Για βιομηχανικο�ς χώ�ους

Industrial and Service Sector
Samurai Technology
246
Samurai
Absorption Chiller-Heaters
248
258
245
Industrial and Service Sector
Features
advantages
Samuraiand
Technology
The range of HITACHI Samurai chillers addresses the needs of air conditioning applications,
or industrial process refrigeration.
Samurai Chillers and Heat Pumps
RCME
40~480AH5
Type of condensation
RCU2E 40~400AG2 RHU2E 40~240AG2
RCUE 40~240WG2
RCUE 40~120CLG2
Air
Air
Air
Water
Without Condensate
Operating mode
Cold Only
Cold Only
Heat pump
Cold and
Heat pump
Cold Only
Cooling Power kW
106 - 1280
112 - 1030
106 - 585
134 - 696
120 - 360
Heating Power kW
-
-
110 - 555
161 - 824
-
R134A
R407C
R407C
R407C
R407C
Double Screw
Double Screw
Double Screw
Double Screw
Double Screw
Refrigerant Gas
Type of Compressor
Solidity and long duration
Semi-Hermetic Double Screw Compressor
The Semi-Hermetic Double Screw
Compressor has been designed to
operate with refrigerant R407C.
It is directly coupled to the electrical
motor, with no external connections,
reducing the number of internal and
external components.
The lubricant oil is continuously delivered by
pressure difference to moving mechanical
parts and power regulation piston.
This system removes the need for an
external oil pump, valves, and associated
control mechanisms.
The new Ciclonic oil separator is inside the
compressor’s shell.
No external oil connecting pipes are needed,
which results in a compact design and high
compressor reliability.
In order to assure compliance with
the specifications, Samurai chillers
undergo a number of tests in the various
production stages:
The compressor is mounted on vibrations
damper pads and is hermetically insulated.
As optional, the compressor housing can be
insulated with a double HITACHI patented
liner, able to further reduce noise emissions.
> Electrical and operation tests,
> Pressure and leak check test.
The new Cyclone oil separator is located
inside the casing of the compressor.
At the end of the production cycle a mechanical seal test is performed on the whole circuit, 16 critical chilling points and all
welding points are checked. Before delivery, HITACHI performs a Run Test, connecting the Chiller both electrically and on the
water side, testing all system variables, to assure correct Samurai operation.
246
Industrial and Service Sector
Samurai Chillers and Heat Pumps
Power (kW)
NEW
100
200
500
1,000
2,500
5,000
Air cooled chiller
Cooler Only R134A Modular
RCME40~480AH5
106 kW ~ 1280 kW
Air cooled chiller
Cold Only
RCU2E 40~400AG2
112 kW ~ 1030 kW
Air Cooled Chiller
Heat pump
RHU2E 40~240AG2
Water Cooled Chiller
Cooler Only and Heat Pump
RCUE 40~240WG2
134 kW ~ 696 kW
Condenser-less Chiller
Cold Only
RCUE 40~120CLG2
134 kW ~ 696 kW
106 kW ~ 585 kW
10,000
Industrial and Service Sector
Samurai
Cooling Only I Air Cooled
NEW
RCU2E-40~400 AG2
R efrigerant Gas R134a
C
ontinuous adjustment from 25 to
100% of compressor capacity
Control on water output
H
igh Performance : EER > 3,52
and ESEER > 5.34 (depending on model)
U p to 8 independent circuits
Low
noise level
ICHIBAN Screw compressor
E xclusive modular concept: Possibility
to request delivery of assembled and
connected (electrically and hydraulically)
modules from the factory.
WIDE POWER RANGE FROM 40HP
TO 480HP (106 KW TO 1280 KW)
HIGH PERFORMANCE TECHNOLOGY
REFRIGERANT GAS R134A
EER
ESEER
3.52 5.34
P ossibility to have factory installed pumps
L CD Control Panel
C
ontrol option via LonWorks or Modbus
protocols through specific interfaces.
