1. Specifications

※ History List
Version
Date
Update Information
1.0
’15.03.30
- 2015 New EHS Mono TDB Released. (Except SCOP / ESEER)
1.1
‘15.04.06
- Add SCOP / ESEER
1.2
’15.04.10
- Modify Capacity Table
1.3
‘15.06.19
1.4
’15.06.22
- Add 5kW Model / Control KIT (E03BN)
- Modify : Change the Note for Refrigerant
- Modify Product Gross for 5kW Model
- Modify : Piping Diagram / Operating Range for DHW
EHS
Technical Data Book
EHS Mono for Europe
Model : AE***JXYDEH/EU
AE***JXYDGH/EU
I. Products
1. Nomenclature
2. Line-up
II. Specifications
1. Specification
2. Capacity Tables
3. Dimensional Drawings
4. Piping Diagrams
5. Wiring Diagrams
6. Electric Specifications
7. Sound Pressure Level
8. Operation Range
9. Hydraulic Performance
III. Application
1. Application Example
I. Products
1. Nomenclature
2. Line-up
EHS Mono
I. Products
1. Nomenclature
1-1. Outdoor Unit
Model Name (New)
AE
090
J
X
Y
D
E
H
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(1) Classification
AE
EHS
(Buyer)
Mono (Outdoor Unit)
(6) Feature 1
x 1/10 kW (3 digits)
(3) Version
J
EU
(5) Type
Y
(2) Capacity
/
2015
(4) Product Type
N
Indoor
X
Outdoor
D
DELUXE (Basic)
(7) Rating Voltage
E
1Φ, 220~240V, 50Hz
G
3Φ, 380~415V, 50Hz
(8) Mode
H
Heat Pump
R410A
3
EHS Mono
I. Products
2. Line-up
2-1. Outdoor Unit
Mono
Type
Capacity (kW)
5.0
9.0
12.0
14.0
16.0
AE050JXYDEH
AE090JXYDEH
AE120JXYDEH
AE140JXYDEH
AE160JXYDEH
AE090JXYDGH
AE120JXYDGH
AE140JXYDGH
AE160JXYDGH
1 Phase
3 Phases
N/A
2-2. Control Kit
Control Unit
MIM-E03A(B)N
4
II. Specifications
1. Specifications
2. Capacity Tables
3. Dimensional Drawings
4. Piping Diagrams
5. Wiring Diagrams
6. Electric Specifications
7. Sound Pressure Level
8. Operation Range
9. Hydraulic Performance
EHS Mono
II. Specifications
1. Specifications
1-1. Outdoor Unit
Type
Model Name
Outdoor Unit
Mode
Heating
Nominal Capacity
Cooling
Performance
(A7/W35) *1
Power Input
(Nominal)
Heating
Current Input
(Nominal)
Heating
Cooling
Cooling
30,700
40,900
W
5,000
7,500
12,000
Btu/h
17,100
25,600
40,900
1,060
2,140
2,660
1,210
1,950
3,160
5,1
9.2
12
5,7
9
14.3
4.51
W
A
3.80
SCOP(35℃)
-
4.50
4.41
4.46
-
5.29
5.07
4.98
Heating
W
4,500
7,000
9,800
-
3.46
3.00
3.32
Heating
W
4,700
7,600
10,300
COP
-
2.69
2.39
2.61
MCA
A
20
22
28
MFA
Water Flow Rate
(Heating/Cooling)
Water Pressure (Max)
A
25
27.5
35
LPM
14.5/14.5
26/22
35/35
COP
Water Pipe
bar
3
3
3
Inlet
Φ, inch
BSPP male 1"
BSPP male 1"
BSPP male 1"
Outlet
Φ, inch
BSPP male 1"
BSPP male 1"
BSPP male 1"
Heating
°C
25~55
25~55
25~55
Cooling
°C
5~25
5~25
5~25
Type
-
R410A
R410A
R410A
Control Method
-
EEV INCLUDED
EEV INCLUDED
EEV INCLUDED
g
1,150
1,400
2,600
V, Hz, Φ
220~240V, 50Hz, 1Ф
220~240V, 50Hz, 1Ф
220~240V, 50Hz, 1Ф
Type
-
BLDC Twin Rotary
BLDC Twin Rotary
BLDC Twin Rotary
Model
-
UG4TH200FUAE4
UG8TH8265FJW
UG5T450FU
Oil
-
POE
POE
PVE
CMM
51
53
108
l/s
850
883
1800
Air Flow Rate
Cooling
Number of Unit
EA
1
1
2
W
N/A
150
150
Heating
dB(A)
45
48
50
Cooling
dB(A)
45
48
50
Heating
dB
61
63
64
Cooling
dB
62
64
65
kg
59.0
76.0
108.0
Base Heater
Sound Pressure
Sound*4
Sound Power
Net Weight
Operating
Temp. Range
17,100
4.21
Factory Charging
External
Dimension
12,000
Btu/h
3.85
Power Supply
Outdoor
Unit
9,000
4,13
Leaving Water
Temperature
Fan
Heat Pump (A2W)
5,000
4,72
Capacity
Compressor
Heat Pump (A2W)
-
Performance
(A-7/W35) *3
Refrigerant
Heat Pump (A2W)
W
-
Capacity
Water
Connections
Mono
AE120JXYDEH/EU
COP (Nominal Heating)
Performance
(A2/W35) *2
Field
Wiring
Mono
AE090JXYDEH/EU
EER (Nominal Cooling)
ESEER
System
Mono
AE050JXYDEH/EU
Shipping Weight
kg
63.0
84.0
118.0
Net Dimensions (WxHxD)
mm
880 x 798 x 310
940 x 998 x 330
940 x 1,420 x 330
Shipping Dimensions (WxHxD)
mm
1023 x 911 x 413
995 x 1,178 x 426
995 x 1,598 x 426
Heating*5
℃
-25~35
-25~35
-25~35
Cooling
℃
10~46
10~46
10~46
DHW Tank*6
℃
-25~43
-25~43
-25~43
*1) A2W Condition #1 : (Heating) Water In/Out 30°C/35°C, Outdoor Air DB/WB 7°C/6°C; (Cooling) Water In/Out 23°C/18°C, Outdoor Air DB 35°C.
*2) A2W Condition #2 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB 2°C/1°C
*3) A2W Condition #3 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB -7°C/-8°C
*4) Sound Pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
*5) At the temperature -25°C ~ -20°C, operation is available but capacity cannot be guaranteed.
*6) Heat pump operating range of DHW : -25°C ~ 35°C.
7) These products contain R410A which is fluorinated greenhouse gas.
