I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors 1 INTRODUCTION 2 The digital HMI, HDI, HCLA, HCA and SSI pressure sensors are calibrated and temperature compensated with an on-board ASIC, which provides a corrected digital pressure value. For the HDI, HCLA, HCA and SSI series an additional analog voltage output is available at the same time. The response time of the sensors depend on the adjusted internal resolution. For 12 bit it is typ. 0.5 ms. The HMI, HDI, HCLA, HCA and SSI pressure sensors are configured to comply with the I²C bus protocol. I²C BUS PROTOCOL 2.1 General characteristics Two lines, a serial data line (SDA) and a serial clock line (SCL), carry information between the devices connected to the bus (see Fig. 1). Any device with I²C compatible protocol can be attached to the bus. Both SDA and SCL are bidirectional lines, connected to a positive supply voltage via pull-up resistors (see section 4 Application Circuit). When the bus is free, both lines are HIGH. They can only be pulled LOW by the devices connected to the bus. The I²C bus is a simple, serial 8-bit oriented computer bus for efficient Inter-IC (acronym I²C) control. It provides good support for communication between different IC’s across short circuit-board distances, such as interfacing microcontrollers with various lowspeed peripheral devices. Each device connected to the bus is software addressable by a unique address and a simple master-slave relationship exists at all times. The I²C bus requires only two bi-directional bus lines, a serial data line (SDA) and a serial clock line (SCL). The data transfer rate is freely selectable and can be max. 400 kbit/s. SCL SDA Master Slave Fig. 1: Slave Slave Example of an I²C bus configuration E / 11155 / D 1/10 www.first-sensor.com www.sensortechnics.com I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors SDA Master-Transmitter Slave-Receiver SCL SDA Master-Receiver Slave-Transmitter SCL Fig. 2: I²C master-slave concept 2.2 Master-slave concept 2.3 Data validity The I²C bus uses a simple master-slave concept. The master initialises a data transfer (START command), generates the clock (SCL) signal and terminates the transfer (STOP command). Any device addressed by the master is considered a slave. Data is only valid during the HIGH period of the clock. During this HIGH period the data on the SDA line must be stable HIGH to transmit a “1” or stable LOW for a “0”. The HIGH or LOW state of the data line is only allowed to change when the clock signal on the SCL line is LOW (see Fig. 3). Masters and slaves can operate as either transmitters or receivers, depending on their function (see Fig. 2). The transmitter is the device that sends data to the bus. A transmitter can either put data on the bus on its own accord (master-transmitter), or in response to a request from the master (slave-transmitter). The receiver is the device that receives data from the bus. A receiver can either receive data on its own request (master-receiver) or in response to a request from the master (slavereceiver). NOTE: The digital HMI, HDI, HCLA, HCA and SSI pressure sensors are designed to work as slave-transmitters and will therefore only respond to requests from a master device. E / 11155 / D SDA SCL Data Data valid allowed to change Fig. 3: I²C bus data validity 2/10 www.first-sensor.com www.sensortechnics.com I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors 2.4 START (S) and STOP (P) conditions 2.5 Byte format Prior to any transaction on the bus, a START condition needs to be issued. The START condition acts as a signal to all connected IC’s that something is about to be transmitted on the bus. As a result, all connected devices will listen to the bus and the bus is considered to be busy. After a message has been completed, a STOP condition is sent by the master. In this way the master can notify that no further data will be received or sent. This is the signal for all devices that the bus is idle again. START and STOP conditions are always generated by the master. Every byte put on the SDA line must be 8-bits long. Data is transferred with the most significant bit (MSB) first and the other bits following down to bit 8, the least significant bit (LSB). As you can see in Fig. 5, the bit representing decimal number 128 will be transmitted first (MSB). The START condition is defined as a HIGH to LOW transition