248
Industrial and Service Sector
NEW
HIGH EFFICIENCY COOLER ONLY CHILLER
RCME40AH
Modules
RCME50AH
1 × RCME40AH
1 × RCME50AH
RCME60AH
RCME80AH
1 × RCME60AH
2 × RCME40AH
RCME100AH
RCME120AH3
2 × RCME50AH
3 × RCME40AH
Cooling Power
kW
106.00
132.00
160.00
212.00
264.00
318.00
Input Power
kW
30.10
38.30
49.10
60.20
76.60
90.30
Sound level (1.5 m)
Dimensions (H × L × D) (1)
Weight (2)
dB(A)
64
65
66
-
2450 × 2000 × 2000
mm
kg
1 500
-
2450 × 6000 × 2000
3 000
4 500
2
3
1 580
Power Control
-
2450 × 4000 × 2000
25 ~ 100
Number of Independent circuits
1
Temp. Water output
°C
+5°C ~ +15°C
Temp. Condenser air inflow
°C
-15°C / +46°C
HIGH EFFICIENCY COOLER ONLY CHILLER
Modules
RCME120AH2
RCME150AH
RCME160AH
RCME180AH
RCME200AH4
RCME200AH5
2 × RCME60AH
3 × RCME50AH
4 × RCME40AH
3 × RCME60AH
4 × RCME50AH
5 × RCME40AH
Cooling Power
kW
320.00
396.00
424.00
480.00
528.00
530.00
Input Power
kW
98.20
114.90
120.40
147.30
153.20
383.00
dB(A)
-
-
-
-
-
-
Sound level (1.5 m)
Dimensions (H × L × D) (1)
Weight (2)
mm
kg
2450 × 4000 × 2000 2450 × 6000 × 2000 2450 × 8000 × 2000 2450 × 6000 × 2000 2450 × 8000 × 2000 2450 × 10000 × 2000
3 160
4 500
6 000
Power Control
4 740
3 160
7 500
3
4
5
25 ~ 100
Number of Independent circuits
2
3
4
Temp. Water output
°C
+5°C ~ +15°C
Temp. Condenser air inflow
°C
-15°C / +46°C
HIGH EFFICIENCY COOLER ONLY CHILLER
Modules
RCME240AH6
RCME240AH4
RCME250AH
RCME280AH
RCME300AH6
RCME300AH5
6 × RCME40AH
4 × RCME60AH
5 × RCME50AH
7 × RCME40AH
6 × RCME50AH
5 × RCME60AH
Cooling Power
kW
636.00
640.00
660.00
742.00
792.00
800.00
Input Power
kW
180.60
196.40
191.50
210.70
229.80
245.50
dB(A)
-
-
-
-
-
-
mm
2450 × 12000 × 2000
2450 × 8000 × 2000
kg
9 000
6 320
Sound level (1.5 m)
Dimensions (H × L × D) (1)
Weight (2)
2450 × 10000 × 2000 2450 × 14000 × 2000 2450 × 12000 × 2000 2450 × 10000 × 2000
7 500
Power Control
10 500
9 000
7 900
7
6
5
25 ~ 100
Number of Independent circuits
6
4
5
Temp. Water output
°C
+5°C ~ +15°C
Temp. Condenser air inflow
°C
-15°C / +46°C
HIGH EFFICIENCY COOLER ONLY CHILLER
RCME320AH
RCME350AH
RCME360AH
RCME400AH
RCME420AH
RCME480AH
8 × RCME40AH
7 × RCME50AH
6 × RCME60AH
8 × RCME50AH
7 × RCME60AH
8 × RCME60AH
Cooling Power
kW
848.00
924.00
960.00
1 056.00
1 120.00
1 280.00
Input Power
kW
240.80
268.10
294.60
306.40
343.70
392.80
dB(A)
-
-
-
-
-
-
Modules
Sound level (1.5 m)
Dimensions (H × L × D) (1)
Weight (2)
mm
kg
2450 × 16000 × 2000 2450 × 14000 × 2000 2450 × 12000 × 2000 2450 × 16000 × 2000 2450 × 14000 × 2000 2450 × 16000 × 2000
16 000
10 500
9 480
Power Control
12 000
11 060
12 640
8
7
8
25 ~ 100
Number of Independent circuits
8
7
6
Temp. Water output
°C
+5°C ~ +15°C
Temp. Condenser air inflow
°C
-15°C / +46°C
Module (1) Outer casing (2) not connected
249
Industrial and Service Sector
Samurai
Cooling Only I Air Cooled
RCU2E-40~400 AG2
WIDE POWER RANGE FROM 40HP
TO 400HP (112KW TO 1030 KW)
HIGH TECHNOLOGY PERFORMANCE
OF DOUBLE SCREW COMPRESSORS
250
CONTINUOUS CAPACITY CONTROL
which affords between 15 and 20% reduction in energy consumption compared to step
control systems.