6
EHS Mono
II. Specifications
1. Specifications
1-1. Outdoor Unit
Type
Model Name
Outdoor Unit
Mode
Heating
Nominal Capacity
Cooling
Performance
(A7/W35) *1
Power Input
(Nominal)
Heating
Current Input
(Nominal)
Heating
Cooling
Cooling
System
Mono
AE090JXYDGH/EU
Heat Pump (A2W)
-
Heat Pump (A2W)
Heat Pump (A2W)
W
14,000
16,000
9,000
Btu/h
47,800
54,600
30,700
W
13,000
14,000
7,000
Btu/h
44,300
47,800
23,900
3,140
3,800
2,140
3,500
3,840
1,920
14.3
17.1
3.5
15.7
17.3
3.2
4.21
W
A
COP (Nominal Heating)
-
4.46
4.21
-
3.71
3.65
3.65
SCOP(35℃)
-
4.43
4.41
4.41
Capacity
-
4.97
4.92
4.69
Heating
W
11,200
12,500
7,000
-
3.26
3.10
3.00
Heating
W
10,800
13,400
7,600
2.39
COP
Performance
(A-7/W35) *3
Capacity
COP
-
2.56
2.47
Field
Wiring
MCA
A
30
32
10
MFA
Water Flow Rate
(Heating/Cooling)
Water Pressure (Max)
A
37.5
40
16.1
LPM
40/37
46/40
26/21
Water
Connections
Water Pipe
Leaving Water
Temperature
Refrigerant
bar
3
3
3
Inlet
Φ, inch
BSPP male 1"
BSPP male 1"
BSPP male 1"
Outlet
Φ, inch
BSPP male 1"
BSPP male 1"
BSPP male 1"
Heating
°C
25~55
25~55
25~55
Cooling
°C
5~25
5~25
5~25
Type
-
R410A
R410A
R410A
Control Method
-
EEV INCLUDED
EEV INCLUDED
EEV INCLUDED
Factory Charging
g
2,600
2,600
1,500
V, Hz, Φ
220~240V, 50Hz, 1Ф
220~240V, 50Hz, 1Ф
380~415V, 50Hz, 3Ф
Type
-
BLDC Twin Rotary
BLDC Twin Rotary
BLDC Twin Rotary
Model
-
UG5T450FU
UG5T450FU
UG8T300FUCJU
Oil
-
PVE
PVE
PVE
CMM
108
108
53
l/s
1800
1800
883
Power Supply
Compressor
Fan
Air Flow Rate
Cooling
Number of Unit
EA
2
2
1
W
150
150
150
Heating
dB(A)
51
52
48
Cooling
dB(A)
52
54
48
Heating
dB
65
66
63
Cooling
dB
66
69
64
kg
108.0
108.0
76.0
Base Heater
Outdoor
Unit
Mono
AE160JXYDEH/EU
EER (Nominal Cooling)
ESEER
Performance
(A2/W35) *2
Mono
AE140JXYDEH/EU
Sound Pressure
Sound*4
Sound Power
Net Weight
External
Dimension
Operating
Temp. Range
Shipping Weight
kg
118.0
118.0
84.0
Net Dimensions (WxHxD)
mm
940 x 1,420 x 330
940 x 1,420 x 330
940 x 998 x 330
Shipping Dimensions (WxHxD)
mm
995 x 1,598 x 426
995 x 1,598 x 426
995 x 1,178 x 426
Heating*5
℃
-25~35
-25~35
-25~35
Cooling
℃
10~46
10~46
10~46
DHW Tank*6
℃
-25~43
-25~43
-25~43
*1) A2W Condition #1 : (Heating) Water In/Out 30°C/35°C, Outdoor Air DB/WB 7°C/6°C; (Cooling) Water In/Out 23°C/18°C, Outdoor Air DB 35°C.
*2) A2W Condition #2 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB 2°C/1°C
*3) A2W Condition #3 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB -7°C/-8°C
*4) Sound Pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
*5) At the temperature -25°C ~ -20°C, operation is available but capacity cannot be guaranteed.
*6) Heat pump operating range of DHW : -25°C ~ 35°C.
7) These products contain R410A which is fluorinated greenhouse gas.
7
EHS Mono
II. Specifications
1. Specifications
1-1. Outdoor Unit
Type
Model Name
Outdoor Unit
Mode
Heating
Nominal Capacity
Cooling
Performance
(A7/W35) *1
Power Input
(Nominal)
Heating
Current Input
(Nominal)
Heating
Cooling
Cooling
System
Mono
AE160JXYDGH/EU
Heat Pump (A2W)
-
Heat Pump (A2W)
Heat Pump (A2W)
W
12,000
14,000
16,000
Btu/h
40,900
47,800
54,600
W
12,000
13,000
14,000
Btu/h
40,900
44,300
47,800
2,660
3,140
3,800
3,160
3,500
3,840
4.2
4.8
5.7
5.2
5.3
5.8
4.21
W
A
COP (Nominal Heating)
-
4.51
4.46
-
3.80
3.71
3.65
SCOP(35℃)
-
4.46
4.43
4.41
Capacity
-
4.98
4.97
4.92
Heating
W
9,800
11,200
12,500
-
3.32
3.26
3.10
Heating
W
10,300
10,800
13,400
2.47
COP
Performance
(A-7/W35) *3
Capacity
COP
-
2.61
2.56
Field
Wiring
MCA
A
10
12
12
MFA
Water Flow Rate
(Heating/Cooling)
Water Pressure (Max)
A
16.1
16.1
16.1
LPM
35/35
40/37
46/40
Water
Connections
Water Pipe
Leaving Water
Temperature
Refrigerant
bar
3
3
3
Inlet
Φ, inch
BSPP male 1"
BSPP male 1"
BSPP male 1"
Outlet
Φ, inch
BSPP male 1"
BSPP male 1"
BSPP male 1"
Heating
°C
25~55
25~55
25~55
Cooling
°C
5~25
5~25
5~25
Type
-
R410A
R410A
R410A
Control Method
-
EEV INCLUDED
EEV INCLUDED
EEV INCLUDED
Factory Charging
g
2,600
2,600
2,600
V, Hz, Φ
380~415V, 50Hz, 3Ф
380~415V, 50Hz, 3Ф
380~415V, 50Hz, 3Ф
Type
-
BLDC Twin Rotary
BLDC Twin Rotary
BLDC Twin Rotary
Model
-
UG5T450FU
UG5T450FU
UG5T450FU
Oil
-
PVE
PVE
PVE
CMM
108
108
108
l/s
1800
1800
1800
Power Supply
Compressor
Fan
Air Flow Rate
Cooling
Number of Unit
EA
2
2
2
W
150
150
150
Heating
dB(A)
50
51
52
Cooling
dB(A)
50
52
54
Heating
dB
64
65
66
Cooling
dB
65
66
69
kg
108.0
108.0
108.0
Base Heater
Outdoor
Unit
Mono
AE140JXYDGH/EU
EER (Nominal Cooling)
ESEER
Performance
(A2/W35) *2
Mono
AE120JXYDGH/EU
Sound Pressure
Sound*4
Sound Power
Net Weight
External
Dimension
Operating
Temp. Range
Shipping Weight
kg
118.0
118.0
118.0
Net Dimensions (WxHxD)
mm
940 x 1,420 x 330
940 x 1,420 x 330
940 x 1,420 x 330
Shipping Dimensions (WxHxD)
mm
995 x 1,598 x 426
995 x 1,598 x 426
995 x 1,598 x 426
Heating*5
℃
-25~35
-25~35
-25~35
Cooling
℃
10~46
10~46
10~46
DHW Tank*6
℃
-25~43
-25~43
-25~43
*1) A2W Condition #1 : (Heating) Water In/Out 30°C/35°C, Outdoor Air DB/WB 7°C/6°C; (Cooling) Water In/Out 23°C/18°C, Outdoor Air DB 35°C.