on the SDA line while SCL is HIGH. The STOP condition is defined as a LOW to HIGH transition on the SDA line while SCL is HIGH (see Fig. 4). SDA SCL START condition Fig. 4: STOP condition MSB D u al 0 Decimal Fig. 5: 1 1 0 1 1 0 1 128 64 32 16 8 4 2 1 I²C bus byte format 2.6 Addressing and data direction The first byte after the START condition determines which slave will be selected by the master. Each slave has a unique address to identify it on the bus. This address is 7 bits long followed by bit 8 which is the data direction bit (R/W) (see Fig. 6). A ‘0’ for the R/W bit indicates that the master wants to transmit information to a selected slave (WRITE), a ‘1’ indicates that the master requests information from the slave (READ). MSB LS B 7 bit address I²C bus START and STOP conditions b7 Fig. 6: E / 11155 / D LS B b6 b5 b4 b3 R/W b2 b1 b0 I²C bus address byte 3/10 www.first-sensor.com www.sensortechnics.com I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors When an address is sent, each device in the system compares the first seven bits after the START condition with its own address. If they match, the device considers itself addressed by the master as a slave-receiver or slavetransmitter, depending on the R/W bit. The 7-bit addressing allows 128 (27) different addresses on the same bus. Since 16 addresses are reserved (in the Phillips specification), in practice 112 addresses remain for communication on the bus. However, the total number of devices connected to the bus is limited by the maximum bus capacitance CSDA=400 pF. A slave address can be made-up of a fixed and a programmable part. Typically, the four most significant bits are fixed and assigned to specific categories of devices. The three least significant bits are programmable through hardware address pins allowing up to eight (23) devices of identical categories on the same I²C bus. 2.7 Acknowledge (ACK or A) Each byte sent on the bus has to be followed by an acknowledge bit issued from the receiver for correct receipt of data. The acknowledge also means that the device is ready to continue the data transfer. The master must generate an extra clock pulse for this purpose. The transmitter releases the SDA line (HIGH) during the acknowledge clock pulse. The receiver must pull down the SDA line so that it is stable LOW from the beginning (rising edge) of the acknowledge clock pulse until its end (LOW level after falling edge) (see Fig. 7). If the receiver does not want to receive a further byte it leaves the SDA line HIGH and a not acknowledge (NACK or A) will be sent. Now the master can terminate the transfer with a STOP condition. NOTE: The digital I²C bus pressure sensors of the HMI, HDI, HCLA, HCA and SSI series have a general preconfigured slave address (0x1111000b). By factory programming it is possible to define an additional secondary slave address for each individual device. According to I²C bus specification 127 different addresses are available. The sensor will then listen to both slave addresses. E / 11155 / D 4/10 www.first-sensor.com www.sensortechnics.com I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors Data from transmitter Data from receiver SCL 1 2-8 START condition Fig. 7: 9 ACK Acknowledge (ACK) on the I²C bus 2.8 Data transfer overview A complete data transfer is shown in Fig. 8. After the START condition, the slave address is sent. The data direction bit (R/W) determines whether it is a READ or WRITE transfer. The addressed slave acknowledges (ACK) the correct receipt of the first byte. Now an unrestricted number of data bytes can be transmitted, always followed by an acknowledgement. The data transfer is always terminated by a STOP condition generated by the master. If the master afterwards wishes to continue the communication, it has to generate a new START condition and initiate a new data transfer. SDA 1-7 8 Address R/W 9 1-8 9 1-8 9 ACK Data ACK Data NACK l SCL START condition Fig. 8: STOP condition Complete I²C bus data transfer E / 11155 / D 5/10 www.first-sensor.com www.sensortechnics.com I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors 3 DATA TRANSFER WITH HMI, HDI, HCLA, HCA AND SSI PRESSURE SENSORS Data Byte 1 Data Byte 2 X P14 P13 P12 P11 P10 P9 P8 P7 P6 P5 P4 P3 P2 P1 P0 Relevant data The digital HMI, HDI, HCLA, HCA and SSI pressure sensors are designed to work as slave-transmitters and will