PRECISE CONTROL OF WATER OUTPUT
TEMPERATURE
capacity per square metre of occupied surface.
EXCELLENT PERFORMANCE AT PARTIAL
LOADS
LOW NOISE LEVEL
HITACHI makes full use of its high technology
to obtain extremely low sound emissions. The
two-blade Inverter control fan further reduces
the sound emission level, increasing the air
volume, at the same time as reducing electrical absorption.
DOUBLE SCREW COMPRESSOR
RECOVERY SYSTEM (Optional)
By ordering the Recovery option with plate
exchanger, it is possible to recover about
30% of power output in cooling mode, heating water in a dedicated circuit, with output
temperatures up to 70°C, at peak operating
conditions.
HIGHLY RELIABLE WITH EXTREMELY LOW
NOISE AND VIBRATION
REDUCED INSTALLATION SPACE
Thanks to painstaking design of each component, it is possible to achieve high cooling
Industrial and Service Sector
COOLING ONLY
RCU2E 40AG2 RCU2E 50AG2 RCU2E 60AG2 RCU2E 70AG2 RCU2E 80AG2 RCU2E 100AG2 RCU2E 120AG2 RCU2E 140AG2
Cool. Capacity
kW
112
130
156
178
206
260
Cool. Input Power
312
356
kW
38.60
44.70
53.00
61.00
70.00
89.40
106
122
EER
-
2.90
2.91
2.94
2.92
2.94
2.91
2.94
2.92
ESEER
-
3.48
3.49
3.52
3.50
3.52
3.49
3.52
Dimensions (H x L x D)
Weight
mm
kg
2430 x 2190 x 1900
1,430
1,470
2430 x 2790 x 1900
1,560
1,760
Capacity Control
Capacity Variation
2,830
3,000
3,420
2
2
2
86
87
88
Continuous Control
%
Number of Compressors
15% ~ 100%
1
Cool. Water Output Temperature
°C
Air Input Temperature
Condenser
°C
Sound Power Level
1,820
2430 x 4090 x 1900
3.50
2430 x 5290
x 1900
dB(A)
1
1
1
1
(-10 ˚C Optional) +5°C~ +15°C
-15°C + 46°C
82
83
84
85
85
COOLING ONLY
RCU2E 160AG2 RCU2E 180AG2 RCU2E 210AG2 RCU2E 240AG2 RCU2E 280AG2 RCU2E 320AG2 RCU2E 360AG2 RCU2E 400AG2
Cool. Capacity
kW
412
468
534
618
712
824
890
1030
Cool. Input Power
kW
140
159
183
210
244
280
305
350
EER
-
2.94
2.94
2.92
2.94
2.92
2.94
2.92
2.94
ESEER
-
3.52
3.52
3.50
3.52
3.50
3.52
3.50
3.52
mm
2,430 x 5,290
x 1,900
2,430 x 5,990
x 1,900
kg
3,550
4,450
Dimensions (H x L x D)
Weight
2,430 x 1,900 x 7,790
2,430 x 10,290 x 1,900
2,430 x 12,790 x 1900
5,070
6,750
7,000
8,450
8,750
4
5
5
92
94
94
Capacity Control
Capacity Variation
Continuous Control
%
Number of Compressors
15% ~ 100%
2
Cool. Water Output Temperature
°C
Air Input Temperature
Condenser
°C
Sound Power Level
5,250
dB(A)
3
3
3
4
(-10 ˚C Optional) +5°C~ +15°C
-15°C + 46°C
88
89
91
NOTES:
1 Nominal cooling capacity is based on European Standard EN14511.
Cooled water input/output temperature 12/7 °C, Temp. External Air = 35°C.