*2) A2W Condition #2 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB 2°C/1°C
*3) A2W Condition #3 : (Heating) Water In/Out */35°C, Outdoor Air DB/WB -7°C/-8°C
*4) Sound Pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
*5) At the temperature -25°C ~ -20°C, operation is available but capacity cannot be guaranteed.
*6) Heat pump operating range of DHW : -25°C ~ 35°C.
7) These products contain R410A which is fluorinated greenhouse gas.
8
EHS Mono
II. Specifications
1. Specifications
1-2. Control Kit
MIM-E03AN
MIM-E03BN
-
090/120/140/160 Model
050 Model
Model Name
Use with
V, Hz, Φ
220~240V, 50Hz, 1Ф
220~240V, 50Hz, 1Ф
Net
kg
3.5
3.5
Gross
kg
6.0
6.0
Net
mm
370x110x290
370x110x290
Gross
mm
439x168x329
439x168x329
Power Supply
Weight
External
Dimension
Flow Switch
External
Control
Dimensions
(WxHxD)
LPM
16±1.5
7±1.5
Booster Heater
Set Point (Min. flow rates)
-
AC 230V (Max 20A)
AC 230V (Max 20A)
Back up Heater (/Boiler)
-
AC 230V (Max 0.5A)
AC 230V (Max 0.5A)
Water Pump
-
AC 230V (Max 2A)
AC 230V (Max 2A)
2way(or 3way) Valve
-
AC 230V (Max 0.5A / 120W)
AC 230V (Max 0.5A / 120W)
Room Thermostat
-
AC 230V (Max 10mA)
AC 230V (Max 10mA)
Solar Pump
-
AC 230V (Max 10mA)
AC 230V (Max 10mA)
Inverter Pump
-
AC 230V (Max 2A) (NEW)
AC 230V (Max 2A)
3way Mixing Valve
-
AC 230V (Max 0.5A / 120W) (NEW)
AC 230V (Max 0.5A / 120W)
9
EHS Mono
II. Specifications
2. Capacity Tables
2-1. AE050/090/120/140/160JXYDEH/EU (1 Phase)
1) Maximum Heating Capacity (Peak Value)
AE160JXYDEH/EU
AE140JXYDEH/EU
AE120JXYDEH/EU
AE090JXYDEH/EU
AE050JXYDEH/EU
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input)
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
30
HC(kW)
3.57
5.25
4.94
4.57
4.62
5.25
5.73
6.54
7.35
35
PI(kW)
1.47
1.78
1.69
1.20
1.04
0.94
0.95
0.97
0.98
HC(kW)
3.40
5.00
4.70
4.36
4.40
5.00
5.46
6.23
7.00
PI(kW)
2.67
3.03
2.87
2.43
2.10
1.90
1.90
1.90
1.89
HC(kW)
6.00
8.60
8.08
7.84
7.92
9.00
9.89
11.36
12.84
PI(kW)
4.09
4.09
3.89
3.02
2.60
2.37
2.35
2.31
2.28
HC(kW)
9.35
11.80
11.09
10.45
10.56
12.00
13.25
15.32
17.40
PI(kW)
4.36
4.63
4.40
3.57
3.07
2.79
2.79
2.77
2.76
HC(kW)
9.65
12.80
12.03
12.20
12.32
14.00
14.92
16.46
18.00
PI(kW)
5.30
5.43
5.16
4.32
3.72
3.38
3.42
3.49
3.56
HC(kW)
11.30
14.40
13.54
13.94
14.08
16.00
17.38
19.69
22.00
30
HC(kW)
6.30
9.03
8.49
8.23
8.32
9.45
10.38
11.93
13.48
HC(kW)
5.85
8.34
7.84
7.45
7.52
8.55
9.47
11.01
12.55
PI(kW)
4.60
4.60
4.37
3.39
2.93
2.66
2.64
2.60
2.56
HC(kW)
8.93
11.45
10.76
10.19
10.30
11.70
12.89
14.88
16.86
PI(kW)
4.90
5.20
4.94
4.01
3.45
3.14
3.13
3.12
3.10
HC(kW)
9.33
12.42
11.67
11.76
11.88
13.50
14.42
15.96
17.50
PI(kW)
5.95
6.10
5.80
4.85
4.18
3.80
3.85
3.92
4.00
HC(kW)
10.75
13.97
13.13
13.37
13.51
15.35
16.71
18.98
21.25
45
PI(kW)
1.75
2.10
2.00
1.54
1.33
1.21
1.22
1.21
1.24
HC(kW)
3.36
4.70
4.42
4.09
4.14
4.70
5.18
5.99
6.80
PI(kW)
3.20
3.59
3.41
2.89
2.49
2.27
2.29
2.30
2.35
HC(kW)
5.70
8.08
7.60
7.06
7.13
8.10
9.06
10.66
12.26
PI(kW)
4.90
5.14
4.88
3.90
3.36
3.06
3.02
2.92
2.88
HC(kW)
8.50
11.09
10.43
9.93
10.03
11.40
12.54
14.43
16.32
PI(kW)
5.20
5.59
5.31
4.52
3.90
3.55
3.52
3.41
3.38
HC(kW)
9.01
12.03
11.31
11.33
11.44
13.00
13.92
15.46
17.00
PI(kW)
6.25
6.67
6.34
5.36
4.62
4.20
4.25
4.26
4.36
HC(kW)
10.20
13.54
12.72
12.81
12.94
14.70
16.04
18.27
20.50
40
PI(kW)
HC(kW)
PI(kW)
4.56
4.20
3.89
3.93
4.60
4.93
5.69
6.46
2.32
2.36
1.94
1.67
1.48
1.53
1.55
1.58
4.23
3.98
3.69
3.72
4.50
4.67
5.39
6.12
2.54
2.62
2.15
1.86
1.60
1.70
1.73
1.75
PI(kW)
3.53
3.78
3.59
3.05
2.63
2.39
2.44
2.53
2.62
HC(kW)
PI(kW)
HC(kW)
PI(kW)
7.84
7.22
6.70
6.77
8.05
8.61
10.13
11.65
3.97
4.04
3.43
2.96
2.68
2.75
2.85
2.95
7.28
6.84
6.35
6.42
8.00
8.15
9.59
11.03
4.35
4.49
3.81
3.29
2.96
3.05
3.16
3.27
PI(kW)
5.29
5.67
5.39
4.40
3.80
3.45
3.40
3.33
3.25
HC(kW)
PI(kW)
HC(kW)
PI(kW)
10.76
9.91
9.44
9.53
10.95
11.91
13.71
15.50
5.95
6.06
4.95
4.27
3.68
3.83
3.74
3.66
9.98
9.38
8.94
9.03
10.50
11.28
12.98
14.69
6.52
6.73
5.50
4.74
3.90
4.25
4.16
4.06
PI(kW)
5.59
5.99
5.69
5.04
4.35
3.95
3.90
3.81
3.73
HC(kW)
PI(kW)
HC(kW)
PI(kW)
11.67
10.74
10.76
10.87
12.63
13.23
14.69
16.15
6.28
6.40
5.67
4.89
4.20
4.39
4.29
4.20
10.83
10.18
10.19
10.30
12.25
12.53
13.92
15.30
6.88
7.11
6.30
5.43
4.45
4.87
4.77
4.66
PI(kW)
6.76
7.25
6.88
5.87
5.06
4.60
4.65
4.72
4.80
HC(kW)
PI(kW)
HC(kW)
PI(kW)
13.13
12.09
12.17
12.29
14.60
15.24
17.36
19.48
7.61
7.74
6.60
5.69
5.00
5.23
5.31
5.40
12.18
11.45
11.53
11.64
14.50
14.43
16.44
18.45
8.33
8.60
7.34
6.33
5.40
5.81
5.90
6.00
50
55
50
45
40
55
HC(kW)
45
40
35
50
PI(kW)
2.06
2.21
2.09
1.72
1.49
1.35
1.36
1.38
1.40
45
40
35
30
HC(kW)
11.87
15.12
14.21
14.64
14.78
16.80
18.25
20.68
23.10
PI(kW)
3.00
3.40
3.23
2.73
2.35
2.14
2.14
2.13
2.12
35
30
HC(kW)
10.13
13.44
12.63
12.81
12.94
14.70
15.67
17.28
18.90
HC(kW)
3.38
4.85
4.56
4.23
4.27
4.85
5.32
6.11
6.90
35
30
HC(kW)
9.82
12.39
11.65
10.98
11.09
12.60
13.91
16.09
18.27
40
PI(kW)