therefore only respond to requests from a master device. Fig. 10: Two data bytes containing the pressure value as a 15 bit information NOTE: With a SCL clock frequency of 400 kHz the exchange of the 2 data bytes containing the current pressure value takes about 40 µs. However, the internal sensor conversion cycle to obtain a new pressure value is 250 µs for 12 bit resolution. Therefore, if the sensors are not deactivated they will send up to 7 times the same digital pressure value. For further information please contact us. 3.1 Pressure reading To read out a pressure value the master generates a START condition and sends the sensors slave address (either the hard codeded addess 0x1111000bin or the secondary factory programmed address) followed by a READ command (R/W=1) (see Fig. 9). At the moment of the first acknowledge (A) from the sensor, the master-transmitter becomes a masterreceiver. The sensor starts to send two data bytes containing the current pressure value as a 15 bit information placed in the output registers of its ASIC (see Fig. 10). The master must acknowledge the reception of the first data byte. To terminate the pressure reading from the sensor the master sends a STOP condition. The sensor is also able to send pressure values “online”. That means if the master does not send a STOP condition but an acknowledge after the third exchanged byte the sensor-slave will go on sending the last available pressure value when it is clocked. 1 S Slave Address R/W A Data Byte 1 3.2 Optional temperature reading As an option the sensors can be factory configured to deliver an additional 15 bit temperature reading. This will then be transmitted as a 3rd and 4th byte after the pressure value. If there is an acknowledge sent after these two additional bytes the sensor will continue sending alternating pressure and temperature values until it is deactivated by a STOP condition. A Data Byte 2 generated by slave n Data Bytes A P Read out of n pressure values Read out of first pressure value generated by master A S = START condition Data Byte 1 = High Byte (MSB first) A = Acknowledge Data Byte 2 = Low Byte (LSB last) A = Not Acknowledge P = STOP condition Fig. 9: Readout of digital pressure information using I²C bus protocol E / 11155 / D 6/10 www.first-sensor.com www.sensortechnics.com I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors 3.3 Calculation of the actual pressure value from the digital pressure word For an actual digital pressure reading of P counts = 5080 counts hex = 20608 counts dec The following formulas show how to calculate the actual pressure value from the digital sensor output: Definitions: S = Sensitivity [counts/mbar] Outmax = Output @ max. pressure [counts] Outmin = Output @ min. pressure [counts] Pmax = Max. value of pressure range [mbar] Pmin = Min. value of pressure range [mbar] P = Pressure reading [mbar] Pcounts = Digital pressure reading [counts] Out max − Out min S= Pmax − Pmin P= Pcounts − Out min + Pmin S the actual pressure in mbar can be calculated from equation (2) to be P= 20608 counts − 1638 counts + 0 mbar = 36,18 mbar 524,28 counts / mbar This pressure reading is calculated with the typical calibration values, not taking into account that the individual sensor calibrations might differ within the tolerances specified in the HCLA data sheet. 3.4 Resolution of data (1) (2) The following example shows the calculation for a HCLA0050…U device (pressure range 0…50 mbar unidirectional). Please refer to the HCLA data sheet for the specified calibration values. Outmin = 0666 counts hex = 1638 counts dec Out max = 6CCC counts hex = 27852 counts dec Each temperature and pressure value will be transmitted as a 15 bit word. However, the actual resolution can be less than this depending upon how the internal A/D-converter is configured. Also internal calculations and signal windowing will reduce the effective resolution. The standard resolution for pressure measurement is set at 12 bits, which results in an effective resolution of 11 to 12 bits. For temperature measurement the limiting factor is the sensitivity of the sensing element. For further information please contact us. With equation (1) the sensitivity of the sensor gives S= 27852 counts − 1638 counts = 524,28 counts/mbar 50 mbar − 0 mbar E / 11155 / D 7/10 www.first-sensor.com www.sensortechnics.com I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors 3.5 Timing parameters Parameter Symbol Min. tBUF 1.3 tHD.STA 0.8 LOW period of SCL tLOW 1.3 HIGH period of SCL tHIGH 0.6 Setup time repeated START condition tSU.STA 1 Data hold time tHD.DAT 0 Data setup time tSU.DAT 0.2 Bus free time between STOP and START condition Hold time (repeated) START condition, to first clock pulse Typ. Max. Unit µs Rise time of both SDA and SCL tR 0.3 Fall time of both SDA and SCL tF 0.3 Setup time for STOP condition tSU.STO 0.6 Table 1: Timing parameters for I²C bus communication with HMI, HDI, HCLA, HCA and SSI pressure sensors tSU;DAT tHD;DAT tSU;STA tHD;STA tR tSU;STO tBUF tHD;STA tF SCL SDA tHIGH tLOW SCL SDA Fig. 11: I²C bus timing characteristics E / 11155 / D 8/10 www.first-sensor.com www.sensortechnics.com I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors Parameter Symbol Min. Typ. Max. Input high level 90 100 Input low level 0 10 Output low level Unit % of V s 10 Pull-up resistor Ω 500 Load capacitance @ SDA C SD A 400 Input capacitance @ SDA/SCL CI2C_IN 10 FSC L SCL clock frequency 100* pF 400 kHz * recommended Table 2: I²C bus communication parameters for HMI, HDI, HCLA, HCA and SSI pressure sensors 3.6 Communication parameters The maximum allowed communication speed on the bus depends on the configured internal clock frequency of the HMI, HDI, HCLA, HCA and SSI pressure sensors. It is 400 kHz in the standard configuration. If both digital and analog interfaces are used in parallel it is recommended to separate these lines as far as possible from each other. Further, decoupling capacitors of 220 nF between supply and ground and 15 nF between the analog output and ground are beneficial. It is important to place the capacitors as close to the pins as possible. 3.7 Signal noise due to communication 4 As the pulses transmitted on the two bus lines have very sharp edges, this can cause some electromagnetic interference. Especially for very low pressure values and small PCB designs, these spikes can influence the analog millivolt measurement of the sensor bridge and downgrade signal quality. NOTE: To prevent signal noise we recommend a min. clock frequency of 100 kHz (max. 400 kHz) and transmission breaks of min. 500 µs between two pressure readings. This is especially valid for low pressure devices up to 25 mbar. Please contact us for more information. APPLICATION CIRCUIT Both SCL and SDA lines have to be connected to a 5 V supply voltage via pull-up resistors RP as shown in Fig. 12. We recommend to use 1.5 kΩ resistors. Additionally, serial resistors RS of max. 240 Ω should be used in each communication line. +VS R P SCL SDA R P R S Sensor R S Fig. 12: I²C bus application circuit for HMI, HDI, HCLA, HCA and SSI pressure sensors E / 11155 / D 9/10 www.first-sensor.com www.sensortechnics.com I²C bus communication with digital HMI, HDI, HCLA, HCA and SSI pressure sensors 5 SAMPLE PROGRAM CODE byte byte_msb, byte_lsb; int16 pressure; // 8bit values // 16bit value // Set I2C unit to I2C master mode, clock speed 100 kHz and 7 bit addressing configureI2C (I2C_MASTER | CLK_SPEED_100KHZ | ADDRESSING_7BIT); // Set the target address of the sensor (0x78 = 120dec) I2C_set_target(0x78); // Send start condition for reading from sensor (slave) I2C_send_start_read(); // Read first (MSB) data byte and answer with ACK (continue communication) I2C_read (&byte_msb, SEND_ACK); // Read second (LSB) data byte and answer with NACK (end communication) I2C_read (&byte_lsb, SEND_NACK); // Send Stop condition I2C_send_stop(); // Put both values together pressure = ((int16)byte_msb << 8) | byte_lsb; 6 TROUBLESHOOTING 6.1 Sensor does not respond · For HDI, HCLA, HCA, SSI only: Check the analogue output signal of the sensor. If it responds to pressure changes the sensor works. Then, errors of the digital output can be limited to problems of the I²C bus. · Switch the supply voltage on and off in order to restart the sensor. · Check the acknowledge signals (ACK or NACK) and the STOP condition from the master in the application circuit. If the sensor has stopped the communication due to an error, it has to be restarted by power off and on. Please contact us for further information: 6.2 Sensor supplies unstable data · Have the advices regarding signal noise under point 3.7 been followed? E / 11155 / D www.sensortechnics.com/contact [email protected] 10/10 www.first-sensor.com www.sensortechnics.com