RR2 Polarity Reversal Relay Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS
RR2 Polarity Reversal
Relay Module
Specifications
Operating Voltage Range:
Maximum Operating Current:
Relay Contacts:
Operating Temperature Range:
Operating Humidity Range:
Dimensions:
Wire connections:
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
8.5 to 35 VDC
NOTE: In an alarm condition, a wiring-fault
25mA
trouble state may also register at the panel
2A at 35 VDC
when the RR2 is used.
0° to 55° C (32° to 131° F)
5% to 95% non-condensing
21⁄2″ x 21⁄2″ x 1″
18 AWG stranded, tinned, 16″ long
General Description
The RR2 polarity reversing relay module is intended for
use with 2-wire and 4-wire detectors with built-in sounder,
such as System Sensor 2100AT, 2112/24AT, 2112/24ATR
and 2112/24AITR, 501BH, and other compatible models. It
is designed to allow all the detectors in the same loop to
sound when one of the detectors goes into alarm.
WARNING
When calculating total current draw of the control panel,
remember to add current consumption (25mA) for the
power reversal relay module (RR2).
IMPORTANT: If the fire alarm output signal is coded, set
the switch on the RR2 to “OFF”. If the fire alarm output
signal is continuous, set the switch to “ON”.
The RR2 may be used with an alarm zone that provides
coded output for fire and continuous output for burglary.
By default the RR2 will only trigger when the alarm output
is coded. In this manner, smoke detectors will only sound
from the result of a fire, and not from a burglary alarm.
When the RR2 is used in this mode, the smoke detectors
must provide for coded alarm signals if required by the
specification.
Wiring
IMPORTANT: All polarities must be observed!
1. Connect the RR2 module trigger wire to the fire alarm
output terminals.
A. Alarm/Bell output: (Figures 1 and 2)
Connect the purple wire to the Alarm or Bell output.
B. Alarm relay, normally open contact: (Figures 3 and 4)
1. Connect one end of the alarm relay contact output
to positive auxiliary or detector power fire alarm
output.
2. Connect the purple wire to the other end of the
alarm relay contact output.
2. Connect the red and black wires to the panel auxiliary
or detector power (red to positive, black to negative).
3. 2-wire models
Connect the yellow and orange wires to the panel initiating circuit (yellow to positive, orange to negative).
4-wire models
Connect the yellow and orange wires to the panel detector power circuit (yellow to positive, orange to negative).
4. 2-wire models
Connect the brown and white wires to the smoke detector
initiating circuit (brown to positive, white to negative).
4-wire models
Connect the brown and white wires to the smoke detector power circuit (brown to positive, white to negative).
The RR2 can also be set to only trigger on continuous
alarm zone signals. When used in this mode, it will not
trigger from a coded fire alarm signal.
NOTICE: This manual shall be left with the owner/user of
this equipment.
NOTE: If your panel configuration does not match any of
the provided wiring diagrams, please contact System Sensor
technical services at 1-800-SENSOR2 for assistance.
Installation
Choose a mounting location in the control panel within
reach of the provided wire leads. Use a water/isopropyl
alcohol mixture (50/50) to clean the mounting surface.
Allow surface to dry and remove paper backing from the
Velcro and catch. Stick the Velcro in the panel and the catch
on the back of the module, then mount the module inside
the control panel. Route terminals to the appropriate terminals as noted below.
D500-44-00
1
I56-1683-02
NOTE: If your panel configuration does not match any of the following wiring diagrams, please contact System Sensor
technical services at 1-800-SENSOR2 for assistance. Please refer to Figures 5 and 6 for Ademco Vista panels and Figure
7 for DSC Power 832 panels.
Figure 1. 2-Wire system triggered from IAC/bell circuit:
UL LISTED
ALARM
CONTROL
PANEL
BELL/
ALARM
CIRCUIT
(positive signal
in alarm state)
INITIATING
CIRCUIT
PURPLE
T+
EOL
+
YELLOW
IN+
–
ORANGE
IN–
BROWN
OUT+
+
+
–
A+
A-
WHITE
OUT–
+
+
–
A+
A-
Power
Not
Used
Not
Used
+
+
AUX POWER
–
–
RED
PWR+
+
Power
RA400Z
RA400Z
BLACK
PWR–
–
S0124-00
NOTE: If optional Style A (Class B) wiring is used, a second RR2 module must be added to enable concurrent loop
polarity reversal.