1.65
2.00
1.90
1.35
1.17
1.06
1.07
1.08
1.10
55
50
45
55
50
55
1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C
3. Power input : Power input is according to Eurovent rating standard OM-3-2015.
4. Peak value : Tested without defrost operation in accordance with EN14511
5. Integrated value : Tested with defrost operation in accordance with EN14511
※ The real capacity would be changed according to the install environment.
10
EHS Mono
II. Specifications
2. Capacity Tables
2-1. AE050/090/120/140/160JXYDEH/EU (1 Phase)
2) Maximum Heating Capacity (Integrated Value)
AE160JXYDEH/EU
AE140JXYDEH/EU
AE120JXYDEH/EU
AE090JXYDEH/EU
AE050JXYDEH/EU
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input)
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
30
HC(kW)
3.70
4.64
4.94
4.83
4.73
5.25
5.73
6.54
7.35
35
PI(kW)
1.50
1.54
1.56
1.36
1.16
0.94
0.95
0.97
0.98
HC(kW)
3.53
4.42
4.70
4.60
4.50
5.00
5.46
6.23
7.00
PI(kW)
2.72
2.80
2.83
2.45
2.07
1.90
1.90
1.90
1.89
HC(kW)
5.70
7.14
7.60
7.30
7.00
9.00
9.89
11.36
12.84
PI(kW)
3.37
3.48
3.52
3.07
2.63
2.37
2.35
2.31
2.28
HC(kW)
7.73
9.68
10.30
10.05
9.80
12.00
13.25
15.32
17.40
PI(kW)
3.61
3.72
3.76
3.41
3.06
2.79
2.79
2.77
2.76
HC(kW)
8.10
10.15
10.80
11.00
11.20
14.00
14.92
16.46
18.00
PI(kW)
4.63
4.78
4.82
4.21
3.59
3.38
3.42
3.49
3.56
HC(kW)
10.05
12.60
13.40
12.95
12.50
16.00
17.38
19.69
22.00
30
HC(kW)
5.99
7.50
7.98
7.67
7.35
9.45
10.38
11.93
13.48
HC(kW)
5.53
6.93
7.38
7.06
6.75
8.55
9.47
11.01
12.55
PI(kW)
3.79
3.91
3.95
3.45
2.95
2.66
2.64
2.60
2.56
HC(kW)
7.38
9.25
9.85
9.87
9.90
11.70
12.89
14.88
16.86
PI(kW)
4.05
4.18
4.22
3.83
3.44
3.14
3.13
3.12
3.10
HC(kW)
8.06
10.11
10.75
10.96
11.18
13.50
14.42
15.96
17.50
PI(kW)
5.20
5.37
5.42
4.73
4.03
3.80
3.85
3.92
4.00
HC(kW)
10.09
12.64
13.45
12.49
11.53
15.35
16.71
18.98
21.25
45
PI(kW)
1.90
1.96
1.98
1.68
1.38
1.21
1.22
1.21
1.24
HC(kW)
3.38
4.23
4.50
4.25
4.00
4.70
5.18
5.99
6.80
PI(kW)
3.21
3.31
3.34
2.90
2.47
2.27
2.29
2.30
2.35
HC(kW)
5.36
6.72
7.15
6.83
6.50
8.10
9.06
10.66
12.26
PI(kW)
4.17
4.30
4.34
3.86
3.38
3.06
3.02
2.92
2.88
HC(kW)
7.04
8.83
9.39
9.70
10.00
11.40
12.54
14.43
16.32
PI(kW)
4.75
4.89
4.94
4.45
3.97
3.55
3.52
3.41
3.38
HC(kW)
8.03
10.06
10.70
10.93
11.15
13.00
13.92
15.46
17.00
PI(kW)
5.88
6.05
6.11
5.13
4.15
4.20
4.25
4.26
4.36
HC(kW)
10.13
12.69
13.50
12.03
10.55
14.70
16.04
18.27
20.50
40
PI(kW)
HC(kW)
PI(kW)
4.02
4.60
4.04
3.80
4.60
4.93
5.69
6.46
2.45
2.40
2.05
1.63
1.48
1.53
1.55
1.58
3.81
4.70
3.83
3.60
4.50
4.67
5.39
6.12
2.72
2.60
2.28
1.81
1.60
1.70
1.73
1.75
PI(kW)
3.36
3.47
3.50
3.05
2.60
2.39
2.44
2.53
2.62
HC(kW)
PI(kW)
HC(kW)
PI(kW)
6.38
6.53
6.48
6.18
8.05
8.61
10.13
11.65
3.90
3.60
3.43
2.93
2.68
2.75
2.85
2.95
6.05
5.90
6.14
5.85
8.00
8.15
9.59
11.03
4.33
3.70
3.81
3.25
2.96
3.05
3.16
3.27
PI(kW)
4.54
4.68
4.73
4.27
3.80
3.45
3.40
3.33
3.25
HC(kW)
PI(kW)
HC(kW)
PI(kW)
8.39
8.93
9.21
9.50
10.95
11.91
13.71
15.50
5.27
5.12
4.80
4.28
3.68
3.83
3.74
3.66
7.94
8.47
8.73
9.00
10.50
11.28
12.98
14.69
5.85
5.51
5.33
4.75
3.90
4.25
4.16
4.06
PI(kW)
5.42
5.59
5.65
5.08
4.50
3.95
3.90
3.81
3.73
HC(kW)
PI(kW)
HC(kW)
PI(kW)
9.56
10.35
10.38
10.59
12.63
13.23
14.69
16.15
6.29
5.78
5.71
5.06
4.20
4.39
4.29
4.20
9.05
10.00
9.83
10.04
12.25
12.53
13.92
15.30
6.99
5.90
6.34
5.63
4.45
4.87
4.77
4.66
PI(kW)
6.53
6.73
6.80
5.54
4.27
4.60
4.65
4.72
4.80
HC(kW)
PI(kW)
HC(kW)
PI(kW)
12.06
12.65
11.42
10.02
14.60
15.24
17.36
19.48
7.57
6.90
6.23
4.80
5.00
5.23
5.31
5.40
11.42
11.80
10.82
9.50
14.50
14.43
16.44
18.45
8.42
7.00
6.92
5.34
5.40
5.81
5.90
6.00
50
55
50
45
40
55
HC(kW)
45
40
35
50
PI(kW)
2.11
2.18
2.20
1.83
1.45
1.35
1.36
1.38
1.40
45
40
35
30
HC(kW)
10.55
13.23
14.07
13.60
13.13
16.80
18.25
20.68
23.10
PI(kW)
3.05
3.15
3.18
2.76
2.33
2.14
2.14
2.13
2.12
35
30
HC(kW)
8.51
10.66
11.34
11.55
11.76
14.70
15.67
17.28
18.90
HC(kW)
3.45
4.32
4.60
4.43
4.25
4.85
5.32
6.11
6.90
35
30
HC(kW)
8.11
10.17
10.82
10.55
10.29
12.60
13.91
16.09
18.27
40
PI(kW)