2 Sound power values have been calculated according to the EUROVENT test.
Measurement taken at 1 m from the surface of the control panel and 1.5 m height
from floor level.
91
92
The above data have been measured in an anechoic chamber, and do not take into
account the reflected sound in the field.
Operative conditions:
Standard models: Chilled water input/output temperature 12/7 °C, Condensation
Temperature 45°C.
- Low output temperature applications are not standard.
- High condensation temperature applications are not standard.
251
Industrial and Service Sector
Samurai
Heat pump I Air cooled
RH2UE-40 240AG2
WIDE POWER RANGE FROM 40HP A
TO 240 HP (106 TO 585KW)
HIGH PERFORMANCE
TECHNOLOGY OF DOUBLE SCREW
COMPRESSORS
252
CONTINUOUS CAPACITY CONTROL
which affords between 15 and 20% reduction in energy consumption compared to step
control systems.
PRECISE CONTROL OF WATER OUTPUT
TEMPERATURE
LOW NOISE LEVEL
HITACHI makes full use of its high technology
to obtain extremely low sound emissions. The
two-blade Inverter control fan further reduces
the sound emission level, increasing the air
volume, at the same time as reducing electrical absorption.
DOUBLE SCREW COMPRESSOR
EXCELLENT PERFORMANCE AT PARTIAL
LOADS
HIGHLY RELIABLE WITH EXTREMELY LOW
NOISE AND VIBRATION
REDUCED INSTALLATION SPACE
Thanks to painstaking design of each component, it is possible to achieve high cooling
capacity per square metre of occupied surface.
RECOVERY SYSTEM (Optional)
By ordering the Recovery option with plate
exchanger, it is possible to recover about
30% of power output in cooling mode, heating water in a dedicated circuit, with output
temperatures up to 70°C, at peak operating
conditions.
Industrial and Service Sector
HEAT PUMP
RHU2E40AG2
RHU2E50AG2
RHU2E60AG2
RHU2E70AG2
RHU2E80AG2
kW
106
123
148
169
195
246
42.70
52.00
60.00
70.00
85.40
MODEL
Cool. Capacity
Cool. Input Power
RHU2E100AG2
kW
37.90
EER
-
2.80
2.88
2.85
2.82
2.79
2.88
ESEER
-
3.36
3.45
3.42
3.38
3.34
3.45
Heat. Capacity
kW
110
127
152
185
185
254
Heat. Input Power
kW
40.70
44.50
54.00
68.00
68.00
89.00
-
2.70
2.85
2.81
2.72
2.72
2.85
1,670
1,880
COP
Dimensions (H x L x D)
Weight
mm
kg
2430 x 2190 x 1900
1,550
1,600
2430 x 2790 x 1900
Capacity Control
Capacity Variation
2430 x 4090 x 1900
1,950
3,050
1
2
85
85
86
Continuous Control
%
Number of Compressors
15 ~ 100
1
Cool. Water Output Temperature
°C
Heat. Water Output Temperature
Air Input Temperature
Condenser
Air Temperature
Evaporator Input
Sound Power Level
°C
1
1
(-10 ˚C Optional) +5°C~ +15°C
+35°C ~ +55°C
°C
-15°C + 46°C In Cooling
°C
dB(A)
1
-9.5°C + 21°C(DB)
82
83
-10°C + 15.5°C (WB) In Heating
84
HEAT PUMP
RHU2E120AG2
RHU2E140AG2
RHU2E160AG2
RHU2E180AG2
RHU2E210AG2
RHU2E240AG2
Cool. Capacity
kW
296
338
390
444
507
585
Cool. Input Power
kW
104
120
140
156
180
210
EER
-
2.85
2.82
2.79
2.85
2.82
2.79
ESEER
-
3.42
3.38
3.34
3.42
3.38
3.34
Heat. Capacity
kW
304
370
370
456
555
555
Heat. Input Power
kW
108
136
136
162
204
204
-
2.81
2.72
2.72
2.81
2.72
2.72
mm
2430 x 4090 x 1900
kg
3,250
MODEL
COP
Dimensions (H x L x D)
Weight
2430 x 5290 x 1900
3,670
2430 x 5990 x 1900
3,780
Capacity Control
Capacity Variation
Number of Compressors
Cool. Water Output
Temperature
Heat. Water Output
Temperature
Air Input Temperature
Condenser
Air Temperature
Evaporator Input
Sound Power Level
4,780
2430 x 7790 x 1900
5,440
5,650
3
3
91
91
Continuous Control
%
15 ~ 100
2
2
2
3
°C
(-10 ˚C Optional) +5°C~ +15°C
°C
+35°C ~ +55°C
°C
-15°C + 46°C In Cooling
°C
dB(A)
-9.5°C + 21°C (DB)
87
88
NOTES:
1 Nominal cooling capacity is based on European Standard EN14511.
Cooled water input/output temperature 12/7 °C, Temp. External Air = 35°C.
2 Sound power values have been calculated according to the EUROVENT test.
Measurement taken at 1 m from the surface of the control panel and 1.5 m height
from floor level.
88
-10°C + 15.5°C (WB) In Heating
89
The above data have been measured in an anechoic chamber, and do not take into
account the reflected sound in the field.
Operative conditions:
Standard models: Chilled water input/output temperature 12/7 °C, Condensation
Temperature 45°C.
- Low output temperature applications are not standard.
- High condensation temperature applications are not standard.
253
Industrial and Service Sector
Samurai
Cooling Only and Heat Pump I Water Cooled
RCUE-40~240WG2
WIDE POWER RANGE
FROM 40HP TO 240 HP (106 TO 585KW)
HIGH TECHNOLOGY PERFORMANCE
OF DOUBLE SCREW COMPRESSORS
CONTINUOUS CAPACITY CONTROL
which affords between 15 and 20% reduction in energy consumption compared to step
control systems.
LOW NOISE LEVEL
PRECISE CONTROL OF WATER OUTPUT
TEMPERATURE
EXCELLENT PERFORMANCE AT PARTIAL
LOADS
DOUBLE SCREW COMPRESSOR
254
HIGHLY RELIABLE WITH EXTREMELY LOW
NOISE AND VIBRATION
REDUCED INSTALLATION SPACE
Thanks to painstaking design of each component, it is possible to achieve high cooling capacity per square metre of occupied surface.
POSSIBILITY TO OPERATE IN
HEATING MODE (Optional)
By inverting plumbing connections and additional control.
Industrial and Service Sector
COOLING ONLY AND HEAT PUMP*2
Model
RCUE40WG2
RCUE50WG2
RCUE60WG2
RCUE80WG2
RCUE100WG2
Cool. Capacity*
kW
134
160
194
232
320
Cool. Input Power*1
kW
33.50
40.00
49.10
54.50
80
EER
-
4.00
4.00
3.95
4.26
4.00
ESEER
-
4.52
4.52
4.46
4.81
4.52
kW
161.10
192.30
233.90
274.70
384.70
Heat. Input Power*
kW
39.80
47.50
58.30
64.70
Dimensions (H x L x D)
mm
Weight
kg
1
Heat. Capacity*
2
2
1520 x 1105 x 850
750
765
830
Capacity Control
95
1700 x 1105 x 1465
950
1,570
1
2
71
72
RCUE200WG2
RCUE240WG2
Continuous Control
Capacity Variation
%
Number of Compressors
15 ~ 100
1
1
1
Cool. Water Output Temperature
°C
(-10 ˚C Optional) +5°C~ +15°C
Heat. Water Output Temperature
°C
+35°C ~ +45°C ~ (55°C)
Sound Power Level
dB(A)
68
69
71
COOLING ONLY AND HEAT PUMP*2
RCUE120WG2
RCUE150WG2
RCUE180WG2
Cool. Capacity*
kW
388
445
525
600
696
Cool. Input Power*1
kW
104.50
104.50
123.00
149.00
163.00
EER
-
3.95
4.28
4.27
4.03
4.27
ESEER
-
4.46
4.83
4.82
4.55
4.82
kW
467.90
526.90
621.90
719.50
824.20
Heat. Input Power*
kW
116.60
124.10
146.70
176.40
194.20
Dimensions (H x L x D)
mm
Weight
kg
1
Heat. Capacity*
2
2
1700 x 1105 x 1465
1,670
1580 x 1105 x 2350
1,770
Capacity Control
Capacity Variation
2,500
%
Number of Compressors
2,670
3
3
76
77
15 ~ 100
2
2
3
Cool. Water Output Temperature
°C
(-10 ˚C Optional) +5°C~ +15°C
Heat. Water Output Temperature
°C
+35°C ~ +45°C ~ (55°C)*3
Sound Power Level
2,580
Continuous Control
dB(A)
74
74
NOTES:
*1 Nominal cooling capacity is based on European Standard EN14511.