Figure 2. 4-Wire system triggered from IAC/bell circuit:
UL LISTED
ALARM
CONTROL
PANEL
BELL/ALARM
CIRCUIT
(positive signal
in alarm state)
DETECTOR
POWER
PURPLE
T+
+
YELLOW
IN+
–
ORANGE
IN–
+
+
–
+
+
–
Power
WHITE
OUT–
Power
A
A
NC
C Aux
NO
A
A
NC
C Aux
NO
RED
PWR+
AUX POWER +
OR
DETECTOR
POWER –
INITIATING
CIRCUIT
BROWN
OUT+
BLACK
PWR–
EOL
+
–
S0125-00
Figure 3. 2-Wire system triggered from alarm relay contact:
UL LISTED
ALARM
CONTROL
PANEL
PURPLE
T+
ALARM
RELAY
(NO Contact)
INITIATING
CIRCUIT
EOL
+
YELLOW
IN+
–
ORANGE
IN–
BROWN
OUT+
+
+
–
A+
A-
WHITE
OUT–
AUX POWER
–
RED
PWR+
–
RA400Z
Power
Not
Used
Not
Used
+
+
+
+
–
A+
A-
Power
+
–
RA400Z
BLACK
PWR–
S0126-00
NOTE: If optional Style A (Class B) wiring is used, a second RR2 module must be added to enable concurrent loop
polarity reversal.
D500-44-00
2
I56-1683-02
Figure 4. 4-Wire system triggered from alarm relay contact:
UL LISTED
ALARM
CONTROL
PANEL
DETECTOR
POWER
+
YELLOW
IN+
–
ORANGE
IN–
AUX POWER +
OR
DETECTOR
POWER –
INITIATING
CIRCUIT
EOL RELAY
(shown energized)
PURPLE
T+
ALARM
RELAY
(NO Contact)
BROWN
OUT+
+
+
–
+
+
–
Power
WHITE
OUT–
Power
A
A
NC
C Aux
NO
A
A
NC
C Aux
NO
RED
PWR+
BLACK
PWR–
EOL
+
–
S0127-00
Connection Diagrams with Ademco Vista Panels
The connection diagrams enclosed show how to connect the 2100AT model smoke detector to the Vista panels using the
System Sensor power reversal relay module (RR2). Please make sure that the smoke detectors are connected properly to
the zones specified in the wiring diagrams for proper operation of the smoke detectors.
Figure 5. Connecting 2100AT smoke detectors to Ademco controls using RR2 module triggered from
bell/alarm circuit:
BELL/
ALARM
CIRCUIT
(positive signal
in alarm state)
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
VISTA-20
VISTA-40
VISTA-50P
VISTA-32FB
VISTA-100
VISTA-128FB
SYSTEM SENSOR
POWER REVERSAL
RELAY MODULE (RR2)
(MOUNT INSIDE CONTROL ENCLOSURE)
PURPLE
T+
EOL
2K OHMS
BROWN
2-WIRE
SMOKE
ZONE
+
YELLOW
–
ORANGE
+
+
–
A+
A-
WHITE
+
+
–
A+
A-
Power
Not
Used
Not
Used
+
+
+
–
RED
SYSTEM SENSOR
2100AT SMOKE DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
RA400Z
AUX POWER
–
BLACK
Power
Programming information:
•The supervisory feature for the
bell circuit must be turned off.
See applicable control manual
for procedure.
RR2 Configuration:
•Set switch on RR2 to “OFF”.
470Ω
1/2 WATT
–
SYSTEM SENSOR
2100AT SMOKE DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
RA400Z
S0128-00
Figure 6. Connecting 2100AT smoke detectors to Ademco controls using RR2 module triggered from
auxiliary relay:
NOT REQUIRED ON 5110XM
WHEN 5100XM JUMPER W3 INTACT
N.C.
AUXILIARY
RELAY
SYSTEM SENSOR
POWER REVERSAL
RELAY MODULE (RR2)
(MOUNT INSIDE CONTROL ENCLOSURE)
EOLR
2K OHMS
N.O.