1.68
1.73
1.75
1.53
1.30
1.06
1.07
1.08
1.10
55
50
45
55
50
55
1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C
3. Power input : Power input is according to Eurovent rating standard OM-3-2015.
4. Peak value : Tested without defrost operation in accordance with EN14511
5. Integrated value : Tested with defrost operation in accordance with EN14511
※ The real capacity would be changed according to the install environment.
11
EHS Mono
II. Specifications
2. Capacity Tables
2-1. AE050/090/120/140/160JXYDEH/EU (1 Phase)
3) Maximum Cooling Capacity
AE160JXYDEH/EU
AE140JXYDEH/EU
AE120JXYDEH/EU
AE090JXYDEH/EU
AE050JXYDEH/EU
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), CC (Cooling Capacity), PI (Power input)
LWE(℃)
7
10
13
15
18
25
Tamb(℃)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
10
4.21
0.90
4.54
0.90
4.87
0.90
5.20
0.90
5.54
0.90
6.09
0.92
20
4.05
1.02
4.37
1.02
4.69
1.02
5.01
1.02
5.33
1.02
5.86
1.04
30
3.88
1.14
4.19
1.14
4.50
1.14
4.80
1.14
5.11
1.14
5.62
1.17
35
3.80
1.21
4.10
1.21
4.40
1.21
4.70
1.21
5.00
1.21
5.50
1.23
46
3.62
1.34
3.91
1.34
4.19
1.34
4.48
1.34
4.77
1.34
5.24
1.36
LWE(℃)
7
10
13
15
18
25
Tamb(℃)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
10
6.09
1.39
6.64
1.41
7.18
1.44
7.55
1.46
8.09
1.49
8.82
1.52
20
5.86
1.57
6.40
1.60
6.95
1.63
7.31
1.65
7.86
1.67
8.58
1.71
30
5.62
1.76
6.16
1.78
6.71
1.81
7.07
1.83
7.62
1.86
8.35
1.89
35
5.50
1.85
6.05
1.88
6.59
1.90
6.95
1.92
7.50
1.95
8.23
1.99
46
5.24
2.05
5.78
2.08
6.33
2.11
6.69
2.13
7.24
2.15
7.97
2.19
LWE(℃)
7
10
13
15
18
25
Tamb(℃)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
10
9.97
2.37
10.79
2.37
11.61
2.37
12.15
2.37
12.97
2.37
14.06
2.37
20
9.58
2.69
10.40
2.69
11.22
2.69
11.77
2.69
12.58
2.69
13.67
2.69
30
9.19
3.00
10.01
3.00
10.83
3.00
11.38
3.00
12.19
3.00
13.29
3.00
35
9.00
3.16
9.82
3.16
10.64
3.16
11.18
3.16
12.00
3.16
13.09
3.16
46
8.57
3.51
9.39
3.51
10.21
3.51
10.75
3.51
11.57
3.51
12.66
3.51
LWE(℃)
7
10
13
15
18
25
Tamb(℃)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
10
10.76
2.62
11.66
2.63
12.56
2.64
13.16
2.65
14.06
2.67
15.26
2.68
20
10.33
2.95
11.23
2.96
12.13
2.98
12.73
2.99
13.63
3.00
14.83
3.02
30
9.91
3.28
10.81
3.30
11.71
3.31
12.31
3.32
13.21
3.33
14.41
3.35
35
9.70
3.45
10.60
3.46
11.50
3.48
12.10
3.49
13.00
3.50
14.20
3.52
46
9.24
3.82
10.14
3.83
11.04
3.84
11.64
3.85
12.54
3.87
13.74
3.89
LWE(℃)
7
10
13
15
18
25
Tamb(℃)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
10
11.54
2.85
12.52
2.88
13.50
2.90
14.15
2.92
15.14
2.94
16.44
2.98
20
11.08
3.21
12.06
3.24
13.04
3.26
13.70
3.28
14.68
3.30
15.99
3.34
30
10.63
3.57
11.61
3.60
12.59
3.62
13.25
3.64
14.23
3.66
15.54
3.69
35
10.40
3.75
11.38
3.77
12.36
3.80
13.02
3.82
14.00
3.84
15.31
3.87
46
9.90
4.14
10.88
4.17
11.86
4.19
12.52
4.21
13.50
4.23
14.81
4.27
1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C
3. Power input : Power input is according to Eurovent rating standard OM-3-2015.
4. Peak value : Tested without defrost operation in accordance with EN14511
5. Integrated value : Tested with defrost operation in accordance with EN14511
※ The real capacity would be changed according to the install environment.
