.10 3.49 13.00 3.50 14.20 3.52 46 9.24 3.82 10.14 3.83 11.04 3.84 11.64 3.85 12.54 3.87 13.74 3.89 LWE(℃) 7 10 13 15 18 25 Tamb(℃) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) CC(kW) PI(kW) 10 11.54 2.85 12.52 2.88 13.50 2.90 14.15 2.92 15.14 2.94 16.44 2.98 20 11.08 3.21 12.06 3.24 13.04 3.26 13.70 3.28 14.68 3.30 15.99 3.34 30 10.63 3.57 11.61 3.60 12.59 3.62 13.25 3.64 14.23 3.66 15.54 3.69 35 10.40 3.75 11.38 3.77 12.36 3.80 13.02 3.82 14.00 3.84 15.31 3.87 46 9.90 4.14 10.88 4.17 11.86 4.19 12.52 4.21 13.50 4.23 14.81 4.27 1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C 2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C 3. Power input : Power input is according to Eurovent rating standard OM-3-2015. 4. Peak value : Tested without defrost operation in accordance with EN14511 5. Integrated value : Tested with defrost operation in accordance with EN14511 ※ The real capacity would be changed according to the install environment. 15 EHS Mono II. Specifications 3. Dimensional Drawings 3-1. Outdoor Unit 1) AE050JXYD*H/EU (Unit : mm) ① ② ③ No. Table of Descriptions ① Water Pipe(Out) ② Water Pipe(In) ③ Power & Communication Wiring Conduits 16 EHS Mono II. Specifications 3. Dimensional Drawings 3-1. Outdoor Unit 2) AE090JXYD*H/EU (Unit : mm) No. Table of Descriptions ① Water Pipe(Out) ② Water Pipe(In) ③ Power & Communication Wiring Conduits 17 EHS Mono II. Specifications 3. Dimensional Drawings 3-1. Outdoor Unit 3) AE120/140/160JXYD*H/EU No. Table of Descriptions ① Water Pipe(Out) ② Water Pipe(In) ③ Power & Communication Wiring Conduits (Unit : mm) 18 EHS Mono II. Specifications 3. Dimensional Drawings 3-2. Control Kit 1) MIM-E03A(B)N (Unit : mm) 342 371 2-R2.5 2-R4.0 2-R3.0 23 87 110 290 ① No. Table of Descriptions ① Conduit for Wiring (Rubber) 19 EHS Mono II. Specifications 4. Piping Diagrams 4-1. AE050JXYDEH/EU 4-2. AE090JXYD*H/EU 20 EHS Mono 4. Piping Diagrams 4-3. AE120/140/160JXYD*H/EU II. Specifications EHS Mono II. Specifications 5. Wiring Diagrams 5-1. Outdoor Unit 1) AE050JXYDEH/EU 22 EHS Mono II. Specifications 5. Wiring Diagrams 5-1. Outdoor Unit 2) AE090~160JXYDEH/EU 23 EHS Mono II. Specifications 5. Wiring Diagrams 5-1. Outdoor Unit 3) AE090~160JXYDGH/EU 24 EHS Mono II. Specifications 5. Wiring Diagrams 5-2. Control Kit 1) MIM-E03A(B)N 25 EHS Mono II. Specifications 6. Electric Specifications 6-1. Outdoor Unit Voltage Range Rated Product Mono MCA MFA 264 20.0 25.0 198 264 22.0 27.5 220-240 198 264 28.0 35.0 50 220-240 198 264 30.0 37.5 AE160JXYDEH/EU 50 220-240 198 264 32.0 40.0 AE090JXYDGH/EU 50 380-415 342 457 10.0 16.1 AE120JXYDGH/EU 50 380-415 342 457 10.0 16.1 AE014JXYDGH/EU 50 380-415 342 457 12.0 16.1 AE160JXYDGH/EU 50 380-415 342 457 12,0 16.1 Model Name Hz Volts Min. Max. AE050JXYDEH/EU 50 220-240 198 AE090JXYDEH/EU 50 220-240 AE120JXYDEH/EU 50 AE014JXYDEH/EU ※ Notes 1. The power cable is not supplied with air conditioner. 2. Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC:H05RN-F) 3. This Equipment complies with IEC 61000-3-12. ※ Abbreviations 1. MCA : Min. Circuit Amps. (A) 2. MFA : Max. Fuse Amps. (A) 6-2. Control Kit Product Model Name Load Power supply No Heater (Water Pump, Valve, Wired RMC) Control Kit MIM-E03AN MIM-E03BN Booster Heater (3kW) 1Φ, 220~240V, 50Hz Booster Heater (~3kW) + Backup Heater (~3kW) Power cable Max. Length Type GL mm , wires m A 1.5 / 3 < 10m 10 2.5 / 3 10m < L< 20m 10 4.0 / 3 < 10m 20 6.0 / 3 10m < L< 20m 20 4.0 / 3 < 10m 40 6.0 / 3 10m < L< 20m 40 2 ※ Notes 1. The power cable is not supplied with the heat pump. 2. For power cable, use the grade H07RN-F materials in 1Ø system. 