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
5110XM
5140XM
VISTA-32FB
VISTA-100
VISTA-128FB
BROWN
2-WIRE
SMOKE
ZONE
+
–
+
+
–
A+
A-
YELLOW
ORANGE
WHITE
+
+
–
A+
A-
Power
Not
Used
Not
Used
+
+
+
AUXILIARY
POWER
OUTPUT –
RED
470Ω
1/2 WATT
–
RA400Z
BLACK
Power
SYSTEM SENSOR
2100AT SMOKE DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
–
RA400Z
SYSTEM SENSOR
2100AT SMOKE DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
Programming information:
•Program Auxiliary relay to
activate on alarms
•Assign Auxiliary relay as an
output for zones programmed
for fire alarm response only
(Types 9, 16, or 17)
RR2 Configuration:
•Set switch on RR2 to “ON”.
TAKE POWER FROM CONTROLS
AUXILIARY POWER OUTPUT ONLY
S0129-00
D500-44-00
3
I56-1683-02
Connection diagrams with DSC Power 832 Panels
Figure 7. Connecting 2112/24AT, 2112/24ATR, and 2112/24AITR smoke detectors to DSC Power 832 controls using RR2 module with PGM output:
DSC POWER 832
PGM1
PURPLE
RR2
BROWN
AUX (+)
PGM2
YELLOW
ORANGE
WHITE
5.6
KΩ*
AUX +
RED
AUX –
BLACK
+
+
–
+
+
–
Power
EOL
ZONE (+)
ZONE (COM)
Power
A
A
NC
C Aux
NO
A
A
NC
C Aux
NO
*NOTE: 5.6KΩ resistor must be rated for 1/4W or greater.
S0112-00
All smoke detectors on the 4-wire fire
zone will sound temporal 3 only from a
fire alarm event.
NOTE: •Program zone section attributes
for bell output to be pulsing.
•PGM2 must be programmed for
sensor reset.
•PGM1 must be programmed as
Burglary and Fire Bell Output (01)
with ON, ON, OFF attributes.
•RR2 switch must be set to OFF
(factory default setting).
Testing
Before testing, notify the proper authorities that the system
is undergoing maintenance and will temporarily be out of
service.
2. Initiate an alarm with one of the smoke detectors connected to the RR2 module using any approved test
method. In the alarm state, all the detectors connected
to the RR2 module must be sounding their sounders.
Test in accordance with NFPA 72 test methods, inspections,
and testing frequency.
3. Reset the system from the control panel. All smoke
detector sounders should be silent.
1. Confirm that all smoke detectors connected to the RR2
module(s) contain a sounder and the sounders are activated upon power reversal.
4. If the fire alarm panel also functions in burglary mode,
initiate a burglary alarm and ensure the smoke detectors
do not sound.
Three-Year Limited Warranty
System Sensor warrants its enclosed relay module to be free from defects
RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include
in materials and workmanship under normal use and service for a period
a note describing the malfunction and suspected cause of failure. The
of three years from date of manufacture. System Sensor makes no other
Company shall not be obligated to repair or replace units which are found
express warranty for this smoke detector. No agent, representative, dealer,
to be defective because of damage, unreasonable use, modifications, or
or employee of the Company has the authority to increase or alter the
alterations occurring after the date of manufacture. In no case shall the
obligations or limitations of this Warranty. The Company’s obligation of
Company be liable for any consequential or incidental damages for breach
this Warranty shall be limited to the repair or replacement of any part of
of this or any other Warranty, expressed or implied whatsoever, even if
the smoke detector which is found to be defective in materials or workthe loss or damage is caused by the Company’s negligence or fault. Some
manship under normal use and service during the three year period comstates do not allow the exclusion or limitation of incidental or consequenmencing with the date of manufacture. After phoning System Sensor’s toll
tial damages, so the above limitation or exclusion may not apply to you.
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
This Warranty gives you specific legal rights, and you may also have other
send defective units postage prepaid to: System Sensor, Repair Department,
rights which vary from state to state.
D500-44-00
4
I56-1683-02
© System Sensor 2003