12
EHS Mono
II. Specifications
2. Capacity Tables
2-2. AE090/120/140/160JXYDGH/EU (3 Phase)
1) Maximum Heating Capacity (Peak Value)
AE160JXYDGH/EU
AE140JXYDGH/EU
AE120JXYDGH/EU
AE090JXYDGH/EU
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input)
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
30
HC(kW)
6.30
9.03
8.49
8.23
8.32
9.45
10.38
11.93
13.48
35
PI(kW)
2.67
3.03
2.87
2.43
2.10
1.90
1.90
1.90
1.89
HC(kW)
6.00
8.60
8.08
7.84
7.92
9.00
9.89
11.36
12.84
PI(kW)
4.09
4.09
3.89
3.02
2.60
2.37
2.35
2.31
2.28
HC(kW)
9.35
11.80
11.09
10.45
10.56
12.00
13.25
15.32
17.40
PI(kW)
4.36
4.63
4.40
3.57
3.07
2.79
2.79
2.77
2.76
HC(kW)
9.65
12.80
12.03
12.20
12.32
14.00
14.92
16.46
18.00
PI(kW)
5.30
5.43
5.16
4.32
3.72
3.38
3.42
3.49
3.56
HC(kW)
11.30
14.40
13.54
13.94
14.08
16.00
17.38
19.69
22.00
30
HC(kW)
9.82
12.39
11.65
10.98
11.09
12.60
13.91
16.09
18.27
PI(kW)
4.60
4.60
4.37
3.39
2.93
2.66
2.64
2.60
2.56
HC(kW)
8.93
11.45
10.76
10.19
10.30
11.70
12.89
14.88
16.86
PI(kW)
4.90
5.20
4.94
4.01
3.45
3.14
3.13
3.12
3.10
HC(kW)
9.33
12.42
11.67
11.76
11.88
13.50
14.42
15.96
17.50
PI(kW)
5.95
6.10
5.80
4.85
4.18
3.80
3.85
3.92
4.00
HC(kW)
10.75
13.97
13.13
13.37
13.51
15.35
16.71
18.98
21.25
45
PI(kW)
3.20
3.59
3.41
2.89
2.49
2.27
2.29
2.30
2.35
HC(kW)
5.70
8.08
7.60
7.06
7.13
8.10
9.06
10.66
12.26
PI(kW)
4.90
5.14
4.88
3.90
3.36
3.06
3.02
2.92
2.88
HC(kW)
8.50
11.09
10.43
9.93
10.03
11.40
12.54
14.43
16.32
PI(kW)
5.20
5.59
5.31
4.52
3.90
3.55
3.52
3.41
3.38
HC(kW)
9.01
12.03
11.31
11.33
11.44
13.00
13.92
15.46
17.00
PI(kW)
6.25
6.67
6.34
5.36
4.62
4.20
4.25
4.26
4.36
HC(kW)
10.20
13.54
12.72
12.81
12.94
14.70
16.04
18.27
20.50
40
35
30
HC(kW)
11.87
15.12
14.21
14.64
14.78
16.80
18.25
20.68
23.10
HC(kW)
5.85
8.34
7.84
7.45
7.52
8.55
9.47
11.01
12.55
35
30
HC(kW)
10.13
13.44
12.63
12.81
12.94
14.70
15.67
17.28
18.90
40
PI(kW)
3.00
3.40
3.23
2.73
2.35
2.14
2.14
2.13
2.12
PI(kW)
HC(kW)
PI(kW)
7.84
7.22
6.70
6.77
8.05
8.61
10.13
11.65
3.97
4.04
3.43
2.96
2.68
2.75
2.85
2.95
7.28
6.84
6.35
6.42
8.00
8.15
9.59
11.03
4.35
4.49
3.81
3.29
2.96
3.05
3.16
3.27
PI(kW)
5.29
5.67
5.39
4.40
3.80
3.45
3.40
3.33
3.25
HC(kW)
PI(kW)
HC(kW)
PI(kW)
10.76
9.91
9.44
9.53
10.95
11.91
13.71
15.50
5.95
6.06
4.95
4.27
3.68
3.83
3.74
3.66
9.98
9.38
8.94
9.03
10.50
11.28
12.98
14.69
6.52
6.73
5.50
4.74
3.90
4.25
4.16
4.06
PI(kW)
5.59
5.99
5.69
5.04
4.35
3.95
3.90
3.81
3.73
HC(kW)
PI(kW)
HC(kW)
PI(kW)
11.67
10.74
10.76
10.87
12.63
13.23
14.69
16.15
6.28
6.40
5.67
4.89
4.20
4.39
4.29
4.20
10.83
10.18
10.19
10.30
12.25
12.53
13.92
15.30
6.88
7.11
6.30
5.43
4.45
4.87
4.77
4.66
PI(kW)
6.76
7.25
6.88
5.87
5.06
4.60
4.65
4.72
4.80
HC(kW)
PI(kW)
HC(kW)
PI(kW)
13.13
12.09
12.17
12.29
14.60
15.24
17.36
19.48
7.61
7.74
6.60
5.69
5.00
5.23
5.31
5.40
12.18
11.45
11.53
11.64
14.50
14.43
16.44
18.45
8.33
8.60
7.34
6.33
5.40
5.81
5.90
6.00
50
45
40
55
HC(kW)
45
40
35
50
PI(kW)
3.53
3.78
3.59
3.05
2.63
2.39
2.44
2.53
2.62
55
50
45
55
50
55
1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C
3. Power input : Power input is according to Eurovent rating standard OM-3-2015.
4. Peak value : Tested without defrost operation in accordance with EN14511
5. Integrated value : Tested with defrost operation in accordance with EN14511
※ The real capacity would be changed according to the install environment.
13
EHS Mono
II. Specifications
2. Capacity Tables
2-2. AE090/120/140/160JXYDGH/EU (3 Phase)
2) Maximum Heating Capacity (Integrated Value)
AE160JXYDGH/EU
AE140JXYDGH/EU
AE120JXYDGH/EU
AE090JXYDGH/EU
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), HC (Heating Capacity), PI (Power input)
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
LWE(℃)
Tamb(℃)
-20
-10
-7
-2
2
7
10
15
20
30
HC(kW)
5.99
7.50
7.98
7.67
7.35
9.45
10.38
11.93
13.48
35
PI(kW)
2.72
2.80
2.83
2.45
2.07
1.90
1.90
1.90
1.89
HC(kW)
5.70
7.14
7.60
7.30
7.00
9.00
9.89
11.36
12.84
PI(kW)
3.37
3.48
3.52
3.07
2.63
2.37
2.35
2.31
2.28
HC(kW)
7.73
9.68
10.30
10.05
9.80
12.00
13.25
15.32
17.40
PI(kW)
3.61
3.72
3.76
3.41
3.06
2.79
2.79
2.77
2.76
HC(kW)
8.10
10.15
10.80
11.00
11.20
14.00
14.92
16.46
18.00
PI(kW)
4.63
4.78
4.82
4.21
3.59
3.38
3.42
3.49
3.56
HC(kW)
10.05
12.60
13.40
12.95
12.50
16.00
17.38
19.69
22.00
30
HC(kW)
8.11
10.17
10.82
10.55
10.29
12.60
13.91
16.09
18.27
PI(kW)
3.79
3.91
3.95
3.45
2.95
2.66
2.64
2.60
2.56
HC(kW)
7.38
9.25
9.85
9.87
9.90
11.70
12.89
14.88
16.86
PI(kW)
4.05
4.18
4.22
3.83
3.44
3.14
3.13
3.12
3.10
HC(kW)
8.06
10.11
10.75
10.96
11.18
13.50
14.42
15.96
17.50
PI(kW)
5.20
5.37
5.42
4.73
4.03
3.80
3.85
3.92
4.00
HC(kW)
10.09
12.64
13.45
12.49
11.53
15.35
16.71
18.98
21.25
45
PI(kW)
3.21
3.31
3.34
2.90
2.47
2.27
2.29
2.30
2.35
HC(kW)
5.36
6.72
7.15
6.83
6.50
8.10
9.06
10.66
12.26
PI(kW)
4.17
4.30
4.34
3.86
3.38
3.06
3.02
2.92
2.88
HC(kW)
7.04
8.83
9.39
9.70
10.00
11.40
12.54
14.43
16.32
PI(kW)
4.75
4.89
4.94
4.45
3.97
3.55
3.52
3.41
3.38
HC(kW)
8.03
10.06
10.70
10.93
11.15
13.00
13.92
15.46
17.00
PI(kW)
5.88
6.05
6.11
5.13
4.15
4.20
4.25
4.26
4.36