3. If you connect Backup Heater at separated power cable, you can reduce wire size. (Please refer to indoor unit installation manual) 26 EHS Mono II. Specifications 7. Sound Pressure Level 7-1. Operation Sound Level Unit (dB(A)) Model Heating Cooling AE050JXYDEH/EU 45 45 AE090JXYDEH/EU 48 48 AE090JXYDGH/EU 48 48 7-2. NC Curve 1) AE050JXYDEH/EU 2) AE090JXYDEH/EU 1) AE090JXYDGH/EU ※ Notes 1. These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed. 2. Operation sound level may differ depending on operation and ambient conditions. 27 EHS Mono II. Specifications 7. Sound Pressure Level 7-1. Operation Sound Level Unit (dB(A)) Model Heating Cooling AE120JXYDEH/EU 50 50 AE120JXYDGH/EU 50 50 AE140JXYDEH/EU 51 52 AE140JXYDGH/EU 51 52 7-2. NC Curve 1) AE120JXYDEH/EU 2) AE120JXYDGH/EU 3) AE140JXYDEH/EU 4) AE140JXYDGH/EU ※ Notes 1. These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed. 2. Operation sound level may differ depending on operation and ambient conditions. 28 EHS Mono II. Specifications 7. Sound Pressure Level 7-1. Operation Sound Level Unit (dB(A)) Model Heating Cooling AE160JXYDEH/EU 52 54 AE160JXYDGH/EU 52 54 7-2. NC Curve 1) AE160JXYDEH/EU 2) AE160JXYDGH/EU ※ Notes 1. These operation values were obtained in an anechoic room. Sound pressure level will vary depending on a range of factors such as the construction of the particular room where the equipment is installed. 2. Operation sound level may differ depending on operation and ambient conditions. 29 EHS Mono II. Specifications 8. Operation Range 8-1. Outdoor Unit 1) Cooling 2) Heating Outdoor temp. (℃, DB) 35 Outdoor temp. (℃, DB) 46 10 Backup heater operation only. (No heat-pump operation). -10 -25 5 25 Leaving water temp. (℃) Outdoor Unit Controller Cooling Heating 15 25 40 55 Leaving water temp. (℃) Water Temp. (℃) Water Flow Rates (LPM) Min Std Max Cooling 5 - 25 Heating 15 - 55 Inlet - 23 (12*3) 30 Outlet 5 18 (7*3) 25 Inlet 5 (40*3) Outlet 25(15*4) 30 35 (45*3) - Min 16 (7*1) Std (Δ 5℃) 55 Max Air Temp. (℃, DB/WB) Min Std Max 10/- 35/24 46/27 -25/- 7/6 35/24 58 (42*2) *1) Figures in brackets are for 5kW model. *2) Figures in brackets are for 5kW/9kW models. *3) Figures in brackets are based on Eurovent Test Condition #2 *4) Figures in brackets are based on back up heater operation only. 3) DHW (Domestic Hot Water Tank) Outdoor temp. (℃, DB) 43 35 Booster heater operation only. -10 -25 70 25 32 50 DHW Tank temp. (℃) ※ Special condition( 35℃ < Outdoor temp. ≤ 43℃) is operated by only Booster Heater. SAMSUNG doesn’t supply DHW for EHS Mono. Since it is a reference data, you have to check DHW operation range for yours. 30 EHS Mono II. Specifications 9. Hydraulic Performance 9-1. Correction Graph 1) AE050/090JXYD*H/EU 2) AE120/140/160JXYD*H/EU 9-2. Capacity Correction 1) Heating 2) Cooling ※ Notes 1. To ensure correct operation and predict the expected performance, this graph can be used. 2. Flow and resistance characteristic is dependent on anti-freezer concentration. 3. Tested with Ethylene Glycol. ※ Abbreviations 1. EG : Ethylene Glycol 31 III. Application 1. Application Examples EHS Mono III. Application 1. Application Examples 1-1. Outdoor Unit + Control Kit 2) Outdoor Unit + Cylinder Unit 33 SI\ MSUNG Samsung E뻐ctronics Co., LTD. B2B PM/SE '!'.r./'암 현 SI\ MSUNG