Cooled water input/output temperature: 12 / 7 °C
Cooling water input/output temperature: 30 / 35°C
*2 Nominal heating capacity is intended only for the Heat Pump operation option and
is based on the conditions set out below.
Cooled water input/output temperature: 12 / 7°C
Hot water input/output temperature (Condenser): 40 / 45°C
*3( ) in the event of high temperature option and Heat Pump operation option
75
4 Sound power values have been calculated according to the EUROVENT test.
Measurement taken at 1 m from the surface of the control panel and 1.5 m height from
floor level.
The above data have been measured in an anechoic chamber, and do not take into
account the reflected sound in the field.
Operative conditions:
Standard models: Chilled water input/output temperature 12/7°C, Condenser water
input/output Temperature 30°C/35°C.
- Low output temperature applications are not standard.
- High condensation temperature applications are not standard.
255
Industrial and Service Sector
Samurai
Cooling Only I Condenser-less
RCUE40~120CLG2
WIDE POWER RANGE
FROM 120KW TO 360KW
HIGH TECHNOLOGY PERFORMANCE
OF DOUBLE SCREW COMPRESSORS
CONTINUOUS CAPACITY CONTROL
which affords between 15 and 20% reduction in energy consumption compared to step
control systems.
LOW NOISE LEVEL
PRECISE CONTROL OF WATER OUTPUT
TEMPERATURE
EXCELLENT PERFORMANCE AT PARTIAL
LOADS
DOUBLE SCREW COMPRESSOR
256
HIGHLY RELIABLE WITH EXTREMELY LOW
NOISE LEVEL AND VIBRATION
REDUCED INSTALLATION SPACE
Thanks to painstaking design of each component, it is possible to achieve high cooling capacity per square metre of occupied surface.
GREAT EFFICIENCY WITH INSTALLATION
AND USE OF A CHILLING REMOTE CONDENSER.
Industrial and Service Sector
COOLING ONLY
RCUE40CLG2
Model
RCUE50CLG2
RCUE60CLG2
RCUE80CLG2
RCUE100CLG2
RCUE120CLG2
Cool. Capacity
kW
120
145
180
240
290
360
Cool. Input Power
kW
34.40
42.40
52.10
68.80
84.80
104.20
-
3.50
3.40
3.50
3.50
3.40
3.50
EER
Dimensions (H x L x D)
Weight
mm
kg
1562 x 1104 x 885
1562 x 1045 x 885
630
680
730
Capacity Control
Capacity Variation
1720 x 1104 x 1471
1,200
1380
2
2
72
74
Continuous Control
%
Number of Compressors
15 ~ 100
1
1
1
2
Cool. Water Output Temperature
°C
(-10 ˚C Optional) +5°C~ +15°C
Condensation Temperature
˚C
30 ~ 65
Sound Power Level
1,310
dB(A)
68
69
NOTES:
1 Nominal cooling capacity is based on European Standard EN14511.
Chilled water input/output temperature 12/7°C, Condensation Temperature 45°C.
2 Sound power values have been calculated according to the EUROVENT test.
Measurement taken at 1 m from the surface of the control panel and 1.5 m height
from floor level.
71
71
The above data have been measured in an anechoic chamber, and do not take into
account the reflected sound in the field.
Operative conditions:
Standard models: Chilled water input/output temperature 12/7°C, Condensation
Temperature 45°C.
- Low output temperature applications are not standard.
- High condensation temperature applications are not standard.
257