HC(kW)
10.13
12.69
13.50
12.03
10.55
14.70
16.04
18.27
20.50
40
35
30
HC(kW)
10.55
13.23
14.07
13.60
13.13
16.80
18.25
20.68
23.10
HC(kW)
5.53
6.93
7.38
7.06
6.75
8.55
9.47
11.01
12.55
35
30
HC(kW)
8.51
10.66
11.34
11.55
11.76
14.70
15.67
17.28
18.90
40
PI(kW)
3.05
3.15
3.18
2.76
2.33
2.14
2.14
2.13
2.12
PI(kW)
HC(kW)
PI(kW)
6.38
6.53
6.48
6.18
8.05
8.61
10.13
11.65
3.90
3.60
3.43
2.93
2.68
2.75
2.85
2.95
6.05
5.90
6.14
5.85
8.00
8.15
9.59
11.03
4.33
3.70
3.81
3.25
2.96
3.05
3.16
3.27
PI(kW)
4.54
4.68
4.73
4.27
3.80
3.45
3.40
3.33
3.25
HC(kW)
PI(kW)
HC(kW)
PI(kW)
8.39
8.93
9.21
9.50
10.95
11.91
13.71
15.50
5.27
5.12
4.80
4.28
3.68
3.83
3.74
3.66
7.94
8.47
8.73
9.00
10.50
11.28
12.98
14.69
5.85
5.51
5.33
4.75
3.90
4.25
4.16
4.06
PI(kW)
5.42
5.59
5.65
5.08
4.50
3.95
3.90
3.81
3.73
HC(kW)
PI(kW)
HC(kW)
PI(kW)
9.56
10.35
10.38
10.59
12.63
13.23
14.69
16.15
6.29
5.78
5.71
5.06
4.20
4.39
4.29
4.20
9.05
10.00
9.83
10.04
12.25
12.53
13.92
15.30
6.99
5.90
6.34
5.63
4.45
4.87
4.77
4.66
PI(kW)
6.53
6.73
6.80
5.54
4.27
4.60
4.65
4.72
4.80
HC(kW)
PI(kW)
HC(kW)
PI(kW)
12.06
12.65
11.42
10.02
14.60
15.24
17.36
19.48
7.57
6.90
6.23
4.80
5.00
5.23
5.31
5.40
11.42
11.80
10.82
9.50
14.50
14.43
16.44
18.45
8.42
7.00
6.92
5.34
5.40
5.81
5.90
6.00
50
45
40
55
HC(kW)
45
40
35
50
PI(kW)
3.36
3.47
3.50
3.05
2.60
2.39
2.44
2.53
2.62
55
50
45
55
50
55
1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C
3. Power input : Power input is according to Eurovent rating standard OM-3-2015.
4. Peak value : Tested without defrost operation in accordance with EN14511
5. Integrated value : Tested with defrost operation in accordance with EN14511
※ The real capacity would be changed according to the install environment.
14
EHS Mono
II. Specifications
2. Capacity Tables
2-2. AE090/120/140/160JXYDGH/EU (3 Phase)
3) Maximum Cooling Capacity
AE160JXYDGH/EU
AE140JXYDGH/EU
AE120JXYDGH/EU
AE090JXYDGH/EU
LWT (Leaving Water Temp.), Tamb (Ambient Temp.), CC (Cooling Capacity), PI (Power input)
LWE(℃)
7
10
13
15
18
25
Tamb(℃)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
10
6.09
1.19
6.50
1.41
6.91
1.44
7.18
1.46
7.59
1.49
8.14
1.55
20
5.86
1.23
6.27
1.60
6.67
1.63
6.95
1.65
7.36
1.67
7.90
1.74
30
5.62
1.24
6.03
1.78
6.44
1.81
6.71
1.83
7.12
1.86
7.66
1.92
35
5.50
1.94
5.91
1.88
6.32
1.90
6.59
1.92
7.00
1.92
7.55
2.01
46
5.24
1.24
5.65
2.08
6.06
2.11
6.33
2.13
6.74
2.15
7.28
2.22
LWE(℃)
7
10
13
15
18
25
Tamb(℃)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
10
9.97
2.37
10.79
2.37
11.61
2.37
12.15
2.37
12.97
2.37
14.06
2.37
20
9.58
2.69
10.40
2.69
11.22
2.69
11.77
2.69
12.58
2.69
13.67
2.69
30
9.19
3.00
10.01
3.00
10.83
3.00
11.38
3.00
12.19
3.00
13.29
3.00
35
9.00
3.16
9.82
3.16
10.64
3.16
11.18
3.16
12.00
3.16
13.09
3.16
46
8.57
3.51
9.39
3.51
10.21
3.51
10.75
3.51
11.57
3.51
12.66
3.51
LWE(℃)
7
10
13
15
18
25
Tamb(℃)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
10
10.76
2.62
11.66
2.63
12.56
2.64
13.16
2.65
14.06
2.67
15.26
2.68
20
10.33
2.95
11.23
2.96
12.13
2.98
12.73
2.99
13.63
3.00
14.83
3.02
30
9.91
3.28
10.81
3.30
11.71
3.31
12.31
3.32
13.21
3.33
14.41
3.35
35
9.70
3.45
10.60
3.46
11.50
3.48
12.10
3.49
13.00
3.50
14.20
3.52
46
9.24
3.82
10.14
3.83
11.04
3.84
11.64
3.85
12.54
3.87
13.74
3.89
LWE(℃)
7
10
13
15
18
25
Tamb(℃)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
CC(kW)
PI(kW)
10
11.54
2.85
12.52
2.88
13.50
2.90
14.15
2.92
15.14
2.94
16.44
2.98
20
11.08
3.21
12.06
3.24
13.04
3.26
13.70
3.28
14.68
3.30
15.99
3.34
30
10.63
3.57
11.61
3.60
12.59
3.62
13.25
3.64
14.23
3.66
15.54
3.69
35
10.40
3.75
11.38
3.77
12.36
3.80
13.02
3.82
14.00
3.84
15.31
3.87
46
9.90
4.14
10.88
4.17
11.86
4.19
12.52
4.21
13.50
4.23
14.81
4.27
1. Heating capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for heated water range △t = 3∼8°C
2. Cooling capacity : Capacity is according to Eurovent rating standard OM-3-2015 and valid for chilled water range △t = 3∼8°C
3. Power input : Power input is according to Eurovent rating standard OM-3-2015.
4. Peak value : Tested without defrost operation in accordance with EN14511
5. Integrated value : Tested with defrost operation in accordance with EN14511
※ The real capacity would be changed according to the install environment.
15
EHS Mono
II. Specifications
3. Dimensional Drawings
3-1. Outdoor Unit
1) AE050JXYD*H/EU
(Unit : mm)
①
②
③
No.
Table of Descriptions
①
Water Pipe(Out)
②
Water Pipe(In)
③
Power & Communication Wiring Conduits
16
EHS Mono
II. Specifications
3. Dimensional Drawings
3-1. Outdoor Unit
2) AE090JXYD*H/EU
(Unit : mm)
No.
Table of Descriptions
①
Water Pipe(Out)
②
Water Pipe(In)
③
Power & Communication Wiring Conduits
17
EHS Mono
II. Specifications
3. Dimensional Drawings
3-1. Outdoor Unit
3) AE120/140/160JXYD*H/EU
No.
Table of Descriptions
①
Water Pipe(Out)
②
Water Pipe(In)
③
Power & Communication Wiring Conduits
(Unit : mm)
18
EHS Mono
II. Specifications
3. Dimensional Drawings
3-2. Control Kit
1) MIM-E03A(B)N
(Unit : mm)
342
371
2-R2.5
2-R4.0
2-R3.0
23
87
110
290
①
No.
Table of Descriptions
①
Conduit for Wiring (Rubber)
19
EHS Mono
II. Specifications
4. Piping Diagrams
4-1. AE050JXYDEH/EU
4-2. AE090JXYD*H/EU
20
EHS Mono
4. Piping Diagrams
4-3. AE120/140/160JXYD*H/EU
II. Specifications
EHS Mono
II. Specifications
5. Wiring Diagrams
5-1. Outdoor Unit
1) AE050JXYDEH/EU
22
EHS Mono
II. Specifications
5. Wiring Diagrams
5-1. Outdoor Unit
2) AE090~160JXYDEH/EU
23
EHS Mono
II. Specifications
5. Wiring Diagrams
5-1. Outdoor Unit
3) AE090~160JXYDGH/EU
24
EHS Mono
II. Specifications
5. Wiring Diagrams
5-2. Control Kit
1) MIM-E03A(B)N
25
EHS Mono
II. Specifications
6. Electric Specifications
6-1. Outdoor Unit
Voltage Range
Rated
Product
Mono
MCA
MFA
264
20.0
25.0
198
264
22.0
27.5
220-240
198
264
28.0
35.0
50
220-240
198
264
30.0
37.5
AE160JXYDEH/EU
50
220-240
198
264
32.0
40.0
AE090JXYDGH/EU
50
380-415
342
457
10.0
16.1
AE120JXYDGH/EU
50
380-415
342
457
10.0
16.1
AE014JXYDGH/EU
50
380-415
342
457
12.0
16.1
AE160JXYDGH/EU
50
380-415
342
457
12,0
16.1
Model Name
Hz
Volts
Min.
Max.
AE050JXYDEH/EU
50
220-240
198
AE090JXYDEH/EU
50
220-240
AE120JXYDEH/EU
50
AE014JXYDEH/EU
※ Notes
1. The power cable is not supplied with air conditioner.
2. Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord.
(Code designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
3. This Equipment complies with IEC 61000-3-12.
※ Abbreviations
1. MCA : Min. Circuit Amps. (A)
2. MFA : Max. Fuse Amps. (A)
6-2. Control Kit
Product
Model Name
Load
Power supply
No Heater
(Water Pump, Valve, Wired RMC)
Control
Kit
MIM-E03AN
MIM-E03BN
Booster Heater (3kW)
1Φ, 220~240V,
50Hz
Booster Heater (~3kW)
+ Backup Heater (~3kW)
Power cable
Max. Length
Type GL
mm , wires
m
A
1.5 / 3
< 10m
10
2.5 / 3
10m < L< 20m
10
4.0 / 3
< 10m
20
6.0 / 3
10m < L< 20m
20
4.0 / 3
< 10m
40
6.0 / 3
10m < L< 20m
40
2
※ Notes
1. The power cable is not supplied with the heat pump.
2. For power cable, use the grade H07RN-F materials in 1Ø system.
3. If you connect Backup Heater at separated power cable, you can reduce wire size.
(Please refer to indoor unit installation manual)
26
EHS Mono
II. Specifications
7. Sound Pressure Level
7-1. Operation Sound Level
Unit (dB(A))
Model
Heating
Cooling
AE050JXYDEH/EU
45
45
AE090JXYDEH/EU
48
48
AE090JXYDGH/EU
48
48
7-2. NC Curve
1) AE050JXYDEH/EU
2) AE090JXYDEH/EU
1) AE090JXYDGH/EU
※ Notes
1. These operation values were obtained in an anechoic room. Sound pressure level will vary depending on
a range of factors such as the construction of the particular room where the equipment is installed.
2. Operation sound level may differ depending on operation and ambient conditions.
27
EHS Mono
II. Specifications
7. Sound Pressure Level
7-1. Operation Sound Level
Unit (dB(A))
Model
Heating
Cooling
AE120JXYDEH/EU
50
50
AE120JXYDGH/EU
50
50
AE140JXYDEH/EU
51
52
AE140JXYDGH/EU
51
52
7-2. NC Curve
1) AE120JXYDEH/EU
2) AE120JXYDGH/EU
3) AE140JXYDEH/EU
4) AE140JXYDGH/EU
※ Notes
1. These operation values were obtained in an anechoic room. Sound pressure level will vary depending on
a range of factors such as the construction of the particular room where the equipment is installed.
2. Operation sound level may differ depending on operation and ambient conditions.
28
EHS Mono
II. Specifications
7. Sound Pressure Level
7-1. Operation Sound Level
Unit (dB(A))
Model
Heating
Cooling
AE160JXYDEH/EU
52
54
AE160JXYDGH/EU
52
54
7-2. NC Curve
1) AE160JXYDEH/EU
2) AE160JXYDGH/EU
※ Notes
1. These operation values were obtained in an anechoic room. Sound pressure level will vary depending on
a range of factors such as the construction of the particular room where the equipment is installed.
2. Operation sound level may differ depending on operation and ambient conditions.
29
EHS Mono
II. Specifications
8. Operation Range
8-1. Outdoor Unit
1) Cooling
2) Heating
Outdoor temp. (℃, DB)
35
Outdoor temp. (℃, DB)
46
10
Backup heater operation only.
(No heat-pump operation).
-10
-25
5
25
Leaving water temp. (℃)
Outdoor Unit
Controller
Cooling
Heating
15 25
40
55
Leaving water temp. (℃)
Water Temp. (℃)
Water Flow Rates (LPM)
Min
Std
Max
Cooling
5
-
25
Heating
15
-
55
Inlet
-
23 (12*3)
30
Outlet
5
18 (7*3)
25
Inlet
5
(40*3)
Outlet
25(15*4)
30
35 (45*3)
-
Min
16 (7*1)
Std
(Δ 5℃)
55
Max
Air Temp. (℃, DB/WB)
Min
Std
Max
10/-
35/24
46/27
-25/-
7/6
35/24
58 (42*2)
*1) Figures in brackets are for 5kW model.
*2) Figures in brackets are for 5kW/9kW models.
*3) Figures in brackets are based on Eurovent Test Condition #2
*4) Figures in brackets are based on back up heater operation only.
3) DHW (Domestic Hot Water Tank)
Outdoor temp. (℃, DB)
43
35
Booster heater operation only.
-10
-25
70
25
32
50
DHW Tank temp. (℃)
※ Special condition( 35℃ < Outdoor temp. ≤ 43℃) is operated by only Booster Heater.
SAMSUNG doesn’t supply DHW for EHS Mono.
Since it is a reference data, you have to check DHW operation range for yours.
30
EHS Mono
II. Specifications
9. Hydraulic Performance
9-1. Correction Graph
1) AE050/090JXYD*H/EU
2) AE120/140/160JXYD*H/EU
9-2. Capacity Correction
1) Heating
2) Cooling
※ Notes
1. To ensure correct operation and predict the expected performance, this graph can be used.
2. Flow and resistance characteristic is dependent on anti-freezer concentration.
3. Tested with Ethylene Glycol.
※ Abbreviations
1. EG : Ethylene Glycol
31
III. Application
1. Application Examples
EHS Mono
III. Application
1. Application Examples
1-1. Outdoor Unit + Control Kit
2) Outdoor Unit + Cylinder Unit
33
SI\ MSUNG
Samsung E뻐ctronics Co., LTD.
B2B PM/SE
'!'.r./'암
현
SI\ MSUNG